ELR H5-I-PT- 24DC/500AC-0,6
   - 
  Hybrid motor starter
    
      2903908
      
      
    
  
      Hybrid motor starter for reversing 3~ AC motors up to 500 V AC and 0.6 A output current, with 24 V DC control voltage, adjustable overload shutdown, and push-in connection.
Product details
| Notes on operation | If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board. | 
| Product type | Hybrid motor starters | 
| Product family | CONTACTRON | 
| Operating mode | 100% operating factor | 
| Number of phases | 3 | 
| Motor starter type | Reversing starter | 
| Switching frequency | ≤ 2 Hz (Load-dependent) | 
| Maximum power dissipation for nominal condition | 0.4 W | 
| Switching frequency | ≤ 2 Hz (Load-dependent) | 
| Maximum power dissipation | 1.5 W | 
| Minimum power dissipation | 1.1 W | 
| Coordination type | 1 | 
| Supply | |
| Rated control circuit supply voltage US | 24 V DC | 
| Control supply voltage range | 19.2 V DC ... 30 V DC | 
| Rated control supply current IS | 40 mA | 
| Protective circuit | Surge protection | 
| Reverse polarity protection | |
| Insulation characteristics | |
| Rated insulation voltage | 500 V | 
| Rated surge voltage | 6 kV | 
| Overvoltage category | III | 
| Degree of pollution | 2 | 
| Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit | Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC (e.g., 230/400 V AC, 277/480 V AC) | 
| Basic insulation (IEC 60947-1) at operating voltage 300 V AC ... 500 V AC | |
| Isolation characteristics between the control input and control supply voltage to auxiliary circuit | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC | 
| Control | |
| Input name | Control input right/left | 
| Rated actuating voltage UC | 24 V DC | 
| Triggering voltage range | 19.2 V DC ... 30 V DC | 
| Rated actuating current IC | 5 mA (Input type 1) | 
| Switching threshold | 9.6 V (“0” signal) | 
| 19.2 V (“1” signal) | |
| Typical turn-off time | < 30 ms | 
| Protective circuit | Reverse polarity protection | 
| AC output | |
| Rated operating voltage Ue | 500 V AC | 
| Operating voltage range | 42 V AC ... 550 V AC | 
| Rated operating current Ie | 0.6 A (AC-51) | 
| 0.6 A (AC-53a) | |
| Mains frequency | 50/60 Hz | 
| Load current range | 75 mA ... 600 mA (see to derating) | 
| Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A | 
| Cooling time | 20 min (for auto reset) | 
| Leakage current | 0 mA | 
| Protective circuit | Surge protection | 
| Acknowledge output | |
| Note | Confirmation: floating change-over contact, signal contact | 
| Contact switching type | 1 changeover contact | 
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (230 V, AC15) | 
| 2 A (24 V (DC13)) | |
| Control circuits | |
| Connection method | Push-in connection | 
| Stripping length | 10 mm | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 14 | 
| Load circuit | |
| Connection method | Push-in connection | 
| Stripping length | 10 mm | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 14 | 
| Status display | LED (yellow) | 
| Operating voltage display | Green LED | 
| Error indication | Red LED | 
| Width | 22.5 mm | 
| Height | 107.5 mm | 
| Depth | 114 mm | 
| Flammability rating according to UL 94 (Housing) | V0 (Housing) | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -25 °C ... 70 °C (observe derating) | 
| Ambient temperature (storage/transport) | -40 °C ... 80 °C | 
| Altitude | ≤ 2000 m | 
| UKCA | |
| Certificate | UKCA-compliant | 
| UL approval | |
| Certificate | NLDX.E228652 | 
| UL data | |
| SCCR | 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault))) | 
| 5 kA (500 V AC (fuse: 20 A RK5 (standard fault))) | |
| FLA | 0.6 A (500 V AC) | 
| Group installation | 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded) | 
| 30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded) | |
| Category code | NLDX / NRNT | 
| Standards/regulations | |
| Standards/regulations | IEC 60947-1 | 
| IEC 60947-4-2 | |
| Mounting type | DIN rail mounting | 
| Assembly note | alignable, for spacing see derating | 
| Mounting position | vertical (horizontal DIN rail, motor output below) | 
| Item number | 2903908 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | DK7422 | 
| Product key | DK7422 | 
| GTIN | 4046356771313 | 
| Weight per piece (including packing) | 242.5 g | 
| Weight per piece (excluding packing) | 217.7 g | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27370905 | 
| ECLASS-15.0 | 27370905 | 
ETIM
| ETIM 9.0 | EC001037 | 
UNSPSC
| UNSPSC 21.0 | 25173900 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | 
              EFUP-50
               An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. 
             | 
          
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
| SCIP | a6b2703e-733e-486c-b54c-e47a8bcce463 | 
Compatible products
- 
    
      
BRIDGE-PT 1 - Bridge 1161777
 - 
    
      
BRIDGE-PT 2 - Bridge 2904490
 - 
    
      
BRIDGE-PT 3 - Bridge 2904491
 - 
    
      
BRIDGE-PT 4 - Bridge 2904492
 - 
    
      
BRIDGE-PT 5 - Bridge 2904493
 - 
    
      
BRIDGE-PT 6 - Bridge 2904494
 - 
    
      
BRIDGE-PT 7 - Bridge 2904495
 - 
    
      
BRIDGE-PT 8 - Bridge 2904496
 - 
    
      
BRIDGE-PT 9 - Bridge 2904497
 - 
    
      
BRIDGE-PT 10 - Bridge 2904498
 - 
    
      
BRIDGE-PT 1-1M - Bridge 1161778
 - 
    
      
BRIDGE-PT-2-1M - Bridge 1049407
 - 
    
      
BRIDGE-PT-3-1M - Bridge 1049408
 - 
    
      
BRIDGE-PT-4-1M - Bridge 1049409
 - 
    
      
BRIDGE-PT-5-1M - Bridge 1049413
 - 
    
      
BRIDGE-PT-2-2M/0,3M - Bridge 1107649
 - 
    
      
BRIDGE-PT-3-2M/0,3M - Bridge 1107650
 - 
    
      
BRIDGE-PT-4-2M/0,3M - Bridge 1107644
 - 
    
      
US-EMLP (15X5) - Plastic label 0828790
 - 
    
      
UC-EMLP (15X5) - Plastic label 0819301
 
Your advantages
22.5 mm wide
        Reduction in wiring
        Space saving
        Long service life
        3-phase loop bridges
        Adjustable current for bimetal function
        Low-wear switching
        PHOENIX CONTACT Ltd
        
        Unit 15C, 906-930 Great South Road, Penrose, Auckland 1061, New Zealand