Safety device - PSR-MC31-2SDO-1DO-24DC-SP
1015503

Safety relay module for safety shut-off mats, switching strips, emergency stop, safety doors, and light grids up to SIL 3, Cat. 4, PL e, 1 or 2-channel operation, automatic or manual start, 2 safe HL outputs, 1 signal output, US = 24 V DC, pluggable Push-in terminal block

Downloads

Product Details




Product type Safety relays
Application Emergency stop
Safety door
Safety shut-off mats
Light grid
Insulation characteristics
Overvoltage category III
Times
Typical response time < 200 ms (automatic start)
< 175 ms (manual, monitored start)
Typ. starting time with Us < 200 ms (with Us when controlled via A1)
Response time < 10 ms (Take the extension of the response time into consideration if you switch several devices in sequence.)
Restart time < 250 ms (Boot time)
Recovery time 250 ms (following demand of the safety function)

Maximum power dissipation for nominal condition 3.1 W (UB = 30 V , IL1 = IL2 = 2.4 A)
Nominal operating mode 100% operating factor
Designation A1/A2
Rated control circuit supply voltage US 19.2 V DC ... 30 V DC
Rated control circuit supply voltage US 24 V DC -20 % / +25 % (provide external protection)
Rated control supply current IS typ. 54 mA (No load)
Power consumption at US typ. 1.3 W
Inrush current < 5 A (Δt = 200 µs at Us)
Filter time 1 ms (For the logic. At A1 in the event of voltage dips at Us )
Protective circuit Parallel protection against polarity reversal; Suppressor diode (Provide external protection, see safety notes. Fuse type: 5 A FF)
Rated insulation voltage 50 V
Rated insulation voltage 50 V AC
Rated surge voltage/insulation Basic insulation 4 kV between all current paths and housing

Digital: Sensor circuit (S10, S12, S22)
Description of the input safety-related sensor inputs
IEC 61131-2 type 3 (S10, S12) PNP (S22)
Number of inputs 3
Input voltage range "0" signal 0 V DC ... 5 V DC (S10, S12)
S22 open
Input voltage range "1" signal 11 V DC ... 30 V DC (S10, S12)
0 V ... 0 V (S22)
Input current range "0" signal 0 mA ... 2 mA (S10, S12)
Inrush current < 10 mA (Typically with US at S10/S12, Δt = 500 µs)
> -5 mA (typ. with US at S22, Δt = 500 µs)
Filter time max. 1.5 ms (Test pulse width of low test pulses)
Test pulse rate = 5 x Test pulse width
Does not apply for S22
Deactivate the switch-on pulses for safety applications.
Concurrence
Max. permissible overall conductor resistance 150 Ω
Protective circuit Suppressor diode
Current consumption 4 mA (S10, S12)
-4 mA (S22)
Digital: Start circuit (S34, S35)
Description of the input non-safety-related
Number of inputs 2
Input voltage range "1" signal 19.2 V DC ... 30 V DC
Inrush current < 10 mA (Typically with US, Δt < 100 ms)
Max. permissible overall conductor resistance 150 Ω
Protective circuit Suppressor diode
Current consumption < 7 mA (Typically with US at S34)
< 5 mA (Typically with US at S35)
Digital: External release (S36)
Description of the input safety-related
IEC 61131-2 type 3
Number of inputs 1
Input voltage range "0" signal 0 V DC ... 5 V DC
Input voltage range "1" signal 11 V DC ... 30 V DC
Input current range "0" signal 0 mA ... 2 mA
Inrush current < 10 mA (Δt = 500 µs)
Filter time max. 1.5 ms (Test pulse width of low test pulses)
Test pulse rate = 5 x Test pulse width
Max. permissible overall conductor resistance 150 Ω
Protective circuit Suppressor diode
Current consumption 7 mA

Digital: 14, 24
Output description Safety-related digital outputs
PNP, IEC 61131-2 Type 2
Number of outputs 2
Protective circuit Freewheeling circuit for inductive loads
Output voltage ≥ 23 V DC (Us - 1 V)
Leakage current max. 1 mA (in the safe state)
Ohmic load min. 12 Ω
Max. capacitive load max. 10 µF (2.4 A load)
max. 4.7 µF (1 A load)
Max. inductive load max. 1 H
Limitation of the voltage induced on circuit interruption max. 50 V
Output current max. 2.4 A
Inrush current max. 4.8 A (Δt = 10 ms)
Min. load current 2 mA
Switching frequency 1 Hz (Resistive, inductive, capacitive)
Output voltage when switched off < 5 V DC (in the safe state)
Signal: M1
Output description PNP
non-safety-related
Number of outputs 1
Voltage approx. 22 V DC (Us - 2 V)
Current max. 100 mA
Maximum inrush current 500 mA (Δt = 1 ms at Us)
Protective circuit Suppressor diode
Short-circuit protection Yes

Connection technology
pluggable yes
Conductor connection
Connection method Push-in connection
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross-section AWG 24 ... 16

Status display 3 x green LED
Operating voltage display 1 x green LED
Indication 1 x red LED

Width 12.5 mm
Height 116.6 mm
Depth 114.5 mm

Housing material Polyamide
Housing color yellow

Safety data
Stop category 0
Safety data: EN ISO 13849
Category 4
Performance level (PL) e
Safety data: IEC 61508 - High demand
Equipment type Type A
Safety Integrity Level (SIL) 3
Probability of a hazardous failure per hour (PFHD) 1.00 x 10-9
Proof test interval 240 Months
Duration of use 240 Months

Ambient conditions
Degree of protection IP20
Min. degree of protection of inst. location IP54
Ambient temperature (operation) -40 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 70 °C
Maximum altitude ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Shock 30g
Vibration (operation) 10 Hz ... 150 Hz, 5g

CE
Certificate CE-compliant

Air clearances and creepage distances between the power circuits
Standards/regulations DIN EN 50178, EN 60947-5-1

Mounting type DIN rail mounting
Assembly instructions See derating curve
Mounting position vertical or horizontal

Item number 1015503
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C18
Product Key DNA181
GTIN 4055626496467
Weight per Piece (including packing) 137.382 g
Weight per Piece (excluding packing) 104.382 g
Customs tariff number 85371098
Country of origin DE


ECLASS

ECLASS-9.0 27371819
ECLASS-10.0.1 27371819
ECLASS-11.0 27371819

ETIM

ETIM 8.0 EC001449

UNSPSC

UNSPSC 21.0 39122200

UL Listed

Approval ID: FILE E 140324

cUL Listed

Approval ID: FILE E 140324

Functional Safety

Approval ID: 44-780-15124315

Functional Safety

Approval ID: 44-205-15124315

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with IEC 62061
Low housing width of just 12.5 mm
Cascade input
Compatible with numerous signal generators
1 or 2-channel control
2 safe digital outputs, 1 digital signal output