Extension module - AXC F XT SPLC 1000
1159811

The AXC F XT SPLC 1000 (SPLC 1000) is a left-alignable, safety-oriented control for operating PROFIsafe devices. The SPLC 1000 is connected to the AXC F 2152 or AXC F 3152 modular controllers from the PLCnext Control series.

Downloads

Product Details




Type Axioline
Insulation characteristics
Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Supply
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Max. current consumption 100 mA
Typical current consumption 80 mA
Potentials: Supply of the logic voltage UL
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 100 mA
typ. 80 mA
Protective circuit Reverse polarity protection; Polarity protection diode
Transient protection; Suppressor diode

Axioline F connector
Connection method Push-in connection
Conductor cross section, rigid 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm

Web server No

Function
Safety function yes

External dimensions
Width / Height / Depth 45 mm / 126.93 mm / 75 mm (The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).)

Color yellow

Safety data: EN ISO 13849
Category max. 4
Performance level (PL) max. e
Safety data: EN 62061
Safety Integrity Level Claim Limit (SIL CL) max. 3
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL) max. 3
Probability of a hazardous failure per hour (PFHD) 1 * 10-9
Duration of use 300 Months (therefore no restrictions, no maintenance intervals)

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 60 °C up to 2000 m above mean sea level
-25 °C ... 55 °C up to 3000 m above mean sea level
-25 °C ... 50 °C up to 4000 m above mean sea level
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 5 % ... 95 % (according to DIN EN 61131-2)
Shock (operation) 30g (according to EN 60068-2-27/IEC 60068-2-27)
Shock (storage/transport) 30g (according to EN 60068-2-27/IEC 60068-2-27)
Vibration (operation) 5g (according to EN 60068-2-6/IEC 60068-2-6)
Vibration (storage/transport) 5g (according to EN 60068-2-6/IEC 60068-2-6)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 58 kPa ... 106 kPa (up to 4500 m above mean sea level)
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37 Use of the device in these ambient conditions is prohibited.

Conformance with EMC directives Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion A, 2 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion A; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Noise emission test according to EN 61000-6-3/IEC 61000-6-3
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU

Mounting type DIN rail mounting

Order Key 1159811
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key DRADAG
Product Key DRADAG
GTIN 4063151166663
Weight per Piece (including packing) 304 g
Weight per Piece (excluding packing) 304 g
Customs tariff number 85371091
Country of origin DE


ECLASS

ECLASS-9.0 27242207
ECLASS-10.0.1 27242207
ECLASS-11.0 27242207

Functional Safety

Functional Safety

PROFIsafe

PROFIsafe

DNV GL

UL Listed

cUL Listed

cULus Listed


REACh SVHC Lead 7439-92-1

Your advantages

Implementation of safety-related applications up to SIL 3/PL e
PROFIsafe F-Host for up to 32 PROFIsafe F-Devices in PROFINET or Axioline
PROFIsafe F-Device for communication with a higher-level PROFIsafe F-Host SPLC
2 x diverse SCPUs with Cortex M4-based architecture
Full integration into the PLCnext Technology ecosystem