Key: 1 = Input circuit 2 = Voltage limitation 3 = Start circuit 4 = Control circuit channel 1 5 = Control circuit signal output 6 = Control circuit channel 2 7 = Start channel 1 and 2 8 = Channel 1 9 = Diagnostics K1, K2 ... K6 = Force-guided elementary relays
Safety relays - PSR-MC40-3NO-1DO-24DC-SP
2700570
Safety relay for emergency stop, safety doors and light grids up to SIL 3, Cat. 4, PL e, 1 or 2-channel operation, automatic or manual, monitored start, 3 enabling current paths, US = 24 V DC, pluggable Push-in terminal block
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Insulation characteristics
Overvoltage category
III
Times
Typical response time
< 175 ms (automatic start)
< 175 ms (manual, monitored start)
Typ. starting time with Us
< 250 ms (when controlled via A1)
Typical release time
< 20 ms (when controlled via A1 or S12 and S22.)
Recovery time
< 500 ms
Nominal operating mode
100% operating factor
Designation
A1/A2
Rated control circuit supply voltage US
20.4 V DC ... 26.4 V DC
Rated control circuit supply voltage US
24 V DC -15 % / +10 %
Rated control supply current IS
typ. 80 mA
Power consumption at US
typ. 1.92 W
Inrush current
5 A (Δt = 200 µs at Us)
Filter time
1 ms (at A1 in the event of voltage dips at Us)
Protective circuit
Surge protection; Suppressor diode
Protection against polarity reversal for rated control circuit supply voltage
Rated insulation voltage
250 V AC
Rated insulation voltage
250 V AC
Rated surge voltage/insulation
Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14) and enabling current path (23/24) and enabling current path (33/34) Basic insulation 4 kV between all current paths and housing
Digital: Sensor circuit (S12, S22)
Description of the input
safety-related sensor inputs
Number of inputs
2
Input voltage range "0" signal
0 V DC ... 5 V DC (for safe Off; at S12 and S22)
Input current range "0" signal
0 mA ... 2 mA (for safe Off; at S12 and S22)
Inrush current
< 20 mA (with Us/Ix to S12)
< 5 mA (with Us/Ix to S22)
Filter time
max. 1.5 ms (at S12, S22; test pulse width)
min. 7.5 ms (at S12, S22; test pulse rate)
Test pulse rate = 5 x Test pulse width
Concurrence
∞
Max. permissible overall conductor resistance
150 Ω
Protective circuit
Suppressor diode
Current consumption
< 5 mA (with Us/Ix to S12)
< 5 mA (with Us/Ix to S22)
Digital: Start circuit (S34)
Description of the input
non-safety-related
Number of inputs
1
Input voltage range "1" signal
20.4 V DC ... 26.4 V DC
Inrush current
typ. 200 mA
Max. permissible overall conductor resistance
150 Ω
Protective circuit
Suppressor diode
Current consumption
< 10 mA (at S34/24 V)
> -5 mA (at S34/0 V)
Relay: Enabling current paths (13/14, 23/24, 33/34)
Output description
safety-related N/O contacts
Number of outputs
3 (undelayed)
Contact type
3 enabling current paths
Contact material
AgSnO2
Switching voltage
min. 12 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Switching capacity
min. 60 mW
Inrush current
min. 3 mA
max. 6 A
Switching capacity according to IEC 60947-5-1
5 A (AC15)
4 A (DC13)
Limiting continuous current
6 A (observe derating)
Sq. Total current
48 A2 (observe derating)
Switching frequency
0.5 Hz
Mechanical service life
10x 106 cycles
Output fuse
6 A gL/gG (N/O contact)
4 A gL/gG (for low-demand applications)
Signal: M1
Output description
non-safety-related
Number of outputs
1 (digital, PNP)
Voltage
22 V DC (Us - 2 V)
Current
max. 100 mA
Maximum inrush current
500 mA (Δt = 1 ms at Us)
Short-circuit protection
no
Connection technology
pluggable
yes
Conductor connection
Connection method
Push-in connection
Conductor cross section solid
0.2 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve
0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross-section AWG
24 ... 16
Status display
3 x green LED
Operating voltage display
1 x green LED
Width
12.5 mm
Height
116.6 mm
Depth
114.5 mm
Housing material
Polyamide
Housing color
yellow
Safety data
Stop category
0
Safety data: EN ISO 13849
Category
4
Performance level (PL)
e (4 A DC13; 5 A AC15; 8760 switching cycles/year)
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL)
3
Probability of a hazardous failure per hour (PFHD)
1.5 x 10-9 (4 A DC13; 5 A AC15; 8760 switching cycles/year)
Proof test interval
240 Months
Duration of use
240 Months
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL)
3
Probability of a hazardous failure on demand (PFDAVG)
1.46 x 10-4
Proof test interval
60 Months
Duration of use
240 Months
Ambient conditions
Degree of protection
IP20
Min. degree of protection of inst. location
IP54
Ambient temperature (operation)
-40 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)
75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)
75 % (on average, 85% infrequently, non-condensing)
Shock
15g
Vibration (operation)
10 Hz ... 150 Hz, 2g
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 60947-5-1
Mounting type
DIN rail mounting
Assembly instructions
See derating curve
Mounting position
vertical or horizontal
Item number
2700570
Packing unit
1 pc
Minimum order quantity
1 pc
Sales Key
C18
Product Key
DNA181
Catalog Page
Page 223 (C-6-2019)
GTIN
4046356912532
Weight per Piece (including packing)
172.69 g
Weight per Piece (excluding packing)
139.89 g
Customs tariff number
85371098
Country of origin
DE
ECLASS
ECLASS-9.0
27371819
ECLASS-10.0.1
27371819
ECLASS-11.0
27371819
ETIM
ETIM 8.0
EC001449
UNSPSC
UNSPSC 21.0
39122200
EAC
Approval ID: RU C-DE.A*30.B.01082
UL Listed
Approval ID: FILE E 140324
cUL Listed
Approval ID: FILE E 140324
Functional Safety
Approval ID: 44-205-13755201
Functional Safety
Approval ID: 44-780-13755201
cULus Listed
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”