Current transformer - PACT SPC-50-1A-D13
1382384

Split-core current transformer, primary current: 0 ... 50 A AC, secondary current: 0 ... 1 A AC, rated power: 0.2 VA, length of signal cable: 3 m


Product Details




Product type Current transformer

Test voltage 3 kV (EN 61869-1)
Rated insulation voltage 0.72 kV
Measuring coil
Length of signal cable 3 m
General
Converter type Split-core current transformer

Current transformers
Rated power 0.2 VA
Thermal rated short-time current Ith = 60 * In
Thermal rated continuous current Id = 1.2 * In
Rated surge current Idyn = 2.5 * Ith
Rated frequency fn 50 Hz
60 Hz
Primary rated current range 0 A AC ... 50 A AC (depends on type)
Converter type Split-core current transformer

Signal
Designation Current output
Secondary rated current range Isn 0 A AC ... 1 A AC
Surge current limitation factor FS 10
Accuracy class 1

Width 73 mm
Height 35 mm
Depth 22 mm
Primary round conductor (diameter) 13 mm
Item dimensions
Width 73 mm
35 mm
Depth 22 mm
Circular conductor
Diameter 13 mm (Inner hole)
Signal line
Length 3 m

Flammability rating according to UL 94 V0
Housing material PC

Ambient conditions
Ambient temperature (operation) -40 °C ... 65 °C
Ambient temperature (storage/transport) -45 °C ... 80 °C
Altitude ≤ 2000 m
Permissible humidity (operation) Use only indoors, non-condensing

Standards/regulations IEC 61010-1
IEC 61010-2-032
IEC 61869-1
IEC 61869-2

Item number 1382384
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C04
Product Key CK4A12
GTIN 4063151753849
Weight per Piece (including packing) 280 g
Weight per Piece (excluding packing) 280 g
Customs tariff number 85043180
Country of origin CN


ECLASS

ECLASS-9.0 27210902
ECLASS-10.0.1 27210902
ECLASS-11.0 27210902
ECLASS-12.0 27210902

ETIM

ETIM 8.0 EC002048

UNSPSC

UNSPSC 21.0 39121000

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values