PLC-RPT-120UC/21-21/SO46 - Relay Module
1136244

PLC-INTERFACE for protection against interference currents or interference voltages on the control side. Consisting of basic terminal block with Push-in connection and plug-in miniature relay with power contact up to 2x 8 A, 2 changeover contacts, 120 V AC input voltage


Product Details





Notes on operation The PLC-ATP partition plate must be installed for voltages greater than 250 V (L1, L2, L3) between identical terminal blocks on adjacent modules.
Notes on operation The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
Notes on operation The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
Assembly instruction: The PLC-ATP separating plate is required at the start and end of every PLC terminal strip.

Product type Relay Module
Product family PLC-INTERFACE
Application Filter to prevent interference
Operating mode 100% operating factor
Mechanical service life approx. 3x 107 cycles
Insulation characteristics
Insulation Basic insulation
Insulation characteristics: Air clearances and creepage distances between the power circuits
Insulation Basic insulation
Overvoltage category III
Pollution degree 3

Test voltage (Winding/contact) 4 kVrms (50 Hz, 1 min., winding/contact)
Air clearances and creepage distances between the power circuits
Rated insulation voltage 250 V AC
Rated surge voltage 4 kV (Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths)

Coil side
Nominal input voltage UN 120 V AC
110 V DC
Input voltage range 94.8 V AC ... 168 V AC (20 °C)
93.5 V DC ... 168.3 V DC (20 °C)
Mains frequency 50/60 Hz
Typical input current at UN 6 mA (50 Hz)
7 mA (60 Hz)
Typical response time 7 ms
Typical release time 10 ms
Typical release voltage 16 V AC
Coil voltage 110 V DC
Protective circuit RC element
Bridge rectifier
Status display Yellow LED

Switching
Contact type 2 changeover contacts
Type of switch contact Single contact
Drive and function monostable
Drive (polarity) bipolar
Contact material AgNi
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 5 V (10 mA)
Limiting continuous current 6 A
Maximum inrush current 15 A (300 ms)
Min. switching current 10 mA (5 V)
Interrupting rating (ohmic load) max. 144 W (24 V DC)
96 W (48 V DC)
60 W (60 V DC)
44 W (110 V DC)
57 W (220 V DC)
1500 VA (250 V AC)
Switching capacity min. 0.12 W

Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.14 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG 26 ... 14

Width 14 mm
Height 80 mm
Depth 94 mm

Ambient conditions
Degree of protection Relay base IP20 (Relay base)
RT III (Relay)
IP54 (Installation location)
Ambient temperature (operation) -40 °C ... 55 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m

Corrosive gas test
Identification ISA-S71.04. G3 Harsh Group
EN 60068-2-60

Air clearances and creepage distances between the power circuits
Standards/regulations IEC 60947-5-1

Mounting type DIN rail mounting
Assembly instructions in rows with zero spacing
Mounting position any

Item number 1136244
Packing unit 1 pc
Minimum order quantity 10 pc
Sales Key C05
Product Key CK623C
GTIN 4063151070687
Weight per Piece (including packing) 72.22 g
Weight per Piece (excluding packing) 56.1 g
Customs tariff number 85364900
Country of origin DE


ECLASS

ECLASS-9.0 27371601
ECLASS-10.0.1 27371601
ECLASS-11.0 27371601
ECLASS-12.0 27371601
ECLASS-13.0 27371601

ETIM

ETIM 8.0 EC001437

UNSPSC

UNSPSC 21.0 39122300

cUL Recognized

Approval ID: FILE E 238705

UL Recognized

Approval ID: FILE E 238705

EAC

Approval ID: RU*C-DE.*08.B.00010

EAC

Approval ID: RU D-DE.B*00573/18

UL Listed

Approval ID: FILE E 172140

cUL Listed

Approval ID: FILE E 172140

DNV GL

Approval ID: TAE0000196
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
Hexahydromethylphthalic anhydride
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products