PV-SET 1000 DC/AC
-
Surge protection device set
2804458
Surge protection in IP65 housing for the AC and DC sides of an inverter for single string photovoltaic systems up to 1000 V DC.
Product details
IEC test classification | II |
T2 | |
EN type | T2 |
Type | Installation housing |
Number of positions | 2 |
Surge protection fault message | optical |
Insulation characteristics | |
Overvoltage category | III |
Pollution degree | 2 |
Nominal frequency fN | 50 Hz (60 Hz) |
Nominal voltage UN | 230 V AC (UN) |
Nominal current IN | 80 A AC/DC |
Connection method | Screw terminal blocks |
Screw thread | M5 |
Tightening torque, min | 4.5 Nm |
Stripping length | 16 mm |
Conductor cross section flexible min. | 1.5 mm² |
Conductor cross section flexible max. | 25 mm² |
Conductor cross section, rigid min. | 1.5 mm² |
Conductor cross section, rigid max. | 35 mm² |
Dimensional drawing |
|
Width | 254 mm |
Height | 180 mm |
Depth | 110 mm |
Flammability rating according to UL 94 | V0 |
Housing material | PBT/PA |
Direction of action | DC: (L+)-PE & (L-)-PE & (L+)-(L-) / AC: L-N & N-PE |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 1000 V DC |
Maximum continuous operating voltage UC (L-N) | 335 V AC |
Maximum continuous operating voltage UC (N-PE) | 260 V AC |
Rated load current IL | ≤ 80 A DC |
Protective conductor current IPE | ≤ 1 µA (AC) |
≤ 20 µA (DC) | |
Standby power consumption PC | ≤ 20 mW (DC) |
Nominal discharge current In (8/20) µs | 15 kA (DC) |
20 kA (AC) | |
Maximum discharge current Imax (8/20) µs | 30 kA (DC) |
40 kA (AC) | |
Follow current interrupt rating Ifi (N-PE) | 100 A |
Voltage protection level Up | ≤ 5 kV |
Voltage protection level Up (L-N) | ≤ 1.5 kV |
Voltage protection level Up (L-PE) | ≤ 2 kV |
Voltage protection level Up (N-PE) | ≤ 1.5 kV |
Voltage protection level Up (L+) - (L-) | ≤ 5 kV |
Voltage protection level Up (L+/L-) - PE | ≤ 5 kV |
Response time tA | ≤ 25 ns |
Response time tA (N-PE) | ≤ 100 ns |
Max. backup fuse with V-type through wiring | ≤ 80 A (gL/gG (AC side) with 16 mm²) |
Max. backup fuse with branch wiring | ≤ 125 A (gL/gG (AC side)) |
PV protective circuit AC side | |
Rated operating voltage Ue | 230 V AC |
Rated frequency fn | 50 Hz (60 Hz) |
Rated voltage Un | 230 V AC |
Rated surge voltage resistance Uimp | 6 kV |
Rated current IN | 80 A |
Protective circuit DC voltage side (DC) | |
Rated surge voltage resistance Uimp | 6 kV |
Maximum discharge current Imax (8/20) µs | 30 kA (DC) |
40 kA (AC) | |
Response time tA | ≤ 25 ns |
Impulse discharge current (10/350) µs, peak value limp | 12 kA |
Max. backup fuse with V-type through wiring | ≤ 80 A (gL/gG (AC side) with 16 mm²) |
Max. backup fuse with branch wiring | ≤ 125 A (gL/gG (AC side)) |
Nominal discharge current In (8/20) µs | 15 kA (DC) |
20 kA (AC) | |
Rated load current IL | ≤ 80 A DC |
Maximum continuous operating voltage UCPV | 1000 V DC |
Short-circuit current rating ISCPV | 80 A |
Protective conductor current IPE | ≤ 1 µA (AC) |
≤ 20 µA (DC) | |
Voltage protection level Up | ≤ 5 kV |
Voltage protection level Up (L+) - (L-) | ≤ 5 kV |
Voltage protection level Up (L+/L-) - PE | ≤ 5 kV |
Standby power consumption PC | ≤ 20 mW (DC) |
Ambient conditions | |
Degree of protection | IP65 |
Ambient conditions | A, B |
Ambient temperature (operation) | -25 °C ... 40 °C |
Altitude | max. 2000 m |
Air clearances and creepage distances | |
Standards/regulations | IEC 61643-1 / IEC 60664-1 / EN 61643-11 |
Standards/specifications | IEC 61643-1 |
Note | 2005 |
Standards/specifications | EN 61643-11/A11 |
Note | 2007 |
Mounting type | Surface/Panel mounting |
Item number | 2804458 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Note | Made to order (non-returnable) |
Product key | CL132E |
GTIN | 4046356317849 |
Weight per piece (including packing) | 1,854 g |
Weight per piece (excluding packing) | 1,764.7 g |
Country of origin | DE |
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Compatible products
PHOENIX CONTACT Ltd
Halesfield 13, Telford, Shropshire, TF7 4PG