Distributed I/O device - AXL E IOL AO1 I M12 S
2700351

Axioline E-IO-Link/analog converter for connecting an analog actuator, 4 mA ... 20 mA, M12 fast connection technology, straight version

Downloads

Product Details




Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Type Stand-alone
Axioline E
Product type Interface converter
Diagnostics messages Short circuit Message in the diagnostic code (in the IB IL format)
Configuration invalid Message in the diagnostic code (in the IB IL format)
Module faulty Message in the diagnostic code (in the IB IL format)
Insulation characteristics
Pollution degree 2

Supply: IO-Link
Nominal voltage for I/O supply 24 V DC (This supply voltage is provided via the IO-Link interface of the IO-Link master.)
Nominal current for every IO-Link port max. 100 mA
Protective circuit Reverse polarity protection
Short-circuit protection
Overload protection

IO-Link
Number of ports 1
Connection method M12 connector, A-coded
Connection technology 3-conductor

Analog
Output name Analog output
Connection method M12 connector, A-coded
Connection technology 3-conductor
Number of outputs 1 (current)
D/A converter resolution 12 bit
Data formats IB IL, S7-compatible
Current output signal 4 mA ... 20 mA
Load/output load current output max. 500 Ω
Precision < 0.25 % (of output range final value)
Permissible cable length max. 30 m (Shielded cable)

IO-Link
Amount of process data 16 Bit (Input data)
16 Bit (Output data)

Diagnostic messages
Diagnostics Short circuit
Message Message in the diagnostic code (in the IB IL format)
Diagnostic messages
Diagnostics Configuration invalid
Message Message in the diagnostic code (in the IB IL format)
Diagnostic messages
Diagnostics Module faulty
Message Message in the diagnostic code (in the IB IL format)

Dimensional drawing
Width 16.6 mm
Height 29 mm
Depth 79.5 mm

Ambient conditions
Ambient temperature (operation) -25 °C ... 60 °C
Degree of protection IP65/IP67
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 %
Permissible humidity (storage/transport) 5 % ... 95 %

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Item number 2700351
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key DRI7Z5
Product Key DRI7Z5
Catalog Page Page 183 (C-6-2019)
GTIN 4046356782654
Weight per Piece (including packing) 50.2 g
Weight per Piece (excluding packing) 34 g
Customs tariff number 85176200
Country of origin DE


ECLASS

ECLASS-9.0 27242601
ECLASS-10.0.1 27242601
ECLASS-11.0 27242601
ECLASS-12.0 27242601

ETIM

ETIM 8.0 EC001596

UNSPSC

UNSPSC 21.0

UL Listed

Approval ID: FILE E 140324

cUL Listed

Approval ID: FILE E 140324

cULus Listed


REACh SVHC Lead 7439-92-1

Compatible Products

Your advantages

Straight version
1 IO-Link interface
1 analog output
Connection of actuator in 3-conductor technology
Current range: 4 mA ... 20 mA
IO-Link and actuator connections via M12 connectors
Functional ground connection for local connection to functional ground
Supply of the module electronics and the actuator via the IO-Link interface of the IO-Link master
Diagnostic indicator
IO-Link specification V1.1.1