Current transformer - PACT RCP-4000A-1A-D190-10M
2910327

Set consisting of a 1 A measuring transducer and a Rogowski coil with signal line. Length of Rogowski coil: 600 mm, diameter: 190 mm. Length of signal line: 10 m. The Rogowski coil measures the AC current of busbars and power lines.


Product Details




Product type Current transformer
Insulation characteristics
Overvoltage category III (1000 V, to neutral conductor)
IV (600 V, to neutral conductor)
Pollution degree 2
Insulation double insulation

Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Typical measuring error < 1 %
Protective circuit Surge protection; 33 V suppressor diode
Temperature coefficients 0.005 %/K (+10 °C ... +70 °C, both components have the same ambient temperature)
0.07 %/K (-20 °C ... +10 °C, both components have the same ambient temperature)
Measuring coil
Conductor structure signal line 2x 0.22 mm (Signal (tinned))
1x 0.22 mm (Shielding (tinned))
Insulation double insulation
Rated insulation voltage 1000 V AC (rms CAT III)
600 V AC (rms CAT IV)
Test voltage 10.45 kV DC (60 s)
Basic accuracy <± 0.2 %
Measuring transducers
Linearity error < 0.5 % (From the range end value)
Maximum transmission error ≤ 0.5 % (From the range end value)
Frequency range 45 Hz ... 65 Hz
Max. detectable harmonics < 2 kHz
Current consumption < 190 mA (at 19.2 V)
Test voltage 1.5 kV AC (Supply/input and output: 50 Hz, 1 min)
General
Can be calibrated no
Class 1
Accuracy class 1
Converter type Rogowski coil and 1 A measuring transducer
Supply: Measuring transducers
Nominal supply voltage 24 V DC -20 % ... +25 %
Nominal supply voltage range 19.2 V DC ... 30 V DC
Max. current consumption 190 mA
Power consumption 4 W

Frequency
Designation Measuring coil
Frequency measuring range 40 Hz ... 20000 Hz
Position error <± 0.1 % (typical)
Linearity error < 0.1 %
Signal
Input signal (at 50 Hz) 100 mV (1000 A)
Curve type Sine
Input impedance 27 kΩ (smallest measuring range)
Current transformers
Configurable/programmable Via DIP switches
Rated power 1.5 VA
Primary rated current Ipn 0 A AC ... 100 A AC
0 A AC ... 250 A AC
0 A AC ... 400 A AC
0 A AC ... 630 A AC
0 A AC ... 1000 A AC
0 A AC ... 1500 A AC
0 A AC ... 2000 A AC
0 A AC ... 4000 A AC
Phase angle < 1 °
Can be calibrated no
Class 1
Accuracy class 1
Converter type Rogowski coil and 1 A measuring transducer

Signal
Designation Measuring coil
Output signal (at 50 Hz) 100 mV (no load, at 1,000 A)
Output voltage (in no-load operation) VOUT = M * dI/dt
Output voltage (sinusoidal, in no-load operation) 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A))
Accuracy class < 1
Signal
Designation Measuring transducer
Current output signal 0 A AC ... 1 A AC
Rated power 1.5 VA
Load 0 Ω ... 1.5 Ω
Max. distances for copper cables at PN max 32 m (0.75 mm² (AWG 20))
64 m (1.5 mm² (AWG 16))
107 m (2.5 mm² (AWG 14))

Measuring transducer side
Connection method Screw connection
Stripping length 7 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Tightening torque 0.5 Nm ... 0.6 Nm

Operating voltage display Green LED

Width 22.5 mm
Height 85 mm
Depth 70.4 mm
Item dimensions
Width 22.5 mm
85 mm
Depth 70.4 mm
Measuring coil
Length 600 mm
Diameter 8.3 mm ±0.2 mm
Measuring coil when installed
Diameter 190 mm
Signal line
Length 10 m

Coil material Elastollan
Housing material PC
Polyamide

Ambient conditions
Measuring coil degree of protection IP67 (not assessed by UL)
Measuring transducer degree of protection IP20
Ambient temperature (operation) -30 °C ... 80 °C (Measuring coil)
-20 °C ... 70 °C (Measuring transducer)
Ambient temperature (storage/transport) -40 °C ... 80 °C (Measuring coil)
-25 °C ... 85 °C (Measuring transducer)
Altitude < 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

CE
Certificate CE-compliant
UKCA
Certificate UKCA-compliant
CMIM
Certificate CMIM-compliant
UL, USA / Canada
Identification UL 61010 Recognized
Note Measuring coil
UL, USA / Canada
Identification UL 508 Listed
Note Measuring transducer

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-3

Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Standards/regulations IEC 61010-1
IEC 61010-2-032

Mounting type DIN rail mounting

Item number 2910327
Packing unit 1 pc
Minimum order quantity 1 pc
Note Made to Order (non-returnable)
Sales Key C04
Product Key CK4A12
Catalog Page Page 222 (C-5-2019)
GTIN 4055626437668
Weight per Piece (including packing) 643 g
Weight per Piece (excluding packing) 618.9 g
Customs tariff number 85437090
Country of origin DE


ECLASS

ECLASS-9.0 27210902
ECLASS-10.0.1 27210902
ECLASS-11.0 27210902
ECLASS-12.0 27210902

ETIM

ETIM 8.0 EC002048

UNSPSC

UNSPSC 21.0 39121000

EAC

Approval ID: RU*DE*08.B.01187/19

EAC

Approval ID: RU*DE*08.B.01187/19

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”