PLC-RPT- 60DC/21HC - Relay Module
2900295

PLC-INTERFACE for high continuous currents, consisting of PLC-BPT.../21 HC basic terminal block with Push-in connection and plug-in miniature relay, for mounting on DIN rail NS 35/7,5, limiting continuous current up to 10 A, 1 changeover contact, input voltage 60 V DC


Product Details





Product type Relay Module
Product family PLC-INTERFACE
Application High continuous currents
Operating mode 100% operating factor
Mechanical service life 3x 107 cycles
Insulation characteristics
Insulation Safe isolation, reinforced insulation
Insulation characteristics
Insulation Safe isolation, reinforced insulation
Overvoltage category III
Pollution degree 3

Maximum power dissipation for nominal condition 0.6 W
Rated surge voltage 6 kV

Coil side
Nominal input voltage UN 60 V DC
Input voltage range 51 V DC ... 84 V DC (20 °C)
Typical input current at UN 10 mA
Typical response time 8 ms
Typical release time 10 ms
Protective circuit Reverse polarity protection; Polarity protection diode
Surge protection; Freewheeling diode
Operating voltage display Yellow LED

Switching
Contact type 1 changeover contact
Type of switch contact Single contact
Drive and function monostable
Drive (polarity) bipolar
Contact material AgNi
Maximum switching voltage 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage 12 V (10 mA)
Limiting continuous current 10 A
6 A (value applies to connections 12. If connections 12 are bridged, the normal value applies.)
Maximum inrush current 30 A (300 ms)
Min. switching current 10 mA (12 V)
Interrupting rating (ohmic load) max. 240 W (at 24 V DC)
58 W (at 48 V DC)
48 W (at 60 V DC)
50 W (at 110 V DC)
80 W (at 220 V DC)
2500 VA (for 250 V AC)
Interrupting rating (ohmic load) max. bridged 144 W (for 24 V DC. Value applies to connections 12. If connections 12 are bridged, the normal value applies.)
1500 VA (for 250 V AC. Value applies to connections 12. If connections 12 are bridged, the normal value applies.)
Switching capacity 2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.2 A (at 250 V, DC13)
6 A (at 24 V, AC15)
6 A (at 120 V, AC15)
6 A (at 250 V, AC15)

Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.14 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG 26 ... 14

Width 14 mm
Height 80 mm
Depth 94 mm

Flammability rating according to UL 94 V0 (Housing)

Ambient conditions
Degree of protection Relay RT II (Relay)
IP20 (Relay base)
Ambient temperature (operation) -40 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C

Corrosive gas test
Identification ISA-S71.04. G3 Harsh Group
EN 60068-2-60

Standards/regulations IEC 60947-5-1

Mounting type DIN rail mounting
Assembly instructions in rows with zero spacing
Mounting position any

Item number 2900295
Packing unit 1 pc
Minimum order quantity 10 pc
Sales Key C05
Product Key CK623A
Catalog Page Page 384 (C-5-2019)
GTIN 4046356507066
Weight per Piece (including packing) 72.67 g
Weight per Piece (excluding packing) 64.4 g
Customs tariff number 85364190
Country of origin DE


ECLASS

ECLASS-9.0 27371601
ECLASS-10.0.1 27371601
ECLASS-11.0 27371601
ECLASS-12.0 27371601
ECLASS-13.0 27371601

ETIM

ETIM 8.0 EC001437

UNSPSC

UNSPSC 21.0 39122300

cUL Recognized

Approval ID: FILE E 238705

UL Recognized

Approval ID: FILE E 238705

EAC

Approval ID: TR_TS_D_00573_c

DNV GL

Approval ID: TAE0000196
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

EAC

Approval ID: RU*C-DE.*08.B.00010

UL Listed

Approval ID: FILE E 172140

cUL Listed

Approval ID: FILE E 172140

RC FRT

Approval ID: B.00094

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
Hexahydromethylphthalic anhydride
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products



Your advantages

Long electrical service life thanks to 16 A relay
All common input voltages of 12 V DC ... 230 V AC
Efficient connection to system cabling using V8 adapter
Safe isolation according to DIN EN 50178 between coil and contact
Max. continuous current of 10 A
Functional plug-in bridges