Type 3 surge protection device - MNT-TV-SAT D
2882284

Socket attachment plug with surge protection for the power supply unit and signal connection for radio and television equipment (cable, terrestrial antenna, satellite system). Cable is provided.


Product Details




General
Note Shielding requirements according to DIN EN 50083-2, Class A

IEC test classification C2
C3
D1
IEC power supply system TN
TT
Type Attachment plug
Product type Device protection
Number of positions 2
For country-specific use in D, A, NL, E, S, FIN, TR
Surge protection fault message optical
Insulation characteristics
Overvoltage category II
Pollution degree 2
IEC test classification III
T3
EN type T3
Number of ports One

Connection method F connector
Connection method Grounding plug/socket

Dimensional drawing
Width 63 mm
Height 107 mm
Depth 78 mm

Color jet black RAL 9005
Flammability rating according to UL 94 V-0
CTI value of material 400
600
Insulating material PA 6
Housing material PA 6

Power supplies
Direction of action L/N-PE & Signal Line-Shield-Earth Ground
Nominal voltage UN 230/400 V AC (TN/TT)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N) 275 V AC
Maximum continuous operating voltage UC (L-PE) 360 V AC
Maximum continuous operating voltage UC (N-PE) 360 V AC
Rated load current IL 16 A (30 °C)
Residual current IPE ≤ 5 µA
Standby power consumption PC ≤ 1 VA
Reference test voltage UREF 255 V AC
Combination wave UOC 6 kV
Voltage protection level Up ≤ 1.5 kV
TOV behavior at UT (L-N) 460 V AC (5 s / withstand mode)
460 V AC (120 min / safe failure mode)
TOV behavior at UT (L-PE) 460 V AC (5 s / withstand mode)
460 V AC (120 min / withstand mode)
1455 V AC (200 ms / safe failure mode)
TOV behavior at UT (N-PE) 1200 V AC (200 ms / safe failure mode)
Response time tA (L-N) ≤ 25 ns
Response time tA (L-PE) ≤ 100 ns
Response time tA (N-PE) ≤ 100 ns
Max. required back-up fuse 16 A (gG / B / C)
Short-circuit current rating ISCCR 1.5 kA AC
Information technology
Maximum continuous voltage UC 24 V DC
Rated current 1.5 A (25 °C)
Operating effective current IC at UC ≤ 1 µA
Standby power consumption PC ≤ 1 VA
Residual current IPE ≤ 1 µA
Insulation resistance Riso ≥ 70 MΩ
≥ 70 MΩ
Nominal discharge surge current In (8/20) µs (Core-Earth) 2.5 kA
Nominal discharge surge current In (8/20) µs (core-shield) 2.5 kA
Nominal discharge current In (8/20) µs (shield-earth) 5 kA
Total discharge current Itotal (8/20) µs 5 kA
Nominal pulse current Ian (10/1000) µs (line-shield) 120 A
Nominal pulse current Ian (10/1000) µs (shield-earth) 200 A
Output voltage limitation at 1 kV/µs (line-shield) spike ≤ 700 V
Output voltage limitation at 1 kV/µs (shield-earth) spike ≤ 1 kV
Output voltage limitation at 1 kV/µs (line-shield) static ≤ 700 V
Output voltage limitation at 1 kV/µs (shield-earth) static ≤ 1 kV
Residual voltage at In (conductor-shield) ≤ 40 V
Residual voltage at In (shield-ground) ≤ 50 V
Voltage protection level Up (line-shield) ≤ 700 V (C2 - 2 kA)
Voltage protection level Up (shield-earth) ≤ 1.2 kV (C2 - 5 kA)
Response time tA (line-shield) ≤ 100 ns
Response time tA (shield-earth) ≤ 100 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 2.4 GHz /75 Ω)
Cut-off frequency fg (3 dB), asym. (shield) in 75 Ω system typ. 2.5 GHz
Frequency range 0 Hz ... 2400 MHz
Capacity asymmetrical (shield) typ. 10 pF
Alternating current carrying capacity (line-shield) 5 A - 1 s
Alternating current carrying capacity (shield-earth) 10 A - 1 s
Pulse reset time (line-shield) ≤ 4 s

Ambient conditions
Degree of protection IP20 (Child-proofing)
Ambient temperature (operation) -25 °C ... 75 °C
Ambient temperature (storage/transport) -25 °C ... 75 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %

Standards/specifications IEC 61643-11
Standards/specifications EN 61643-11
Standards/specifications EN 61643-21
Standards/specifications IEC 61643-21
Standards/specifications EN 50083

Mounting type Plugging into the mains socket

Item number 2882284
Packing unit 1 pc
Minimum order quantity 1 pc
Product Key CL1424
Catalog Page Page 89 (C-4-2019)
GTIN 4046356073516
Weight per Piece (including packing) 314.6 g
Weight per Piece (excluding packing) 314.6 g
Country of origin DE


ECLASS

ECLASS-9.0 27130810
ECLASS-10.0.1 27130810
ECLASS-11.0 27130810

ETIM

ETIM 8.0 EC001473

UNSPSC

UNSPSC 21.0 39121600

EAC

Approval ID: RU C-DE.*09.B.00169

REACh SVHC Lead 7439-92-1
Hexahydromethylphthalic anhydride

Your advantages

Optimal additional protection of the building installation for longer service life and increased availability of the end devices
Industrial quality for residential buildings, thanks to compliance with international product standard
Meets the most stringent safety requirements with thermal monitoring and additional fuses
Ideal addition to the C-SAT surge protective device, direct end device protection