Power supply unit - MINI-SYS-PS-100-240AC/24DC/1.5
2866983

Please use the following item in new systems: 2904614
Primary-switched MINI POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A


Product Details


MINI POWER power supplies for MCR technology
In measurement and control technology (MCR), modular electronics housing has become the industry standard. MINI POWER is the power supply unit to go with it. The devices are flexible, thanks to special voltages and special versions.



Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
Input voltage range AC 85 V AC ... 264 V AC
Voltage type of supply voltage AC
Inrush current < 15 A (0.6 A2s)
Inrush current integral (I2t) 0.6 A2s
AC frequency range 45 Hz ... 65 Hz
Mains buffering time typ. 35 ms (120 V AC)
typ. 150 ms (230 V AC)
Current consumption 0.75 A (120 V AC)
0.45 A (230 V AC)
Nominal power consumption 90 VA
Protective circuit Transient surge protection; Varistor
Typical response time < 0.5 s
Input fuse 3.15 A (slow-blow, internal)
Permissible backup fuse B6 B10 B16
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)

Efficiency > 84 % (for 230 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Nominal output current (IN) 1.5 A (-25 °C ... 60 °C)
Output current limit 7 A (in the event of a short-circuit)
POWER BOOST (IBoost) 2 A (-25 °C ... 40 °C permanent)
Derating 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 30 V DC
Max. capacitive load unlimited
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 40 mVPP (20 MHz)
Short-circuit-proof yes
Output power 36 W
Peak switching voltages idling < 20 mVPP (20 MHz)
Peak switching voltages nominal load < 20 mVPP (20 MHz)
Maximum no-load power dissipation 1.5 W
Power loss nominal load max. 6.5 W
Rise time < 2 ms
Connection in parallel yes, for redundancy and increased capacity.
Maximum of 2 devices for redundancy on DIN rail connector.
Connection in series No
Signal: DC OK floating
Output description UOUT > 21.5 V: Contact closed
Maximum switching voltage ≤ 30 V AC/DC
Output voltage 30 V AC/DC
Continuous load current ≤ 1 A

Input
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Signal
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

Types of signaling LED
Relay contact
Operating voltage display Green LED
Signal output: DC OK floating
Status display "DC OK" LED green
Note on status display UOUT > 21.5 V: LED lights up

Insulation voltage input/output 4 kV (type test)
3 kV (routine test)

Product type Power supply
MTBF (IEC 61709, SN 29500) > 2789000 h (40 °C)
Insulation characteristics
Protection class II (in closed control cabinet)
Overvoltage category III
Degree of pollution 2

Width 35 mm
Height 99 mm
Depth 95 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm

Mounting type DIN rail mounting
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
Mounting position horizontal DIN rail NS 35, EN 60715
With protective coating No

Color green
Housing material Plastic
Type of housing Polyamide PA, color: green

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.

Rail applications EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage EN 60950-1 (SELV) and EN 60204 (PELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Conformity/Approvals
SIL in accordance with IEC 61508 0
Performance level according to ISO 13849 without

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Noise emission EN 55011 (EN 55022)
Noise immunity EN 61000-6-2:2005
Electrostatic discharge
Standards/regulations EN 61000-4-2
Housing Level 3
Electrostatic discharge
Contact discharge 6 kV
Discharge in air 8 kV
Comments Criterion B
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 2 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (level 4 - asymmetrical: conductor to ground)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
Signal 1 kV (level 2 - asymmetrical: conductor to ground)
Comments Criterion B
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S Level 3 - asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V
Voltage dips
Standards/regulations EN 61000-4-11
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential

Item number 2866983
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C14
Product Key CMPM13
Catalog Page Page 276 (C-4-2019)
GTIN 4017918960650
Weight per Piece (including packing) 288 g
Weight per Piece (excluding packing) 250 g
Customs tariff number 85044030
Country of origin CN


ECLASS

ECLASS-9.0 27040701
ECLASS-10.0.1 27040701
ECLASS-11.0 27040701

ETIM

ETIM 8.0 EC002540

UNSPSC

UNSPSC 21.0 39121000

cUL Recognized

UL Recognized

EAC

EAC

UL Listed

cUL Listed

EAC

cUL Listed

UL Listed

cULus Recognized

cULus Listed

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Easy-maintenance connection technology thanks to keyed COMBICON connectors
For supplying the supply voltage via the foot element (DIN rail connector) where AC voltages are available
100 V AC ... 240 V AC nominal input voltage range
24 V DC output voltage
For up to 60 MINI Analog modules
For up to 1.5 A, secondary
Status and error indication via diagnostic LEDs