Current transducers - MACX MCR-SL-CAC-12-I-UP
2810638

Current measuring transducer for 5 A and 12 A AC, the output signal 0...20 mA or 4...20 mA, can be configured using a DIP switch with an operating mode indication through an LED


Product Details




Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Product type Current transducer
Insulation characteristics
Overvoltage category III
Pollution degree 2

Maximum power dissipation for nominal condition < 0.9 W (24 V DC)
< 3.4 W (230 V AC)
Protective circuit Surge protection; 35 V suppressor diode
Step response (10-90%) ≤ 300 ms
200 ms
Maximum temperature coefficient < 0.02 %/K
Temperature coefficient, typical < 0.015 %/K
Maximum transmission error ≤ 0.5 % (of nominal range value under nominal conditions)
Reverse polarity protection yes
Rated insulation voltage 300 V AC (to earth)
Electrical isolation Input/output
Test voltage 4 kV AC (50 Hz, 60 s)
Electrical isolation Output/supply
Test voltage 2 kV AC (50 Hz, 60 s)
Supply
Supply voltage range 19.2 V AC/DC ... 253 V AC/DC
Max. current consumption < 33 mA (24 V DC)
Power consumption < 0.8 W (24 V DC)

Measurement
Configurable/programmable Via DIP switches
Input current range 0 A AC ... 5 A AC (configurable)
0 A AC ... 12 A AC (configurable)
Voltage input signal ≤ 300 V AC
Input impedance < 50 mΩ
Overload capacity 1 x IN (continuous)
Surge strength 8 x IN (1 s)
Nominal frequency fN 50 Hz
Frequency measuring range 45 Hz ... 65 Hz
Connection method Screw terminal block
Curve type Sine

Signal: Current
Output name Current output
Configurable/programmable Via DIP switches
Non-load voltage 15 V
Current output signal 0 mA ... 20 mA (configurable)
4 mA ... 20 mA (configurable)
Max. current output signal 25 mA
Load/output load current output < 500 Ω (20 mA)
Ripple < 10 mVPP (500 Ω / 20 mA)
Status display LED red (error), LED green (ready)

Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14

Data communication (bypass)
Limit frequency (3 dB) approx. 3 Hz

Dimensional drawing
Width 22.5 mm
Height 104 mm
Depth 114.5 mm

Housing material Polyamide PA non-reinforced

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 65 °C
-4 °F ... 149 °F
Ambient temperature (storage/transport) -40 °C ... 85 °C (-40 °F ... 185 °F)
Altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)

CE
Certificate CE-compliant
ATEX
Identification  II 3 G Ex nA IIC T4 Gc X
UKCA Ex (UKEX)
Identification  II 3 G Ex nA IIC T4 Gc
Certificate PxCIF21UKEX2810638X
EAC Ex
Identification  2Ex nA IIC T4 Gc
Certificate BY/112 02.01 TP012 103.01 00078

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Comments Criterion B
Surge current load (surge)
Standards/regulations EN 61000-4-5
Surge current load (surge)
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6

Mounting type DIN rail mounting
Mounting position any

Item number 2810638
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C04
Product Key CK4A21
Catalog Page Page 234 (C-5-2019)
GTIN 4046356510356
Weight per Piece (including packing) 218.6 g
Weight per Piece (excluding packing) 140 g
Customs tariff number 85437090
Country of origin DE


ECLASS

ECLASS-9.0 27210123
ECLASS-10.0.1 27210123
ECLASS-11.0 27210123

ETIM

ETIM 8.0 EC002475

UNSPSC

UNSPSC 21.0 39121000

EAC Ex

Approval ID: RU C-DE.AB72.B.02066

ATEX

Approval ID: 2810638_Ex-n

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products

Your advantages

Input/output can be configured via DIP switches