MACX MCR-EX-AP-RPSS-I-IR-SP
-
Power/input isolating amplifier
1290776
Ex i-Feed and input signal conditioner with 2 limit value relays, feeds 2 or 3-conductor measuring transducer, transmits 1:1 passive or active 0 mA / 4 mA ... 20 mA input signals and has 2 configurable limit value outputs. HART-transparent, Standard configuration, 4-way isolation, Safety Integrity Level (SIL, IEC 61508): 2, Push-in connection
Free download available.
Downloads
Product details
General | Installation conditions influence the ambient temperature. Please refer to the “Control cabinet installation instructions”. |
General | Output behavior = input signal |
Product type | Repeater power supplies |
Product family | MACX Analog |
No. of channels | 1 |
No. of channels | 1 |
Electrical isolation | 4-way isolation |
Linearity error | ≤ 0.1 % |
Typical offset error | ≤ 0.1 % |
Signal transmission behavior | In = Out |
Temperature coefficient, typical | ≤ 0.1 % (10 K) |
Reverse polarity protection | yes |
Electrical isolation Input/output IEC/EN 60079-11 | |
Standards/regulations | IEC/EN 60079-11 |
Rated insulation voltage | 375 VPP |
Electrical isolation Input/power supply IEC/EN 60079-11 | |
Standards/regulations | IEC/EN 60079-11 |
Rated insulation voltage | 375 VPP |
Electrical isolation Input/error message output IEC/EN 60079-11 | |
Standards/regulations | IEC/EN 60079-11 |
Rated insulation voltage | 375 VPP |
Electrical isolation Input/limit value contact IEC/EN 60079-11 | |
Standards/regulations | IEC/EN 60079-11 |
Rated insulation voltage | 375 VPP |
Electrical isolation Output/supply | |
Test voltage | 350 V (50 Hz, 60 s) |
Electrical isolation Output/limit value contact | |
Test voltage | 350 V (50 Hz, 60 s) |
Electrical isolation Output/supply/error message output | |
Test voltage | 350 V (50 Hz, 60 s) |
Supply | |
Nominal supply voltage | 24 V DC |
Supply voltage range | 18 V ... 31.2 V |
Power dissipation | 1.5 W (RL 250 Ω) |
Power consumption | 2 W (20 mA) |
Signal: Repeater power supply operation | |
Description of the input | active and passive current input, intrinsically safe |
Input signal | Current |
Current input signal | 4 mA ... 20 mA (with HART) |
2 mA ... 22 mA (Function area) | |
Short-circuit current | ≤ 35 mA |
Line fault detection | < 3.6 mA (Line break) |
> 21 mA (Short circuit) | |
Non-load voltage | ≤ 26 V |
Signal: Signal conditioner operation | |
Description of the input | Passive current input, intrinsically safe |
Current input signal | 4 mA ... 20 mA (with HART) |
2 mA ... 22 mA (Function area) | |
Input resistance current input | > 250 Ω (for mA sources) |
Input current | ≤ 50 mA (for mA sources) |
Short-circuit current | ≤ 35 mA |
Line fault detection | < 3.6 mA (Line break) |
> 21 mA (Short circuit) | |
Non-load voltage | ≤ 26 V |
Signal: Error message output | |
Maximum switching voltage | 30 V |
Max. switching current | 100 mA |
Switching: Relay | |
Contact switching type | 2 N/O contacts |
Max. switching current | ≤ 170 mA (Resistive load) |
≤ 500 mA (≤ 1 ms) | |
Typical response time | < 80 ms |
Typical turn-off time | < 100 ms |
Signal: Repeater power supply operation | |
Output description | Current output (active) |
Current output signal | 4 mA ... 20 mA (with HART) |
2 mA ... 22 mA (Function area) | |
Load | 0 Ω ... 600 Ω |
Output ripple (current) | ≤ 40 µA (effective) |
Signal: Signal conditioner operation | |
Output description | Signal conditioner operation |
Current output signal | 4 mA ... 20 mA (with HART) |
2 mA ... 22 mA (Function area) | |
Load | 0 Ω ... 600 Ω |
Output ripple (current) | ≤ 40 µA (effective) |
Connection method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Ex installation (EPL) | Gc |
Ex i circuits (EPL) | Ga |
Da | |
Ma | |
Safety data: Repeater power supply operation (2-conductor measuring transducer) | |
Note | With connection of measuring transducers |
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | negligible |
Max. output voltage Uo | 27 V |
Max. output current Io | 87.9 mA |
Max. output power Po | 574 mW |
Safety-related maximum voltage Um | 253 V AC |
IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 14 mH / 705 nF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 2.3 mH / 90 nF |
IIB/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 10 mH / 290 nF, 1 mH / 380 nF, 0.2 mH / 600 nF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 1 mH / 56 nF, 0.5 mH / 72 nF, 0.2 mH / 90 nF |
Safety data: Repeater power supply operation (3-conductor measuring transducer) | |
Note | With connection of measuring transducers |
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | negligible |
Max. output voltage Uo | 27 V |
Max. output current Io | 88.3 mA |
Max. output power Po | 574 mW |
Safety-related maximum voltage Um | 253 V AC |
IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 14 mH / 705 nF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 2.3 mH / 90 nF |
IIB/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 10 mH / 290 nF, 1 mH / 380 nF, 0.2 mH / 600 nF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 1 mH / 56 nF, 0.5 mH / 72 nF, 0.2 mH / 90 nF |
Safety data: Signal conditioner operation | |
Note | With connection of power sources |
Input voltage Ui | 30 V |
Input current Ii | 100 mA |
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | negligible |
Max. output voltage Uo | 4.1 V |
Max. output current Io | 0 mA |
Max. output power Po | 0 mW |
Data communication (bypass) | |
Protocols supported | HART-transparent |
Frequency measuring range | 0.5 kHz ... 10 kHz (bidirectional HART transmission) |
Status display | Green LED (supply voltage) |
LED yellow (switching state) | |
Red LED (line errors) |
Dimensional drawing |
|
Width | 17.5 mm |
Height | 107.8 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Flammability rating according to UL 94 | V0 |
Housing material | Polyamide (PA 6.6) |
Ambient conditions | |
Degree of protection | IP20 (Terminal blocks) |
IP30 (Housing) | |
Ambient temperature (operation) | -40 °C ... 70 °C (Stand-alone device: any mounting position) |
-40 °C ... 48 °C (Group assembly: vertical DIN rail without circulating air) | |
-40 °C ... 58 °C (Group assembly: vertical DIN rail with circulating air) | |
-40 °C ... 56 °C (Group assembly: horizontal DIN rail without circulating air) | |
-40 °C ... 60 °C (Group assembly: horizontal DIN rail with circulating air) | |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | ≤ 95 % (non-condensing) |
ATEX | |
Identification | II (1) G [Ex ia Ga] IIC |
II (1) D [Ex ia Da] IIIC | |
II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc | |
I (M1) [Ex ia Ma] I | |
IECEx | |
Identification | [Ex ia Ga] IIC |
[Ex ia Da] IIIC | |
Ex nA nC [ia Ga] IIC T4 Gc | |
[Ex ia Ma] I | |
Safety Integrity Level (SIL, IEC 61508) | |
Identification | 2 |
Electromagnetic compatibility | Tested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21 |
Electrical isolation | 4-way isolation |
Mounting type | NS 35/15, NS 35/7,5 |
Mounting position | vertical, horizontal |
Item number | 1290776 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | C430 |
Product key | CK311V |
GTIN | 4063151522711 |
Weight per piece (including packing) | 205.1 g |
Weight per piece (excluding packing) | 160 g |
Customs tariff number | 85437090 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27210120 |
ECLASS-12.0 | 27210120 |
ECLASS-13.0 | 27210120 |
ETIM
ETIM 8.0 | EC002653 |
REACh SVHC | Lead 7439-92-1 |
Compatible products
-
IFS-USB-PROG-ADAPTER - Programming adapter 2811271
-
GW HART USB MODEM - Cable adapter 1003824
-
MACX MCR-PTB - Power and error message module 2865625
-
MACX MCR-PTB-SP - Power and error message module 2924184
-
QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply unit 2904614
-
ME 17,5 TBUS 1,5/ 5-ST-3,81 GY - DIN rail bus connectors 1090049
-
ME-TBUS-A MC 1,5-2 - DIN rail bus connectors 1351974
-
ME-TBUS-A IMC1,5-2 - DIN rail bus connectors 1351982
-
MCR-DP - Separating plate 1430594
-
MPS-IH WH - Insulating sleeve 0201663
-
MPS-IH RD - Insulating sleeve 0201676
-
MPS-IH BU - Insulating sleeve 0201689
-
MPS-IH YE - Insulating sleeve 0201692
-
MPS-IH GN - Insulating sleeve 0201702
-
MPS-IH GY - Insulating sleeve 0201728
-
MPS-IH BK - Insulating sleeve 0201731
-
MPS-MT - Test plugs 0201744
-
UC-EMLP (11X9) - Plastic label 0819291
-
UC-EMLP (11X9) YE - Plastic label 0822602
-
UC-EMLP (11X9) CUS - Plastic label 0824547
-
UC-EMLP (11X9) YE CUS - Plastic label 0824548
-
UC-EMLP (11X9) SR - Plastic label 0828094
-
UC-EMLP (11X9) SR CUS - Plastic label 0828098
-
US-EMLP (11X9) - Plastic label 0828789
-
US-EMLP (11X9) YE - Plastic label 0828871
-
US-EMLP (11X9) SR - Plastic label 0828872
-
LS-EMLP (11X9) WH - Device marker 0831678
-
LS-EMLP (11X9) SR - Device marker 0831705
-
LS-EMLP (11X9) YE - Device marker 0831732
-
SZS 0,6X3,5 - Screwdriver 1205053