Digital module - AXL F DI16/1 DO8/2-2A 2H
2702291

Axioline F, Digital I/O module, Digital inputs: 16, 24 V DC, connection technology: 1-conductor, Digital outputs: 8, 24 V DC, 2 A, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors

Downloads

Product Details


The module is designed for use within an Axioline F station. It is used to acquire and output digital signals. The filter times of the inputs can be adjusted to increase noise immunity. Filter times of 100 μs enable the user to implement a counter function with a maximum input frequency of 5 kHz in the application. The outputs are protected against short circuit and overload.



Dimensional drawing
Width 35 mm
Height 129.9 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Color traffic grey A RAL 7042

Axioline F local bus
Number of interfaces 2
Connection method Bus base module
Transmission speed 100 Mbps

Module
ID code (hex) none

Digital
Input name Digital inputs
Description of the input EN 61131-2 types 1 and 3
Number of inputs 16
Connection method Push-in connection
Connection technology 1-conductor
Input voltage range "0" signal -3 V DC ... 5 V DC
Input voltage range "1" signal 11 V DC ... 30 V DC
Nominal input voltage UIN 24 V DC
Nominal input current at UIN 2.4 mA
Input filter time 3000 µs (Default)
1000 µs
< 100 µs
Protective circuit Polarity reversal protection of the inputs; parallel diode (30 V, 5 s)

Digital
Output name Digital outputs
Connection method Push-in connection
Connection technology 2-conductor
Number of outputs 8
Protective circuit Short-circuit protection, overload protection of the outputs; electronic
Output voltage 24 V DC
Maximum output current per channel 2 A
Maximum output current per module 16 A (Provide external protection; if the total current of 8 A is exceeded, connect the supply at the power connector parallel via both terminal points.)
Nominal output voltage 24 V DC
Output voltage when switched off max. 1 V
Output current when switched off max. 300 µA
Nominal load, inductive max. 48 VA (1.2 H, 12 Ω, at nominal load)
Nominal load, lamp max. 48 W (at nominal voltage)
Nominal load, ohmic max. 48 W (12 Ω, at nominal load)
Switching frequency max. 3000 per second (with at least 50 mA load current)
max. 1 per second (with inductive load)
max. 4 per second (with nominal lamp load)
Reverse voltage resistance to short pulses limited protection up to 0.5 A for 1 s
Behavior with overload Shutdown with automatic restart
Behavior with inductive overload Output can be destroyed

Type block modular
Product type I/O component
Mounting position any (no temperature derating)
Scope of delivery including bus base module and Axioline F connectors
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Current draw max. 120 mA
Power consumption max. 600 mW
Potentials: Supply for digital input and output modules (UIO)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 16 A (Provide external protection; if the total current of 8 A is exceeded, connect the supply at the power connector parallel via both terminal points.)
Power consumption max. 480 W (of which 6.4 W internal losses)
Protective circuit Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; parallel diode; with external 5 A fuse (only for commissioning)

Connection technology
Connection name Axioline F connectors (digital inputs)
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor connection
Connection method Push-in connection
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm
Axioline F connectors (digital inputs)
Connection method Push-in connection
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid 0.2 mm² ... 1.5 mm²
Stripping length 8 mm
Axioline F connectors (digital inputs)
Connection method Push-in connection
Conductor cross section, rigid 0.5 mm² ... 1.5 mm²
Stripping length 8 mm

Ambient temperature (operation) -25 °C ... 60 °C
Degree of protection IP20
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Mounting type DIN rail mounting
Mounting position any (no temperature derating)

Item number 2702291
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key DNI233
Product Key DRI233
Catalog Page Page 81 (C-6-2019)
GTIN 4055626071848
Weight per Piece (including packing) 213.2 g
Weight per Piece (excluding packing) 111 g
Country of origin DE


ECLASS

ECLASS-9.0 27242604
ECLASS-10.0.1 27242604
ECLASS-11.0 27242604

ETIM

ETIM 8.0 EC001599

UNSPSC

UNSPSC 21.0 32151600

cULus Listed

Approval ID: FILE E 238705

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

16 digital inputs according to EN 61131-2 type 1 and type 3
24 V DC, 2.4 mA
Connection of sensors in 1-conductor technology
Filter times can be adjusted in three increments: < 100 µs, 1000 µs or 3000 µs
Maximum input frequency: 5 kHz
8 digital outputs
24 V DC, 2 A
Connection of actuators in 2-conductor technology
Minimum update time of < 150 µs
Device rating plate stored