DC/DC converters - QUINT4-PS/12-24DC/24DC/1.3/PT
1066716

Primary-switched DC/DC converter, QUINT POWER, DIN rail mounting, input: 12 V DC - 24 V DC, output: 24 V DC / 1.3 A


Product Details


In the power range of up to 100 W, QUINT POWER provides superior system availability in the smallest size. Preventative function monitoring and exceptional power reserves are available for applications in the low-power range.



Nominal input voltage range 12 V DC ... 24 V DC
Input voltage range 12 V DC ... 24 V DC -25 % ... +33 % (SELV)
Wide-range input yes
Electric strength, max. 35 V DC (60 s)
Inrush current typ. 1.6 A
Inrush current integral (I2t) typ. 0.1 A2s
Inrush current limitation typ. 1.6 A
Mains buffering time typ. 19 ms (24 V DC)
Current consumption typ. 3.75 A (12 V DC)
typ. 1.85 A (24 V DC)
Typical response time 700 ms (from SLEEP MODE)
Switch-on time < 1 s
Input fuse 15 A (fast blow, internal)
Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C, D, K or comparable)

Efficiency typ. 91.7 % (24 V DC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC ... 28 V DC (> 24 V DC, constant capacity)
Nominal output current (IN) 1.3 A
Static Boost (IStat.Boost) 1.625 A (≤ 40 °C)
Dynamic Boost (IDyn.Boost) 2.6 A (≤ 60 °C (4,9 s))
Short-circuit-proof yes
No-load proof yes
Derating > 60 °C (2.5%/K of POut nom.)
Output power (PN) 30 W
Output power (PStat. Boost) 38 W
Output power (PDyn. Boost) 60 W
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) < 32 V DC
Residual ripple < 20 mVPP
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Rise time < 1 s (UOUT (10 % ... 90 %))
Connection in series yes
Maximum no-load power dissipation < 1.3 W
Power loss nominal load max. < 8 W
Connection in parallel yes, for redundancy and increased capacity
Signal (configurable)
Digital 0 V DC
24 V DC
22 mA
Default 24 V DC
22 mA
24 V DC for UOut > 0.9 x USet

Input
Position 1.x
Conductor connection
Connection method Push-in connection
rigid 0.5 mm² ... 2.5 mm²
flexible 0.5 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve 0.5 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve 0.25 mm² ... 2.5 mm²
rigid (AWG) 22 ... 14
Stripping length 10 mm
Output
Position 2.x
Conductor connection
Connection method Push-in connection
rigid 0.2 mm² ... 2.5 mm²
flexible 0.25 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve 0.25 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve 0.25 mm² ... 2.5 mm²
rigid (AWG) 24 ... 14
Stripping length 10 mm
Signal
Position 3.x
Conductor connection
Connection method Push-in connection
rigid 0.2 mm² ... 2.5 mm²
flexible 0.2 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve 0.25 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve 0.25 mm² ... 2.5 mm²
rigid (AWG) 24 ... 14
Stripping length 10 mm

Signal threshold > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting)
> 0.9 x USet (LED lights up green)
< 0.9 x USet (LED flashes green)

Number of phases 1.00
Insulation voltage input/output 2.6 kV DC (type test)
1.2 kV DC (routine test)
Switching frequency 130 kHz ... 130 kHz (Auxiliary converter stage)
70 kHz ... 250 kHz (Main converter stage)

Product type DC/DC converters
MTBF (IEC 61709, SN 29500) > 1999348 h (25 °C)
> 1120490 h (40 °C)
> 471066 h (60 °C)
Insulation characteristics
Protection class II
Degree of pollution 2
Life expectancy (electrolytic capacitors)
Current 0.65 A
Temperature 40 °C
Time 242000 h
Additional text 24 V DC
Life expectancy (electrolytic capacitors)
Current 1.3 A
Temperature 40 °C
Time 160000 h
Additional text 24 V DC
Life expectancy (electrolytic capacitors)
Current 1.3 A
Temperature 30 °C
Time 320000 h
Additional text 24 V DC

Dimensional drawing
Width 22.5 mm
Height 106 mm
Depth 90 mm
Installation dimensions
Installation distance right/left (active) 15 mm / 15 mm (POut ≥50% )
Installation distance right/left (passive) 5 mm / 5 mm (POut ≥50% )
Installation distance right/left (active, passive) 0 mm / 0 mm (POut ≤50 %)
Installation distance top/bottom (active) 30 mm / 30 mm (POut ≥50% )
Installation distance top/bottom (passive) 30 mm / 30 mm (POut ≥50% )
Installation distance top/bottom (active, passive) 30 mm / 30 mm (POut ≤50 %)

Mounting type DIN rail mounting
Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
With protective coating No

Flammability rating according to UL 94 (housing / terminal blocks) V0
Housing material Plastic
Type of housing Polycarbonate (PC), UL 94 V0

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Ambient temperature (start-up type tested) -40 °C
Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6)

Overvoltage category
EN 61010-1 II (≤ 5000 m)
Safety for measurement, control, and laboratory equipment
Standards/specifications IEC 61010-1
Protective extra-low voltage
Standards/specifications IEC 61010-1 (SELV)
Mains voltage dips
Standards/specifications EN 61000-4-29

SIQ CB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvals UL Listed UL 61010-1
UL Listed UL 61010-2-201
UL 1310 Class 2 Power Units
ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
UL
Identification UL Listed UL 61010-1
UL
Identification CAN/CSA C22.2 No. 61010-1-12
UL
Identification UL Listed UL 61010-2-201
UL
Identification CAN/CSA C22.2 No. 61010-2-201:18
UL
Identification UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
CB scheme
Identification IEC 61010-1
CB scheme
Identification IEC 61010-2-201
Shipbuilding
Identification DNV GL

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements, power plant EN 61850-3
EN 61000-6-5
Conducted noise emission EN 55016
EN 61000-6-3 (Class B)
Interference emission Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise emission Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emission EN 55016
EN 61000-6-3 (Class B)
Noise immunity Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply)
DNV GL conducted interference Class B
Additional text Bridge and deck area
DNV GL noise radiation Class B
Additional text Bridge and deck area
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 6 kV (Test Level 4)
Discharge in air 8 kV (Test Level 3)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz ... 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 4 - asymmetrical)
Output 2 kV (Test Level 4 - asymmetrical)
Signal 2 kV (Test Level 4 - asymmetrical)
Comments Criterion B
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 1 kV (Test Level 4 - symmetrical)
2 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 4 - symmetrical)
2 kV (Test Level 4 - asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations EN 61000-4-8
Frequency 16.67 Hz
50 Hz
60 Hz
Test field strength 100 A/m
Additional text 60 s
Comments Criterion A
Frequency 50 Hz
60 Hz
Frequency range 50 Hz ... 60 Hz
Test field strength 1 kA/m
Additional text 3 s
Frequency 0 Hz
Test field strength 300 A/m
Additional text DC, 60 s
Voltage dips
Standards/regulations EN 61000-4-29
Voltage 24 V DC
Voltage dip 70 %
Number of periods 0.5 / 1 / 25 periods
Time 100 ms
Additional text Test Level 2
Comments Criterion A
Voltage dip 40 %
Number of periods 5 / 10 / 50 periods
Time 100 ms
Additional text Test Level 2
Comments Criterion A
Voltage dip 0 %
Number of periods 0.5 / 1 / 5 / 50 periods
Time 50 ms
Additional text Test Level 2
Comments Criterion B
Pulse-shape magnetic field
Standards/regulations EN 61000-4-9
Test field strength 1000 A/m
Comments Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations EN 61000-4-16
Test level 1 15 Hz 150 Hz (Test Level 3)
Voltage 10 V 1 V (Permanent)
Test level 2 150 Hz 1.5 kHz (Test Level 3)
Voltage 1 V
Test level 3 1.5 kHz 15 kHz (Test Level 3)
Voltage 1 V 10 V
Test level 4 15 kHz 150 kHz (Test Level 3)
Voltage 10 V
Test level 5 16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Voltage 10 V (Permanent)
Test level 6 0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
Voltage 100 V (1 s)
Comments Criterion A
Alternating component of direct voltage
Standards/regulations EN 61000-4-17
Alternating component 10 % (UN)
Frequency 50 Hz
100 Hz
150 Hz
300 Hz
Comments Criterion A
Attenuated oscillating wave
Standards/regulations EN 61000-4-18
Input, output (test level 1) 1 MHz (Test Level 2 - symmetrical)
Voltage 0.5 kV
Input, output (test level 2) 1 MHz (Test Level 2 - asymmetrical)
Voltage 1 kV
Signals (test level 1) 1 MHz (Test Level 2 - symmetrical)
Voltage 0.5 kV
Signals (test level 2) 1 MHz (Test Level 2 - asymmetrical)
Voltage 1 kV
Comments Criterion A
Attenuated oscillating magnetic field
Standards/regulations EN 61000-4-10
Test field strength 100 A/m
Test level 1 100 kHz
Test field strength 100 A/m
Test level 2 1 MHz
Comments Criterion A
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Item number 1066716
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C13
Product Key CMDI43
GTIN 4055626734262
Weight per Piece (including packing) 221.866 g
Weight per Piece (excluding packing) 169 g
Customs tariff number 85044030
Country of origin CN


ECLASS

ECLASS-9.0 27210901
ECLASS-11.0 27040701

ETIM

ETIM 8.0 EC002046

UNSPSC

UNSPSC 21.0 39121000

IECEE CB Scheme

Approval ID: DK-97404-UL

IECEE CB Scheme

Approval ID: DE/PTZ/0122

cULus Listed

Approval ID: FILE E 123528

DNV

Approval ID: TAA00000BV

cULus Listed

Approval ID: FILE E 199827

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products

Your advantages

Most powerful output side: easy system expansion, reliable heavy load startup and miniature circuit breaker tripping
Most comprehensive signaling: preventive function monitoring reports critical operating states before errors occur
Free selection between Push-in and screw connection