Type 1 surge protection plug - FLT-SEC-P-T1-N/PE-350/100-P
2905473

Replacement plug for lightning current arresters from the FLASHTRAB SEC product range, for the N-PE path.


Product Details




IEC test classification I / II
I
T1 / T2
T1
EN type T1 / T2
T1
IEC power supply system TT
Type Male
Product type Replacement plug
Number of positions 1
Surge protection fault message optical
Insulation characteristics
Overvoltage category III
Pollution degree 2

Nominal frequency fN 50 Hz (60 Hz)

Connection method pluggable

Dimensional drawing
Width 35.5 mm
Height 46.4 mm
Depth 59.4 mm
Horizontal pitch 2 Div.

Color light grey RAL 7035
Flammability rating according to UL 94 V-0
CTI value of material 600
Insulating material PA6.6-FR 20% GF
PBT-FR
Material group I
Housing material PA 6.6-FR 20 % GF
PBT-FR

Mode of protection N-PE
Direction of action N-PE
Nominal voltage UN 240 V AC (TN - only N-PE)
240 V AC (TT - only N-PE)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous voltage UC 350 V AC
Residual current IPE ≤ 0.01 mA
Nominal discharge current In (8/20) µs 100 kA
Impulse discharge current (10/350) µs, charge 50 As
Impulse discharge current (10/350) µs, specific energy 2500 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp 100 kA
Follow current interrupt rating Ifi 100 A (350 V AC)
Voltage protection level Up ≤ 1.5 kV
Residual voltage Ures ≤ 1.5 kV (at In)
≤ 1 kV (at 10 kA)
≤ 0.9 kV (at 5 kA)
≤ 0.8 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs ≤ 1.5 kV
TOV behavior at UT 1200 V AC (200 ms / withstand mode)
Response time tA ≤ 100 ns

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 5g (5 - 500 Hz/2.5 h/X, Y, Z)

UL specifications
Mode of protection N-G
Nominal frequency 50/60 Hz
SPD Type 1CA

Standards/specifications IEC 61643-11
Standards/specifications EN 61643-11

Mounting type on base element

Item number 2905473
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C06
Product Key CL1171
Catalog Page Page 37 (C-4-2019)
GTIN 4046356950725
Weight per Piece (including packing) 219.7 g
Weight per Piece (excluding packing) 219.7 g
Customs tariff number 85363030
Country of origin DE


ECLASS

ECLASS-9.0 27130890
ECLASS-10.0.1 27130890
ECLASS-11.0 27130890

ETIM

ETIM 8.0 EC002496

UNSPSC

UNSPSC 21.0 39121600

cUL Recognized

Approval ID: FILE E 330181

UL Recognized

Approval ID: FILE E 330181

IECEE CB Scheme

Approval ID: NL-58252

EAC

Approval ID: RU C-DE.*09.B.00169

CCA

Approval ID: NTR-NL 7736
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

KEMA-KEUR

Approval ID: 71-106983

DNV GL

Approval ID: TAE000040S
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

IECEE CB Scheme

Approval ID: NL-56588

KEMA-KEUR

Approval ID: 71-106982

CCA

Approval ID: NTR-NL 7726
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

cULus Recognized


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Surge protection family for universal use with optimum energy coordination from the lightning current arrester to the device protection
Easy to maintain due to consistently pluggable protection modules
Excellent level of information provided by mechanical/visual status indicator and remote indication contact
Optimum protective effect in the event of high-energy lightning currents, thanks to spark gap technology with low residual voltage characteristic
Low voltage protection level for direct protection of end devices in the main distribution area