PSR-SCP- 24DC/ESP4/2X1/1X2
-
Safety relays
2981020
Safety relay for SIL 3 high-demand and low-demand applications, also approved in accordance with EN 50156, DNV, and EN ISO 13849, emergency stop and safety door monitoring, 1-channel, 2 enabling current paths, 1 signal contact, plug-in screw terminal blocks, width: 22.5 mm
Free download available.
Downloads
Product details
Note on application | |
Note on application | Only for industrial use |
Product type | Safety relays |
Product family | PSRclassic |
Application | Emergency stop |
Process technology | |
Safety door | |
Mechanical service life | approx. 107 cycles |
Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Data management status | |
Article revision | 12 |
Times | |
Typical response time | typ. 60 ms (For Us manual, monitored start) |
60 ms (For Us autostart) | |
Typ. starting time with Us | 60 ms (At Us/on demand via A1) |
Typical release time | typ. 20 ms (At Us/on demand via A1) |
Restart time | < 1 s (Boot time) |
Recovery time | ≥ 1 s (following demand of the safety function) |
Maximum power dissipation for nominal condition | 16.12 W (At US = 26.4 V, IL² = 72 A², PTotal max= 1.72 W + 14.4 W) |
Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits | |
Rated insulation voltage | 250 V |
250 V | |
Rated surge voltage/insulation | See section “Insulation coordination” |
Digital: Logic (A1) | |
Description of the input | safety-related |
Number of inputs | 1 |
Input voltage range "1" signal | 20.4 V ... 26.4 V |
Inrush current | max. 1 A (typ. with US, Δt = < 10 ms) |
Filter time | max. 3 ms (Test pulse width of low test pulses) |
min. 200 ms (Test pulse rate for low test pulse) | |
No brightness test pulses / high test pulses permitted. | |
Max. permissible overall conductor resistance | 50 Ω |
Protective circuit | Suppressor diode |
Current consumption | 65 mA (typ. with US) |
Digital: Start circuit (Y2) | |
Description of the input | non-safety-related |
Number of inputs | 1 |
Input voltage range "1" signal | 20.4 V ... 26.4 V |
Inrush current | < 14 mA (typically with US at Y2, Δt - 10 ms) |
Filter time | No test pulses permitted |
Max. permissible overall conductor resistance | 50 Ω |
Protective circuit | Suppressor diode |
Current consumption | 0 mA (typically with US at Y2) |
Relay: Enabling current paths (13/14, 23/24) | |
Output description | 2 N/O contacts each in series, safety-related, floating |
Number of outputs | 2 |
Contact switching type | 2 enabling current paths |
Contact material | AgSnO2 |
Switching voltage | min. 10 V |
max. 250 V AC/DC | |
Switching capacity | min. 100 mW |
Inrush current | min. 10 mA |
max. 6 A | |
Switching capacity in accordance with IEC 60947-5-1 | 5 A (AC15) |
5 A (DC13) | |
Limiting continuous current | 6 A (Observe derating and load limit curve) |
Sq. Total current | 72 A2 (observe derating) |
Switching frequency | max. 0.5 Hz |
Mechanical service life | 107 cycles |
Interrupting rating (ohmic load) max. | Observe derating and load limit curve |
Maximum interrupting rating (inductive load) | Observe derating and load limit curve |
Output fuse | 10 A gL/gG |
4 A gL/gG (for low-demand applications) | |
Relay: Signaling current path (31/32) | |
Output description | 2 N/C contacts parallel, non-safety-related, floating |
Number of outputs | 1 |
Contact switching type | 1 signaling current path |
Contact material | AgSnO2 |
Switching voltage | min. 10 V AC/DC |
max. 250 V AC | |
Switching capacity | min. 100 mW |
Inrush current | min. 10 mA |
max. 6 A | |
Switching capacity in accordance with IEC 60947-5-1 | 1.5 A (AC15) |
2 A (DC13) | |
Limiting continuous current | 6 A |
Sq. Total current | 36 A2 (observe derating) |
Switching frequency | max. 0.5 Hz |
Mechanical service life | 107 cycles |
Interrupting rating (ohmic load) max. | Observe derating and load limit curve |
Maximum interrupting rating (inductive load) | Observe derating and load limit curve |
Output fuse | 6 A gL/gG |
Connection technology | |
pluggable | yes |
Conductor connection | |
Connection method | Screw connection |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Status display | LED (green) |
Operating voltage display | Green LED |
Width | 22.5 mm |
Height | 99 mm |
Depth | 114.5 mm |
Color (Housing) | yellow (RAL 1018) |
Housing material | Polyamide |
Safety data | |
Stop category | 0 |
Safety data: EN ISO 13849 | |
Category | 4 |
Performance level (PL) | e |
Safety data: IEC 61508 - High demand | |
Safety Integrity Level (SIL) | 3 |
Safety data: IEC 61508 - Low demand | |
Safety Integrity Level (SIL) | 3 |
Safety data: EN IEC 62061 | |
Safety Integrity Level (SIL) | 3 |
Ambient conditions | |
Degree of protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient temperature (operation) | -20 °C ... 55 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Maximum altitude | ≤ 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Shock | 15g |
Vibration (operation) | 10 Hz ... 150 Hz, 2g |
CE | |
Identification | CE-compliant |
Air clearances and creepage distances between the power circuits | |
Standards/regulations | DIN EN 60947-1 |
Mounting type | DIN rail mounting |
Mounting position | On horizontal and vertical DIN rail |
Item number | 2981020 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DN01 |
Product key | DNA161 |
Catalog page | Page 256 (C-6-2019) |
GTIN | 4017918911065 |
Weight per piece (including packing) | 183.05 g |
Weight per piece (excluding packing) | 152.86 g |
Customs tariff number | 85371098 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27371819 |
ECLASS-13.0 | 27371819 |
ECLASS-12.0 | 27371819 |
ETIM
ETIM 9.0 | EC001449 |
UNSPSC
UNSPSC 21.0 | 39122200 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | dd23503e-e0e0-475d-ae14-eaa0f4b647df |
EF3.0 Climate Change | |
CO2e kg | 9.711 kg CO2e |
Compatible products
Your advantages
Up to Cat. 4/PL e in accordance with ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
1-channel control
Safe isolation
With inrush current reduction, therefore suitable for coupling to failsafe controllers (PSR-ESP4)
PHOENIX CONTACT
586 Fulling Mill Road, Middletown, PA 17057