Redundancy module - QUINT4-DIODE/48DC/2X20/1X40
2907720

DIN rail diode module 48 V DC/2x20 A or 1x40 A. Uniform redundancy up to the consumer.


Product Details


A safe redundant system is the result of the parallel connection of two power supply units which are decoupled from one another. To further increase system availability, QUINT DIODE provides the solution: decoupling with diode.



DC operation
Nominal input voltage range 48 V DC
Input voltage range 30 V DC ... 56 V DC
Voltage type of supply voltage DC
Reverse polarity protection < yes120 V
Maximum current Imax 2x 30 A (-40 °C ... 40 °C)
1x 60 A (-40 °C ... 40 °C)
Input current IStatic 2x 25 A (40 °C)
Input current IDynamic 2x 30 A (5 s)
Input current ISFB 2x 120 A (15 ms)
Maximum current Imax 2x 30 A (-25°C ... 40°C)
1x 60 A (-25°C ... 40°C)
Transient surge protection Varistor
Voltage drop, input/output 0.7 V
Input voltage range DC 30 V DC ... 56 V DC

Efficiency > 97 %
Nominal output voltage 48 V DC
Output voltage UIn -
Nominal output current (IN) 40 A (Increasing power)
20 A (Redundancy)
Derating 60 °C ... 70 °C (2.5%/K)
Power loss nominal load max. 14 W (IOUT = 20 A)
Connection in series No
Derating 60 °C ... 70 °C 2.5 %/K

Input
Connection method Screw connection
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section flexible min. 0.5 mm²
Conductor cross section flexible max. 16 mm²
Conductor cross section AWG min. 10
Conductor cross section AWG max. 6
Stripping length 10 mm
Screw thread M4
Tightening torque, min 1.2 Nm
Tightening torque max 1.5 Nm
Output
Connection method Screw connection
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section flexible min. 0.5 mm²
Conductor cross section flexible max. 16 mm²
Conductor cross section AWG min. 10
Conductor cross section AWG max. 6
Stripping length 10 mm
Screw thread M4
Tightening torque, min 1.2 Nm
Tightening torque max 1.5 Nm

Insulation voltage input, output / housing 1000 V

Product type Redundancy module
MTBF (IEC 61709, SN 29500) 40000000 h (40 °C)
Insulation characteristics
Protection class III
Degree of pollution 2

Width 50 mm
Height 130 mm
Depth 125 mm
Installation dimensions
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm

Mounting type DIN rail mounting
Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting position horizontal DIN rail NS 35, EN 60715

Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Housing material Metal
Housing material Aluminum / stainless steel

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 5000 m
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Conformity/Approvals
ATEX  II 3 G Ex ec IIC T4 Gc
DEKRA 20ATEX0041 X
IECEx Ex ec IIC T4 Gc
IECEx DEK 20.0022X

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2

Item number 2907720
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CMRI44
Product Key CMRI44
Catalog Page Page 307 (C-4-2019)
GTIN 4055626231396
Weight per Piece (including packing) 879 g
Weight per Piece (excluding packing) 879 g
Country of origin CN


ECLASS

ECLASS-9.0 27371010
ECLASS-10.0.1 27371010
ECLASS-11.0 27371010

ETIM

ETIM 8.0 EC000683

UNSPSC

UNSPSC 21.0 32151500

cUL Recognized

Approval ID: FILE E 211944

UL Recognized

Approval ID: FILE E 211944

EAC

Approval ID: RU S-DE.BL08.W.00764

DNV GL

Approval ID: TAA000011F

UL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 123528

ATEX

Approval ID: DEKRA 20ATEX0041X

EAC Ex

Approval ID: RU C-DE.HB49.B.00004

IECEx

Approval ID: IECEx DEK 20.0022X

CCC

Approval ID: 2020322303003426

NEPSI

Approval ID: GYJ20.1591X

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

INMETRO

Approval ID: DNV 19.0186X

cULus Recognized

cULus Listed

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Flexible
Rugged design
Consistent redundancy up to the load