Hybrid motor starter - ELR H5-IES-PT/500AC-06-IFS
2905138

Networkable hybrid motor starter for reversing 3~ AC motors up to 500 V AC and 0.6 A output current, with adjustable overload shutdown, emergency stop function to SIL 3 / PL e and push-in connection, DIN rail connector provided.

Downloads

Product Details




Product type Hybrid motor starter
Operating mode 100% operating factor

Number of phases 3
Motor starter type Reversing starter
Maximum power dissipation for nominal condition 0.5 W
Switching frequency ≤ 2 Hz (Load-dependent)
Maximum power dissipation 2.5 W
Minimum power dissipation 0.88 W
Coordination type 1
Supply
Rated control circuit supply voltage US 24 V DC
Control supply voltage range 19.2 V DC ... 30 V DC
Rated control supply current IS 60 mA
Protective circuit Surge protection
Reverse polarity protection; Parallel polarity protection diode
Insulation characteristics
Rated insulation voltage 550 V
Rated surge voltage 6 kV
Overvoltage category III
Degree of pollution 2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit Safe isolation (IEC 60947-1)
Isolation characteristics between the control input and control supply voltage to auxiliary circuit Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Emergency tripping
Operate threshold > 10 A
Response time < 0.5 s

Control
Input name Enable input
Note The enable input is compatible with signals with blanking (semiconductor output signals with test pulse with max. 3 ms duration),
unblanking pulses of max. 4 ms are tolerated without adversely affecting the safety function.
Rated actuating voltage UC 24 V DC
Triggering voltage range 19.2 V DC ... 30 V DC
Rated actuating current IC 7 mA
Switching threshold 9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level < 5 V DC (For EMERGENCY STOP)
Typical turn-off time < 30 ms
Protective circuit Reverse polarity protection

AC output
Rated operating voltage Ue 500 V AC
Operating voltage range 42 V AC ... 550 V AC
Rated operating current Ie 0.6 A (AC-51)
0.6 A (AC-53a)
Mains frequency 50/60 Hz
Load current range 75 mA ... 600 mA (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2 Class 10
Cooling time 20 min. (for auto reset)
Leakage current 0 mA
Protective circuit Surge protection; Varistor

Control circuits
Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Control circuits
Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14

Status display Yellow LED
Operating voltage display Green LED
Indication Red LED

Width 22.5 mm
Height 107.5 mm
Depth 114 mm

Flammability rating according to UL 94 V0 (Housing)

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -5 °C ... 60 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m

UKCA
Designation UKCA
Certificate UKCA-compliant
UKCA
Designation ATEX
Identification  II (2) G [Ex eb] [Ex db] [Ex pxb]
 II (2) D [Ex tb] [Ex pb]
Certificate PTB 15 ATEX 3000
UKCA
Designation UL approval
Certificate NLDX.E228652
NRNT.E172140
UKCA
Designation Safety Integrity Level (SIL, IEC 61508)
Identification ≤ 3
Note Safe shutdown
UKCA
Designation Safety Integrity Level (SIL, IEC 61508)
Identification 2
Note Motor protection
UKCA
Designation Performance Level (ISO 13849)
Identification e
Note Safe shutdown
UKCA
Designation Category (ISO 13849)
Identification ≤ 3
Note Safe shutdown
UL data
SCCR 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA 0.6 A (480 V AC)
Group installation 20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded)
Category code NLDX / NRNT
Horsepower ratings -

Standards/regulations
Standards/regulations IEC 60947-1
EN 60947-4-2
IEC 61508
ISO 13849

Mounting type DIN rail mounting
Assembly instructions alignable, for spacing see derating
Mounting position vertical (horizontal DIN rail, motor output below)

Item number 2905138
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key 00
Product Key CK7432
Catalog Page Page 24 (C-5-2019)
GTIN 4046356919531
Weight per Piece (including packing) 310.7 g
Weight per Piece (excluding packing) 282.7 g
Customs tariff number 85371098
Country of origin DE


ECLASS

ECLASS-9.0 27370905
ECLASS-10.0.1 27370905
ECLASS-11.0 27370905

ETIM

ETIM 8.0 EC001037

UNSPSC

UNSPSC 21.0 25173900

IECEE CB Scheme

Approval ID: DE1-60807

EAC

Approval ID: RU*C-DE.*08.B.00520*

UL Listed

Approval ID: FILE E 172140

CCC

Approval ID: 2016010304900298

cUL Listed

Approval ID: FILE E 172140

cUL Listed

Approval ID: FILE E 228652

UL Listed

Approval ID: FILE E 228652

ATEX

Approval ID: PTB 15 ATEX 3000

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

22.5 mm wide
Safety level according to IEC 61508-1: SIL 3, ISO 13849: PL e
Reduction in wiring
Space saving
Long service life
3-phase loop bridges
Adjustable current for bimetal function
Low-wear switching