Analog module - AXL F RTD4 1H
2688556

Axioline F, Temperature recording module, Analog inputs: 4 (for resistance temperature detectors), connection technology: 2-, 3-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors

Free Download available. Downloads

Product Details


The module is designed for use within an Axioline F station. It is used to acquire signals from resistive temperature sensors. The module supports all common platinum and nickel sensors in accordance with DIN EN 60751 and SAMA. Cu10, Cu50, Cu53 sensors as well as various KTY8x sensor types are also supported.



Dimensional drawing
Width 35 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).

Color traffic grey A RAL 7042

Axioline F local bus
Number of interfaces 2
Connection method Bus base module
Transmission speed 100 Mbps

Module
Input address area 8 Byte
Output address area 8 Byte
Required parameter data 12 Byte
Required configuration data 6 Byte

Analog
Input name Analog inputs
Description of the input Inputs for resistive temperature sensors
Number of inputs 4 (for resistance temperature detectors)
Connection method Push-in connection
Connection technology 2-, 3-, 4-conductor (shielded)
A/D converter resolution 24 bit
Sensor types (RTD) that can be used Pt, Ni, KTY, Cu sensors
Data formats IB IL, S7-compatible
Measured value representation 16 bits (15 bits + sign bit)
Input filter time 40 ms
60 ms
100 ms
120 ms (adjustable)
Nominal value of the current sources 1 mA (Pt 100, Ni 100, RLin 500 Ω; pulse current, the specification is valid during the sampling phase)
210 µA (P t1000, Ni 1000, RLin 5000 Ω; pulse current, the specification is valid during the sampling phase)
Linear resistance measuring range 0 Ω ... 500 Ω
0 kΩ ... 5 kΩ
Protective circuit Short-circuit protection, overload protection of the inputs
Transient protection of inputs
Transient protection of sensor supplies

Type block modular
Product type I/O component
Mounting position any (no temperature derating)
Scope of delivery including bus base module and Axioline F connectors
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Potentials
Power consumption max. 1.1 W (at UBus and UA)
Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Current draw max. 140 mA
Power consumption max. 700 mW
Potentials: Supply for analog modules (UA)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 17 mA
Power consumption max. 400 mW
Protective circuit Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; Polarity protection diode
Transient protection; Suppressor diode

Connection technology
Connection name Axioline F connector
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor connection
Connection method Push-in connection
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm
Axioline F connector
Connection method Push-in connection
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid 0.2 mm² ... 1.5 mm²
Stripping length 8 mm

Ambient temperature (operation) -25 °C ... 60 °C
Degree of protection IP20
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Mounting type DIN rail mounting
Mounting position any (no temperature derating)

Item number 2688556
Packing unit 1 pc
Minimum order quantity 1 pc
Note Made to Order (non-returnable)
Sales Key C21
Product Key DRI243
Catalog Page Page 86 (C-6-2019)
GTIN 4046356744201
Weight per Piece (including packing) 197 g
Weight per Piece (excluding packing) 144 g
Customs tariff number 85389091
Country of origin DE


ECLASS

ECLASS-9.0 27242601
ECLASS-10.0.1 27242601
ECLASS-11.0 27242601
ECLASS-12.0 27242601

ETIM

ETIM 8.0 EC001596

UNSPSC

UNSPSC 21.0 32151600

DNV GL

Approval ID: TAA00000DF

LR

Approval ID: LR2001902TA

NK

Approval ID: 14A006

BV

Approval ID: 36433/B4 BV

PRS

Approval ID: TE/1020/880590/21

UL Listed

Approval ID: FILE E 238705

cUL Listed

Approval ID: FILE E 238705

BSH

Approval ID: 840

RINA

Approval ID: ELE283021XG

ABS

Approval ID: 21-2187864-PDA

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

4 analog input channels for connecting resistance temperature detectors (RTDs)
500 Ω and 5 kΩ linear inputs
Connection of sensors in 2-, 3-, and 4-conductor technology
Integrated, digital sensor linearization
Standardized measured value representation directly in °C, °F or Ω
Measured value display in 16-bit format or floating point format
Programmable filters
Short-circuit protected inputs
Temperature stability
Very high level of noise immunity
Low noise emission
Installation monitoring by means of “Channel scout” function
Device rating plate stored