Current transformer - PACT RCP-4000A-UIRO-D140
2906232

Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 450 mm in length/140 mm in diameter for AC current measurement on busbars and power lines.
The signal conditioner outputs 8 different standard signals on the output side and has one switching output.

Free Download available. Downloads

Product Details




Product type Current transformer
Insulation characteristics
Overvoltage category II
Pollution degree 2

Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Typical measuring error < 1 %
Protective circuit Surge protection; 33 V suppressor diode
Step response (0–99%) 110 ms
Rated insulation voltage 300 V
Measuring coil
Conductor structure signal line 2x 0.22 mm (Signal (tinned))
1x 0.22 mm (Shielding (tinned))
Insulation double insulation
Rated insulation voltage 1000 V AC (rms CAT III)
600 V AC (rms CAT IV)
Test voltage 10.45 kV DC (60 s)
Basic accuracy <± 0.2 %
Measuring transducers
Maximum transmission error ≤ 0.5 % (From the range end value)
Frequency range 16 Hz ... 1000 Hz
Test voltage 3 kV (50 Hz, 1 min.)
General
Can be calibrated no
Class 1
Accuracy class 1
Converter type Rogowski coil and 4-way signal conditioner
Supply: Measuring transducers
Nominal supply voltage 24 V DC
Nominal supply voltage range 9.6 V DC ... 30 V DC
Power consumption ≤ 1 W (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)

Frequency
Designation Measuring coil
Frequency measuring range 40 Hz ... 20000 Hz
Position error <± 0.1 % (typical)
Linearity error < 0.1 %
Signal
Input signal (at 50 Hz) 100 mV (1000 A)
Curve type Sine
Input impedance > 100 kΩ
Current transformers
Configurable/programmable Via DIP switches
Rated frequency: Standard converter 40 Hz ... 20000 Hz
Primary rated current Ipn 0 A AC ... 100 A AC
0 A AC ... 250 A AC
0 A AC ... 400 A AC
0 A AC ... 630 A AC
0 A AC ... 1000 A AC
0 A AC ... 1500 A AC
0 A AC ... 2000 A AC
0 A AC ... 4000 A AC
Can be calibrated no
Class 1
Accuracy class 1
Converter type Rogowski coil and 4-way signal conditioner

Switching: Transistor
Number of outputs 1
Contact type 1 N/O contact
Minimum switching voltage 1 V
Maximum switching voltage 30 V DC
Min. switching current 100 µA
Max. switching current 100 mA (at 30 V)
Signal
Designation Measuring coil
Output signal (at 50 Hz) 100 mV (no load, at 1,000 A)
Output voltage (in no-load operation) VOUT = M * dI/dt
Output voltage (sinusoidal, in no-load operation) 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A))
Accuracy class 1
Signal
Designation Measuring transducer
Configurable/programmable Yes
Voltage output signal 0 V ... 10 V (via DIP switch)
2 V ... 10 V (via DIP switch)
0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
0 V ... 10.5 V (can be set via software)
Max. voltage output signal  12.3 V
Current output signal 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
0 mA ... 10 mA (via DIP switch)
2 mA ... 10 mA (via DIP switch)
0 mA ... 21 mA (can be set via software)
Max. current output signal 24.6 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output ≤ 600 Ω (20 mA)
Ripple < 20 mVPP
< 20 mVPP

Measuring transducer side
Connection method Screw connection
Stripping length 10 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 26 ... 16
Tightening torque 0.5 Nm ... 0.6 Nm

Width 6.2 mm
Height 110.5 mm
Depth 120.5 mm
Item dimensions
Width 6.2 mm
Width 6.2 mm
Height 110.5 mm
Depth 120.5 mm
Measuring coil
Length 450 mm
Diameter 8.3 mm ±0.2 mm
Measuring coil when installed
Diameter 140 mm
Signal line
Length 3 m

Coil material Elastollan
Housing material PC
PBT

Ambient conditions
Measuring coil degree of protection IP67 (not assessed by UL)
Measuring transducer degree of protection IP20
Ambient temperature (operation) -30 °C ... 80 °C (Measuring coil)
-40 °C ... 70 °C (Measuring transducer)
Ambient temperature (storage/transport) -40 °C ... 80 °C (Measuring coil)
-40 °C ... 85 °C (Measuring transducer)
Altitude < 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

CE
Certificate CE-compliant
UKCA
Certificate UKCA-compliant
CMIM
Certificate CMIM-compliant
UL, USA / Canada
Identification UL 61010 Recognized
Note Measuring coil
UL, USA / Canada
Identification UL 508 Listed
Note Measuring transducer

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.

Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Standards/regulations IEC 61010-1
IEC 61010-2-032

Mounting type DIN rail mounting

Item number 2906232
Packing unit 1 pc
Minimum order quantity 1 pc
Note Made to Order (non-returnable)
Sales Key C04
Product Key CK4A12
Catalog Page Page 223 (C-5-2019)
GTIN 4055626048291
Weight per Piece (including packing) 471.7 g
Weight per Piece (excluding packing) 448 g
Customs tariff number 85437090
Country of origin DE


ECLASS

ECLASS-9.0 27210902
ECLASS-10.0.1 27210902
ECLASS-11.0 27210902
ECLASS-12.0 27210902

ETIM

ETIM 8.0 EC002048

UNSPSC

UNSPSC 21.0 39121000

EAC

Approval ID: RU*DE*08.B.01187/19

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products