DNV GL
Approval ID: TAE0000196Nominal Voltage UN | Nominal Current IN | Cross Section AWG | Cross Section mm2 | |
---|---|---|---|---|
PLC-INTERFACE, consisting of DIN-rail-mountable basic terminal block in 14 mm with screw connection and plug-in relay with 10 A power contact, 1 changeover contact, 12 V DC input voltage. Approved according to ATEX/IECEx (Zone 2) and Ex Zone Class I, Div. 2.
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product type | Relay Module |
Product family | PLC-INTERFACE |
Application | High continuous currents |
potentially explosive areas | |
Operating mode | 100% operating factor |
Mechanical service life | 3x 107 cycles |
Insulation characteristics | |
Insulation | Safe isolation, reinforced insulation |
Insulation characteristics: Standards/regulations | |
Insulation | Safe isolation, reinforced insulation |
Overvoltage category | III |
Pollution degree | 3 |
Maximum power dissipation for nominal condition | 0.4 W |
Test voltage (Winding/contact) | 4 kV AC (50 Hz, 1 min., winding/contact) |
Standards/regulations | |
Rated insulation voltage | 250 V AC |
Rated surge voltage | 6 kV |
Coil side | |
Nominal input voltage UN | 12 V DC |
Input voltage range | 10.3 V DC ... 16.8 V DC (20 °C) |
Typical input current at UN | 33 mA |
Typical response time | 8 ms |
Typical release time | 10 ms |
Protective circuit | Reverse polarity protection; Polarity protection diode |
Freewheeling diode; Freewheeling diode | |
Operating voltage display | Yellow LED |
Switching | |
Contact type | 1 changeover contact |
Type of switch contact | Single contact |
Drive and function | monostable |
Drive (polarity) | bipolar |
Contact material | AgNi |
Maximum switching voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
Minimum switching voltage | 12 V AC/DC (10 mA) |
Limiting continuous current | 10 A |
6 A (value applies to connections 12. If connections 12 are bridged, the normal value applies.) | |
Maximum inrush current | 30 A (300 ms) |
Min. switching current | 10 mA (12 V) |
Interrupting rating (ohmic load) max. | 240 W (at 24 V DC) |
58 W (at 48 V DC) | |
48 W (at 60 V DC) | |
50 W (at 110 V DC) | |
80 W (at 220 V DC) | |
2500 VA (for 250 V AC) | |
Interrupting rating (ohmic load) max. bridged | 144 W (for 24 V DC. Value applies to connections 12. If connections 12 are bridged, the normal value applies.) |
1500 VA (for 250 V AC. Value applies to connections 12. If connections 12 are bridged, the normal value applies.) | |
Switching capacity | 2 A (at 24 V, DC13) |
0.2 A (at 110 V, DC13) | |
0.2 A (at 250 V, DC13) | |
6 A (at 24 V, AC15) | |
6 A (at 120 V, AC15) | |
6 A (at 250 V, AC15) |
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
0.2 mm² ... 2.5 mm² (Single ferrule) | |
2x 0.5 mm² ... 1.5 mm² (TWIN ferrule) | |
Conductor cross section AWG | 26 ... 14 |
Tightening torque | 0.6 Nm ... 0.8 Nm |
Width | 14 mm |
Height | 80 mm |
Depth | 94 mm |
Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions | |
Degree of protection Relay | RT III (Relay) |
IP20 (Relay base) | |
Ambient temperature (operation) | -20 °C ... 60 °C (UL) |
-40 °C ... 60 °C (ATEX / IECEx) | |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
CE | |
Certificate | CE-compliant |
ATEX | |
Identification | II 3G Ex ec nC IIC T4 Gc |
Certificate | IBExU16ATEXB015 X |
IECEx | |
Identification | Ex ec nC IIC T4 Gc |
Certificate | IECEx IBE 16.0029X |
UKCA Ex (UKEX) | |
Identification | II 3 G Ex ec nC IIC T4 Gc |
Certificate | PxCIF21UKEX2909514X |
UL, USA | |
Identification | Class I, Zone 2, AEx nA nC IIC T6 |
UL, USA / Canada | |
Identification | Class I, Div. 2, Groups A, B, C, D |
UL, Canada | |
Identification | Class I, Zone 2, Ex nA nC IIC Gc T6 X |
Corrosive gas test | |
Identification | ISA-S71.04. G3 Harsh Group |
EN 60068-2-60 |
Standards/regulations | |
Standards/regulations | IEC 60947-5-1 |
EN 60079-0 | |
EN 60079-7 | |
EN 60079-15 |
Mounting type | DIN rail mounting |
Assembly instructions | in rows with zero spacing |
Mounting position | any |
Item number | 2909518 |
Packing unit | 1 pc |
Minimum order quantity | 10 pc |
Sales Key | C05 |
Product Key | CK621A |
Catalog Page | Page 387 (C-5-2019) |
GTIN | 4055626363462 |
Weight per Piece (including packing) | 78.6 g |
Weight per Piece (excluding packing) | 70.63 g |
Customs tariff number | 85364190 |
Country of origin | DE |
ECLASS-10.0.1 | 27371601 |
ECLASS-9.0 | 27371601 |
ECLASS-11.0 | 27371601 |
ECLASS-12.0 | 27371601 |
ECLASS-13.0 | 27371601 |
ETIM 8.0 | EC001437 |
UNSPSC 21.0 | 39122300 |
Nominal Voltage UN | Nominal Current IN | Cross Section AWG | Cross Section mm2 | |
---|---|---|---|---|
REACh SVHC | Lead 7439-92-1 |
Hexahydromethylphthalic anhydride | |
China RoHS | Environmentally Friendly Use Period = 50 years |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |