PACT RCP-4000A-1A-D95-5M
-
Current transformer
2910325
Set consisting of a 1 A measuring transducer and a Rogowski coil with signal line. Length of Rogowski coil: 300 mm, diameter: 95 mm. Length of signal line: 5 m. The Rogowski coil measures the AC current of busbars and power lines.
Product details
Product type | Current transformer |
Data management status | |
Article revision | 08 |
Insulation characteristics | |
Insulation | double insulation |
Overvoltage category | III (1000 V, to neutral conductor) |
IV (600 V, to neutral conductor) | |
Pollution degree | 2 |
Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
Typical measuring error | < 1 % |
Protective circuit | Surge protection; 33 V suppressor diode |
Temperature coefficients | 0.005 %/K (+10 °C ... +70 °C, both components have the same ambient temperature) |
0.07 %/K (-20 °C ... +10 °C, both components have the same ambient temperature) | |
Measuring coil | |
Conductor structure signal line | 2x 0.22 mm (Signal (tinned)) |
1x 0.22 mm (Shielding (tinned)) | |
Insulation | double insulation |
Rated insulation voltage | 1000 V AC (rms CAT III) |
600 V AC (rms CAT IV) | |
Test voltage | 10.45 kV DC (60 s) |
Basic accuracy | <± 0.2 % |
Measuring transducers | |
Linearity error | < 0.5 % (From the range end value) |
Maximum transmission error | ≤ 0.5 % (From the range end value) |
Frequency range | 45 Hz ... 65 Hz |
Max. detectable harmonics | < 2 kHz |
Current consumption | < 190 mA (at 19.2 V) |
Test voltage | 1.5 kV AC (Supply/input and output: 50 Hz, 1 min) |
General | |
Can be calibrated | no |
Class | 1 |
Accuracy class | 1 |
Converter type | Rogowski coil and 1 A measuring transducer |
Supply: Measuring transducers | |
Nominal supply voltage | 24 V DC -20 % ... +25 % |
Nominal supply voltage range | 19.2 V DC ... 30 V DC |
Max. current consumption | 190 mA |
Power consumption | 4 W |
Frequency | |
Designation | Measuring coil |
Frequency measuring range | 40 Hz ... 20000 Hz |
Position error | <± 0.1 % (typical) |
Linearity error | < 0.1 % |
Signal | |
Input signal (at 50 Hz) | 100 mV (1000 A) |
Curve type | Sine |
Input impedance | 27 kΩ (smallest measuring range) |
Current transformer | |
Configurable/programmable | Via DIP switches |
Rated power | 1.25 VA |
Primary rated current Ipn | 0 A AC ... 100 A AC |
0 A AC ... 250 A AC | |
0 A AC ... 400 A AC | |
0 A AC ... 630 A AC | |
0 A AC ... 1000 A AC | |
0 A AC ... 1500 A AC | |
0 A AC ... 2000 A AC | |
0 A AC ... 4000 A AC | |
Phase angle | < 1 ° |
Can be calibrated | no |
Class | 1 |
Accuracy class | 1 |
Converter type | Rogowski coil and 1 A measuring transducer |
Signal | |
Designation | Measuring coil |
Output signal (at 50 Hz) | 100 mV (no load, at 1,000 A) |
Output voltage (in no-load operation) | VOUT = M * dI/dt |
Output voltage (sinusoidal, in no-load operation) | 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A)) |
Accuracy class | < 1 |
Signal | |
Designation | Measuring transducer |
Current output signal | 0 A AC ... 1 A AC |
Rated power | 1.25 VA |
Load | 0 Ω ... 1.25 Ω |
Max. distances for copper cables at PN max | 16 m (0.75 mm² (AWG 20)) |
32 m (1.5 mm² (AWG 16)) | |
55 m (2.5 mm² (AWG 14)) |
Measuring transducer side | |
Connection method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Operating voltage display | Green LED |
Item dimensions | |
Width | 22.5 mm |
Height | 85 mm |
Depth | 70.4 mm |
Measuring coil | |
Length | 300 mm |
Diameter | 8.3 mm ±0.2 mm |
Measuring coil when installed | |
Diameter | 95 mm |
Signal line | |
Length | 5 m |
Width | 22.5 mm |
Height | 85 mm |
Depth | 70.4 mm |
Housing material | PC |
Polyamide | |
Coil material | Elastollan |
Ambient conditions | |
Measuring coil degree of protection | IP67 (not assessed by UL) |
Measuring transducer degree of protection | IP20 |
Ambient temperature (operation) | -30 °C ... 80 °C (Measuring coil) |
-20 °C ... 70 °C (Measuring transducer) | |
Ambient temperature (storage/transport) | -40 °C ... 80 °C (Measuring coil) |
-25 °C ... 85 °C (Measuring transducer) | |
Altitude | < 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE | |
Certificate | CE-compliant |
UKCA | |
Certificate | UKCA-compliant |
CMIM | |
Certificate | CMIM-compliant |
UL, USA/Canada | |
Identification | UL 61010 Recognized |
Note | Measuring coil |
UL, USA/Canada | |
Identification | UL 508 Listed |
Note | Measuring transducer |
Noise immunity | EN 61000-6-3 |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
Standards/regulations | IEC 61010-1 |
IEC 61010-2-032 |
Mounting type | DIN rail mounting |
Item number | 2910325 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | C444 |
Product key | CK4A12 |
Catalog page | Page 222 (C-5-2019) |
GTIN | 4055626437644 |
Weight per piece (including packing) | 525 g |
Weight per piece (excluding packing) | 420.1 g |
Customs tariff number | 85437090 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27210902 |
ECLASS-13.0 | 27210902 |
ECLASS-12.0 | 27210902 |
ETIM
ETIM 9.0 | EC002048 |
UNSPSC
UNSPSC 21.0 | 39121000 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 6(c), 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Diboron trioxide (CAS: 1303-86-2) |
Lead monoxide (lead oxide) (CAS: 1317-36-8) | |
Lead (CAS: 7439-92-1) | |
SCIP | 9a5bde1b-92f5-45b5-8863-208b89cf0a1d |
Compatible products