Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Product type Signal conditioner
No. of channels 1
Configuration DIP switches
Insulation characteristics
Overvoltage category II
Pollution degree 2

No. of channels 1
Electrical isolation Basic insulation according to EN 61010
Electrical isolation between input and output yes
Limit frequency (3 dB) 100 Hz / 30 Hz switchable
Step response (10-90%) 3.5 ms (100 Hz)
Maximum temperature coefficient < 0.01 %/K
Temperature coefficient, typical < 0.002 %/K
Maximum transmission error ≤ 0.2 %
< 0.4 % (Without adjustment)
Electrical isolation Input/output/power supply
Rated insulation voltage 30 V AC
50 V DC
Test voltage 1.5 kV AC (50 Hz, 60 s)
Supply
Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Item No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption < 25 mA
Power consumption < 450 mW (Current output)

Signal: Voltage input
Number of inputs 1
Configurable/programmable Yes, unconfigured
Voltage input signal -50 mV ... 50 mV
-60 mV ... 60 mV
-75 mV ... 75 mV
-80 mV ... 80 mV
-100 mV ... 100 mV
-120 mV ... 120 mV
-150 mV ... 150 mV
-200 mV ... 200 mV
-240 mV ... 240 mV
-300 mV ... 300 mV
-500 mV ... 500 mV
-600 mV ... 600 mV
-750 mV ... 750 mV
-800 mV ... 800 mV
-1 V ... 1 V
-1.2 V ... 1.2 V
-1.5 V ... 1.5 V
-2 V ... 2 V
-2.4 V ... 2.4 V
-3 V ... 3 V
0 mV ... 50 mV (additional areas can be configured, see table)
0 mV ... 60 mV
0 mV ... 75 mV
0 mV ... 80 mV
0 mV ... 100 mV
0 mV ... 120 mV
0 mV ... 150 mV
0 mV ... 200 mV
0 mV ... 240 mV
0 mV ... 300 mV
0 mV ... 500 mV
0 mV ... 600 mV
0 mV ... 750 mV
0 mV ... 800 mV
0 V ... 1 V
0 V ... 1.2 V
0 V ... 1.5 V
0 V ... 2 V
0 V ... 2.4 V
0 V ... 3 V
Max. voltage input signal approx. 3 V DC
Input resistance of voltage input approx. 10 kΩ

Signal: Voltage/current
Output name Voltage output / current output
Number of outputs 1
Configurable/programmable Yes, unconfigured
Voltage output signal 0 V ... 10 V
2 V ... 10 V
0 V ... 5 V
1 V ... 5 V
-10 V ... 10 V (The bi-polar output can be used only for bi-polar input signals.)
-5 V ... 5 V (The bi-polar output can be used only for bi-polar input signals.)
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output < 500 Ω (at 20 mA)
Ripple < 20 mVPP (at 500 Ω)
< 20 mVPP (at 10 kΩ)

Connection method Screw connection
Connection technology 2-conductor
Stripping length 12 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12

Dimensional drawing
Width 6.2 mm
Height 93.1 mm
Depth 102.5 mm

Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
Housing material PBT

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

CE
Designation CE
Certificate CE-compliant
CE
Designation UKCA
Certificate UKCA-compliant
CE
Designation UL, USA / Canada
Identification UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
CE
Designation Shipbuilding approval
Certificate DNV GL TAA000020N
DNV GL data
Temperature B
Humidity B
Vibration B
EMC A
Enclosure Required protection according to the Rules shall be provided upon installation on board

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Comments Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 6 %
Fast transients (burst)
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 6 %
Surge current load (surge)
Standards/regulations EN 61000-4-5
Surge current load (surge)
Comments Criterion B
Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 6 %

Electrical isolation Basic insulation according to EN 61010

Mounting type DIN rail mounting
Assembly instructions The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position any

Item number 2810780
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CK1211
Product Key CK1211
Catalog Page Page 94 (C-7-2015)
GTIN 4046356305341
Weight per Piece (including packing) 117.8 g
Weight per Piece (excluding packing) 117.7 g
Country of origin DE


ECLASS

ECLASS-9.0 27210120
ECLASS-10.0.1 27210120
ECLASS-11.0 27210120

ETIM

ETIM 8.0 EC002653

UNSPSC

UNSPSC 21.0 39121000

cUL Recognized

Approval ID: FILE E 238705

UL Recognized

Approval ID: FILE E 238705

DNV GL

Approval ID: TAA00000N1

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Power supply possible via the foot element (TBUS)
Ideal for converting signals for shunt measurements
Low power consumption
Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of mV signals to create standard analog signals
Up to 280 signal combinations can be configured using DIP switches
3-way isolation