Type 2 surge protection plug - VAL-MS 1000DC-PV-ST
2800624

Replacement plug for PV arrester combinations from the VAL-MS 1000DC-PV-... product range


Product Details




IEC test classification PV II
PV T2
EN type T2
IEC power supply system DC
Type Male
Product type Replacement plug
Installation location Interior
Installation location of the disconnect device Internal
Accessibility Accessible
SPD failure behavior OCFM (Open-Circuit Failure Mode)
Surge protection fault message optical
Insulation characteristics
Overvoltage category III
Pollution degree 2

Connection method pluggable

Dimensional drawing
Width 17.5 mm
Height 52.4 mm
Depth 55.3 mm
Horizontal pitch 1 Div.

Color jet black RAL 9005
Flammability rating according to UL 94 V-0
CTI value of material 600
Insulating material PA 6.6-FR
Material group I
Housing material PA 6.6-FR

Standby power consumption PC ≤ 25 mVA
Nominal discharge current In (8/20) µs 15 kA
Maximum discharge current Imax (8/20) µs 40 kA
Voltage protection level Up ≤ 1.9 kV
Residual voltage Ures ≤ 1.9 kV (at In)
≤ 1.5 kV (at 5 kA)
≤ 1.7 kV (at 10 kA)
≤ 2 kV (at 20 kA)
≤ 2.3 kV (at 30 kA)
≤ 2.5 kV (at 40 kA)
Response time tA ≤ 25 ns
Protective circuit DC voltage side (DC)
Open circuit voltage UOCSTC ≤ 487.5 V DC
Maximum discharge current Imax (8/20) µs 40 kA
Response time tA ≤ 25 ns
Insulation resistance Riso > 5 GΩ (at 500 V DC)
Nominal discharge current In (8/20) µs 15 kA
Continuous operating current ICPV < 20 µA
Maximum continuous operating voltage UCPV 585 V DC
Short-circuit current rating ISCPV 2000 A
Residual voltage Ures ≤ 1.9 kV (at In)
≤ 1.5 kV (at 5 kA)
≤ 1.7 kV (at 10 kA)
≤ 2 kV (at 20 kA)
≤ 2.3 kV (at 30 kA)
≤ 2.5 kV (at 40 kA)
Voltage protection level Up ≤ 1.9 kV
Standby power consumption PC ≤ 25 mVA

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 7.5g (5-500 Hz/2.5 h/XYZ)

UL specifications
Maximum continuous operating voltage MCOV 1170 V DC
Short-circuit current rating (SCCR) 50 kA
Voltage protection rating VPR 3 kV
Nominal discharge current In 10 kA
Mode of protection (L+) - (L-)
(L+) - G
(L-) - G
Nominal voltage 1170 V DC
Power distribution system DC PV
SPD Type 1CA

Standards/specifications EN 61643-31
Standards/specifications IEC 61643-31

Mounting type on base element

Item number 2800624
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C06
Product Key CL1324
Catalog Page Page 73 (C-4-2019)
GTIN 4046356615099
Weight per Piece (including packing) 76.1 g
Weight per Piece (excluding packing) 73 g
Customs tariff number 85363030
Country of origin CN


ECLASS

ECLASS-9.0 27130890
ECLASS-10.0.1 27130890
ECLASS-11.0 27130890

ETIM

ETIM 8.0 EC002496

UNSPSC

UNSPSC 21.0 39121620

cUL Recognized

Approval ID: FILE E 330181

UL Recognized

Approval ID: FILE E 330181

EAC

Approval ID: RU C-DE.*09.B.00169

KEMA-KEUR

Approval ID: 71-123544 REV.2

IECEE CB Scheme

Approval ID: NL-81006/A1

CCA

Approval ID: NTR-NL 7937
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

cULus Recognized


China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Compatible Products



Your advantages

Increased safety, thanks to compliance with standard EN 50539-11
Reliable contact, thanks to integrated rotating latch
Easy replacement, thanks to plug-in arresters
Optimum inverter protection, thanks to low protection level
Efficient replacement of defective plugs, thanks to visual status indicator
Protection against mismatching, thanks to keyed plugs and base elements