PSR-TRISAFE-M relay output extension module with 4 safe relay output contacts (choice of 4 single-channel or 2 two-channel relay contacts), 4 signal outputs; up to SIL 3, Cat. 4/PL e, SIL 3, EN 50156, pluggable Push-in terminal block
DownloadsProduct type | Safety device |
Application | PSR-TRISAFE-M extension module |
Insulation characteristics | |
Overvoltage category | III |
Pollution degree | 2 |
Times | |
Response time | max. 50 ms |
Recovery time | < 10 s |
Maximum power dissipation for nominal condition | 3932 mW (up to 40°C ambient temperature, at m = 4, n = 4, Iload = 4 A, Isignal = 50 mA) |
1532 mW (up to 55°C ambient temperature, at m = 4, n = 4, Iload = 1 A, Isignal = 50 mA) | |
Nominal operating mode | 100% operating factor |
Interfaces | DIN rail TBUS for connection to the master module, supplied as standard |
Rated control circuit supply voltage US | 18 V DC ... 30 V DC (Incl. all tolerances, incl. residual ripple) |
Rated control circuit supply voltage US | 24 V DC (Electrical supply via PSR-TBUS) |
Rated control supply current IS | Electrical supply via PSR-TBUS |
74 mA (At 24 V DC, relay outputs set) | |
54 mA (At 24 V DC, relay outputs not set) | |
Protective circuit | Yes, within the scope of the operating voltage limits |
Status display | 1 x green LED, 1 x red LED |
Rated insulation voltage | 250 V AC |
Rated surge voltage/insulation | 4 kV / basic insulation between output contact current paths (13/14, 23/24, 33/34, 43/44); 6 kV / safe isolation, reinforced insulation between output contact current paths (13/14, 23/24, 33/34, 43/44) and the other circuits |
Maximum switching voltage | 250 V AC/DC |
24 V DC | |
Minimum switching voltage | 5 V AC/DC |
Limiting continuous current | 4 A (see derating curve) |
Maximum inrush current | 6 A |
Inrush current, minimum | 5 mA |
Switching capacity (3600/h cycles) | 3 A (230 V (AC 15)) |
5 A (24 V (DC13)) | |
Output fuse | 6 A gL/gG |
Response time | max. 50 ms |
Relay | |
Output description | Relay contacts, safety-related N/O contacts |
Number of outputs | 4 (Single-channel) |
2 (Two-channel, connected in pairs) | |
Contact type | 4 relay output contacts |
Contact material | AgSnO2 (From HW03) AgCuNi +0.2 ... 0.4 μm Au (up to HW02) |
Switching voltage | min. 12 V AC/DC (as of HW 03) |
min. 5 V AC/DC (Up to HW02) | |
max. 250 V AC/DC | |
Switching current | min. 3 mA (as of HW 03) |
min. 5 mA (Up to HW02) | |
Switching capacity | min. 60 mW |
Limiting continuous current | 4 A (see to derating) |
Mechanical service life | 10x 106 cycles |
Output fuse | 6 A (gL / gG) |
4 A (gL/gG for low-demand applications) | |
Status display | 4 x green LEDs |
Signal | |
Output description | Digital |
Number of outputs | 4 |
Voltage | 24 V DC (Supply via A1/A2) |
Limiting continuous current | 50 mA |
Protective circuit | Yes, within the scope of the operating voltage limits |
Short-circuit protection | Yes |
Connection technology | |
pluggable | yes |
Conductor connection | |
Connection method | Push-in connection |
Conductor cross section solid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
Conductor cross-section AWG | 24 ... 16 |
Width | 22.5 mm |
Height | 112 mm |
Depth | 114.5 mm |
Housing material | Polyamide PA non-reinforced |
Housing color | yellow |
Safety data | |
Stop category | 0 |
Safety data: EN ISO 13849 | |
Category | 1 (1-channel parameterization) |
4 (2-channel parameterization) | |
Performance level (PL) | c (1-channel parameterization) |
e (2-channel parameterization) | |
Safety data: EN 50156 | |
Safety Integrity Level (SIL) | max. 3 (Reference IEC 61508) |
Safety data: IEC 61508 - High demand | |
Safety Integrity Level (SIL) | 1 (1-channel parameterization) |
3 (2-channel parameterization) | |
Proof test interval | 240 Months |
Duration of use | 240 Months |
Safety data: IEC 61508 - Low demand | |
Safety Integrity Level (SIL) | 1 (1-channel parameterization) |
Proof test interval | 60 Months |
Duration of use | 240 Months |
Ambient conditions | |
Degree of protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient temperature (operation) | -20 °C ... 55 °C |
Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Maximum altitude | max. 2000 m (See Appendix "Using PSR-TRISAFE modules at altitudes greater than 2000 m above sea level") |
Max. permissible humidity (storage/transport) | 75 % (On average, 85 % occasionally) |
Max. permissible relative humidity (operation) | 75 % (On average, 85 % occasionally) |
Shock (operation) | 10g (Δt = 11 ms, three shocks in each space direction) |
10g (Δt = 16 ms, continuous shock, 1000 shocks in each space direction) | |
Vibration (operation) | 2g |
Air pressure (operation) | 70 kPa ... 108 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
Air clearances and creepage distances between the power circuits | |
Standards/regulations | DIN EN 50178 |
Mounting type | DIN rail mounting |
Mounting position | On horizontal DIN rail |
Item number | 2986106 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales Key | C18 |
Product Key | DNA332 |
Catalog Page | Page 262 (C-6-2019) |
GTIN | 4046356536547 |
Weight per Piece (including packing) | 200 g |
Weight per Piece (excluding packing) | 140 g |
Customs tariff number | 85371098 |
Country of origin | DE |
ECLASS-9.0 | 27371819 |
ECLASS-10.0.1 | 27371819 |
ECLASS-11.0 | 27371819 |
ETIM 8.0 | EC001449 |
UNSPSC 21.0 | 39122200 |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |