MACX MCR-IDS-2I-2I
-
Output signal conditioner
2908065
2-channel output signal conditioner, HART-transparent. Isolates and transmits 0/4 mA ... 20 mA signals to a load in the safe area. 4-way electrical isolation, line fault detection, SIL 2 (SC3) in accordance with IEC 61508, screw connection.
Product details
Product type | Output signal conditioner |
Product family | MACX Analog |
No. of channels | 2 |
Type | Signal conditioners with SIL functional safety |
No. of channels | 2 |
Electrical isolation | 4-way isolation |
Signal transmission behavior | In = Out |
Step response (10-90%) | < 140 µs (for 4 mA ... 20 mA step) |
Maximum temperature coefficient | 0.01 %/K |
Temperature coefficient, typical | ≤ 0.005 %/K |
Maximum transmission error | 0.1 % (of final value) |
Transmission error, typical | ≤ 0.05 % (of final value) |
Electrical isolation | |
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Input/output IEC/EN 61010-1 | |
Standards/regulations | IEC/EN 61010-1 |
Rated insulation voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation |
Electrical isolation Input/power supply IEC/EN 61010-1 | |
Standards/regulations | IEC/EN 61010-1 |
Rated insulation voltage | 50 Vrms |
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Insulation | Basic insulation |
Electrical isolation Output/supply IEC/EN 61010-1 | |
Standards/regulations | IEC/EN 61010-1 |
Rated insulation voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation |
Electrical isolation Input 1/input 2, output 1/output 2 | |
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Supply | |
Nominal supply voltage | 24 V DC -20 % ... +25 % |
Supply voltage range | 19.2 V DC ... 30 V DC |
Max. current consumption | < 85 mA (24 V DC / 20 mA) |
Power dissipation | < 1.4 W (24 V DC / 20 mA) |
Power consumption | ≤ 2 W (24 V DC / 20 mA) |
Signal: Current | |
Current input signal | 0.2 mA ... 20 mA (Function) |
4 mA ... 20 mA (Safety) | |
0 mA ... 24 mA (Underload/overload range) | |
Input current | ≤ 30 mA |
Input impedance | > 1 MΩ (If there is a line fault) |
Line fault detection | > 0.2 mA (Response threshold of input current) |
Voltage drop | < 2.4 V (at 20 mA) |
Signal: Current | |
Number of outputs | 2 |
Current output signal | 0.2 mA ... 20 mA (Function) |
4 mA ... 20 mA (Safety) | |
0 mA ... 24 mA (Underload/overload range) | |
Load | 100 Ω ... 700 Ω (20 mA) |
100 Ω ... 650 Ω (20.5 mA) | |
100 Ω ... 500 Ω (24 mA) | |
Output ripple | < 20 mVrms |
Non-load voltage | ≤ 27 V |
Line fault detection | > 10 kΩ (Line break) |
< 50 Ω (Short circuit) |
Connection method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
COMBICON connection | |
Max. diameter | 2 mm |
Ex installation (EPL) | Gc |
Div. 2 |
Data communication (bypass) | |
HART function | Yes |
Protocols supported | HART-transparent |
Status display | Green LED (supply voltage) |
Dimensional drawing |
|
Width | 12.5 mm |
Height | 112.5 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing material | PA 6.6-FR |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 70 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m (Ex)) | |
Description | Ex applications |
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient temperature (operation) | -40 °C ... 70 °C |
Rated insulation voltage | 320 V (Power supply, input / output) |
Altitude range (≤ 3000 m (Ex)) | |
Description | Ex applications |
Height range | > 2000 m ... 3000 m |
Ambient temperature (operation) | -40 °C ... 60 °C |
Rated insulation voltage | 190 V (Power supply, input / output) |
Altitude range (≤ 4000 m (Ex)) | |
Description | Ex applications |
Height range | > 3000 m ... 4000 m |
Ambient temperature (operation) | -40 °C ... 55 °C |
Rated insulation voltage | 63 V (Power supply, input / output) |
Altitude range (≤ 5000 m (Ex)) | |
Description | Ex applications |
Height range | > 4000 m ... 5000 m |
Ambient temperature (operation) | -40 °C ... 45 °C |
Rated insulation voltage | 63 V (Power supply, input / output) |
Altitude range (≤ 2000 m) | |
Description | Non-Ex applications (EN 61010-1) |
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient temperature (operation) | -40 °C ... 70 °C |
Rated insulation voltage | 300 V (Power supply, input / output) |
Altitude range (≤ 3000 m) | |
Description | Non-Ex applications (EN 61010-1) |
Height range | > 2000 m ... 3000 m |
Ambient temperature (operation) | -40 °C ... 60 °C |
Rated insulation voltage | 150 V (Power supply, input / output) |
Altitude range (≤ 4000 m) | |
Description | Non-Ex applications (EN 61010-1) |
Height range | > 3000 m ... 4000 m |
Ambient temperature (operation) | -40 °C ... 55 °C |
Rated insulation voltage | 150 V (Power supply, input / output) |
Altitude range (≤ 5000 m) | |
Description | Non-Ex applications (EN 61010-1) |
Height range | > 4000 m ... 5000 m |
Ambient temperature (operation) | -40 °C ... 45 °C |
Rated insulation voltage | 150 V (Power supply, input / output) |
CE | |
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX | |
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | BVS 20 ATEX E 003 X |
UKCA Ex (UKEX) | |
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | PxCIF21UKEx2908065X |
IECEx | |
Identification | Ex ec IIC T4 Gc |
Certificate | IECEx BVS 20.0003X |
CCC / China-Ex | |
Identification | Ex ec IIC T4 Gc |
Certificate | 2021122304114079 |
UL, USA/Canada | |
Identification | UL 61010 Listed |
Class I, Div. 2, Groups A, B, C, D T4 | |
Class I, Zone 2, Group IIC T4 | |
Shipbuilding approval | |
Certificate | DNV GL TAA00000AG |
Safety Integrity Level (SIL, IEC 61508) | |
Identification | 3 |
Systematic Capability | |
Identification | 3 |
INMETRO | |
Identification | Ex ec IIC T4 Gc |
Certificate | DNV 21.0092 X |
EAC | |
Identification | 2Ex e IIC T4 Gc X |
Certificate | RU C-DE.HB49.B.00145/21 |
DNV GL data | |
Temperature | B |
Humidity | B |
Vibration | A |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electrical isolation | 4-way isolation |
GB Standard | |
Standards/regulations | GB/T 3836.1 |
GB/T 3836.3 |
Mounting type | DIN rail mounting |
Item number | 2908065 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | C402 |
Product key | CK1112 |
GTIN | 4055626275321 |
Weight per piece (including packing) | 176.1 g |
Weight per piece (excluding packing) | 160 g |
Customs tariff number | 85437090 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27210120 |
ECLASS-12.0 | 27210120 |
ECLASS-13.0 | 27210120 |
ETIM
ETIM 8.0 | EC002653 |
UNSPSC
UNSPSC 21.0 | 39121000 |
China RoHS | Environmentally Friendly Use Period = 50 years |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |
Compatible products
-
ME 6,2 TBUS-2 1,5/5-ST-3,81 GY - DIN rail bus connectors 2695439
-
ME 6,2 TBUS-PR-ADAPTER - DIN rail bus connectors 1136500
-
MCR-DP - Separating plate 1430594
-
TC-2D37SUB-ADIO32-2EX-P-UNI - Module carrier 2904684
-
EA-MSTB 2,5/ 5 - Accessories 1831016
-
MACX MCR-PTB - Power and error message module 2865625
-
MACX MCR-PTB-SP - Power and error message module 2924184
-
QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply unit 2904614
-
MPS-IH WH - Insulating sleeve 0201663
-
MPS-IH RD - Insulating sleeve 0201676
-
MPS-IH BU - Insulating sleeve 0201689
-
MPS-IH YE - Insulating sleeve 0201692
-
MPS-IH GN - Insulating sleeve 0201702
-
MPS-IH GY - Insulating sleeve 0201728
-
MPS-IH BK - Insulating sleeve 0201731
-
MPS-MT - Test plugs 0201744
-
UC-EMLP (11X9) - Plastic label 0819291
-
UC-EMLP (11X9) YE - Plastic label 0822602
-
UC-EMLP (11X9) CUS - Plastic label 0824547
-
UC-EMLP (11X9) YE CUS - Plastic label 0824548
-
UC-EMLP (11X9) SR - Plastic label 0828094
-
UC-EMLP (11X9) SR CUS - Plastic label 0828098
-
US-EMLP (11X9) - Plastic label 0828789
-
US-EMLP (11X9) YE - Plastic label 0828871
-
US-EMLP (11X9) SR - Plastic label 0828872
-
LS-EMLP (11X9) WH - Device marker 0831678
-
LS-EMLP (11X9) SR - Device marker 0831705
-
LS-EMLP (11X9) YE - Device marker 0831732
-
SZS 0,6X3,5 - Screwdriver 1205053