MACX-MR-V-600-PT - Monitoring relay
1336507

1-phase voltage monitoring relay, 24 V AC/DC … 240 V AC/DC wide range power supply, with adjustable threshold values, response delay, and the functions can be selected by configuration.


Product Details




Product type Voltage monitoring relay
Operating mode Closed circuit or wire break
Insulation characteristics: Railway standard
Overvoltage category III
Pollution degree 3

Service life electrical approx. 1x 105 cycles, resistive load 2000 V A
Railway standard
Rated insulation voltage 600 V
Electrical isolation
Electrical isolation 300 V
Supply
Supply voltage range 24 V ... 240 V AC -15 % ... +10 %
24 V ... 240 V DC -25 % ... +30 %
Nominal power consumption 15 VA (1.5 W)

Input name Measuring input
Measured value DC, AC sine (40 Hz ... 500 Hz)
Input voltage range 0 V AC/DC ... 600 V AC/DC
Frequency range 48 Hz ... 400 Hz
Maximum temperature coefficient 0.05 %/K
Setting range for response delay 0 s ... 99.9 s
Function Undervoltage
Overvoltage
Window
Basic accuracy 1 % (>50V, ±0.5V (0…50V))
Repeat accuracy 0.5 %
Recovery time 200 ms

Switching
Contact type 2 floating changeover contacts
Maximum switching voltage 250 V AC
Interrupting rating (ohmic load) max. 2000 VA (8 A/250 V AC)
Output fuse 8 A (fast-blow)

Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Tightening torque 0.5 Nm ... 0.6 Nm (5 lb in ... 7 lb in)

Width 22.5 mm
Height 109 mm
Depth 114 mm

Flammability rating according to UL 94 V0
Housing insulation material PBT

Ambient conditions
Degree of protection IP40 (Housing)
IP20 (Connection terminal blocks)
Ambient temperature (operation) -25 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 %

CE
Identification CE-compliant
UL, USA / Canada
Identification UL/C-UL Listed UL 508
CCC
Identification GB/T 14048.5
Electronic devices in rail vehicles
Operating temperature class OT4
Class of extended operating temperature upon activation ST2
Temperature change class H1
Interruption of the power supply/supply changeover S2
S3/C1
C2
Hazard levels HL1
HL2
HL3
Protective coating PC2
Shock (operation) Category 1
Vibration (operation) Class B

Low Voltage Directive Conformance with Low Voltage Directive
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2

Railway standard
Standard designation EN 50155, GB/T 25119

Assembly instructions on standard DIN rail NS 35 in accordance with EN 60715
Mounting position any

Item number 1336507
Packing unit 1 pc
Minimum order quantity 1 pc
Product Key CK4711
GTIN 4063151636562
Weight per Piece (including packing) 195 g
Weight per Piece (excluding packing) 195 g
Country of origin CN


ECLASS

ECLASS-9.0 27371801
ECLASS-10.0.1 27371801
ECLASS-11.0 27371801

CCC

Approval ID: 2022000303000015

REACh SVHC Lead 7439-92-1