Product type | Energy measuring device |
Product family | EMpro |
Insulation characteristics | |
Overvoltage category | III (300 V) |
Pollution degree | 2 |
Electrical isolation | IEC 61010-1 (Overvoltage category III at 300 V ACOvervoltage category II at 600 V AC) |
IEC 61010-1 (Overvoltage category III at 300 V ACOvervoltage category II at 600 V AC) | |
IEC 61010-1 (Measurement category III at 300 V ACMeasurement category II at 600 V AC) | |
Test voltage | 4 kV AC (50 Hz, 60 s) |
Maximum power dissipation for nominal condition | 10 VA |
Mains type | 3-phase (3 or 4-conductor), 2-phase (2-conductor), and single-phase (1-conductor) |
Supply | |
Supply voltage range | 100 V AC ... 400 V AC (±20 %) |
150 V DC ... 250 V DC (±20 %) | |
Power consumption | ≤ 4 W |
Nominal frequency | 50 Hz ... 60 Hz (AC sine) |
General | |
Measuring principle | True r.m.s. value measurement (TRMS) |
Measured value | AC sine (50/60 Hz) |
Acquisition of harmonics | up to 63rd harmonic |
Description of the input | Digital input in accordance with IEC/EN 61131-2 (type 3) |
Number | 1 |
Voltage input signal | 24 V DC |
0 V DC ... 30 V DC | |
Current input signal | 2 mA ... 15 mA |
Protection | 250 mA (fast-blow) |
Measurement: Voltage | |
Input name | Voltage measuring input V1, V2, V3 |
Input voltage range direct | 35 V AC ... 690 V AC (Phase/Phase) |
20 V AC ... 400 V AC (Phase/neutral conductor) | |
Input voltage range via external transformers | 60 V AC ... 2000000 V AC (primary) |
60 V AC ... 400 V AC (secondary) | |
Surge voltage capacity | 760 V AC (Phase/Phase) |
Precision | 0.2 % |
Power consumption | < 2 VA |
Measurement: Current | |
Input name | Current measurement I1, I2, I3 |
Input current | 1 A (secondary) |
5 A (secondary) | |
Current measuring range | 1 A ... 20000 A (primary) |
Overload capacity | 6 A (Imax) |
Response threshold from measuring range nominal value | 10 mA (1 A) |
50 mA (5 A) | |
Precision | 0.2 % |
Current overload | 50 A for 1 s |
Power consumption | < 0.5 VA |
Measurement: Power | |
Precision | 0.5 % |
Active energy (IEC 62053-22) | Class 0.5 S |
Reactive power (IEC 62053-23) | Class 2 |
ANSI C12.20 | Class 0.5 S |
Output description | Digital output in accordance with IEC/EN 61131-2 (type 3) |
Number | 1 |
Current output signal | ≤ 100 mA |
Voltage output signal | 24 V DC |
Protection | 250 mA (fast-blow) |
Current / voltage / supply | |
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 6 mm² |
Conductor cross section flexible | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 10 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Digital I/O / communication | |
Connection method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 26 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Data: Network interface | |
Communication protocol | Modbus/TCP |
REST | |
Connection method | RJ45 |
Data: Network interface | |
Communication protocol | EtherNet/IP™ |
Connection method | RJ45 |
Number of connections | 2 |
Note | DLR ready |
Width | 96 mm |
Height | 96 mm |
Depth | 75 mm |
Ambient conditions | |
Degree of protection (Housing) | IP20 (Housing) |
Degree of protection (Display) | IP54 (Display (+ EEM-MA-IP)) |
Ambient temperature (operation) | -10 °C ... 55 °C |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Altitude | ≤ 2000 m |
Max. permissible relative humidity (operation) | ≤ 95 % (non-condensing) |
CE | |
Certificate | CE-compliant |
UKCA | |
Certificate | UKCA-compliant |
UL, USA/Canada | |
Identification | UL/C-UL Listed UL 61010-1 |
UL data | |
Operating mode | Indoor use |
UL data | |
Operating mode | Indoor use |
Mounting type | Panel mount |
Mounting position | Front panel installation, horizontal |
Item number | 2907953 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | C446 |
Product key | CK4C21 |
Catalog page | Page 202 (C-5-2019) |
GTIN | 4055626261096 |
Weight per piece (including packing) | 570 g |
Weight per piece (excluding packing) | 520.1 g |
Customs tariff number | 90303100 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27142330 |
ECLASS-12.0 | 27142330 |
ECLASS-13.0 | 27142330 |
ETIM
ETIM 8.0 | EC002301 |
UNSPSC
UNSPSC 21.0 | 41113600 |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |
Compatible products
-
EEM-MKT-DRA - DIN rail adapter 2902078
-
PACT MCR-V1-21-44 - Current transformer 2277268
-
PACT MCR-V2- 3015- 60 - Current transformer 2277271
-
PACT MCR-V2-3015-60-PT - Current transformer 2907413
-
PACT MCR-V2- 4012- 70 - Current transformer 2277284
-
PACT MCR-V2-4012-70-PT - Current transformer 2907414
-
PACT MCR-V2- 5012- 85 - Current transformer 2277297
-
PACT MCR-V2-5012-85-PT - Current transformer 2907416
-
PACT MCR-V2- 6015- 85 - Current transformer 2277336
-
PACT MCR-V2-6015-85-PT - Current transformer 2907417
-
PACT MCR-V2-10020-129 - Current transformer 2277378
-
PACT MCR-V3-60 - Current transformer 2277417