The terminal is designed for use within an Inline station. The single-channel power-level terminal for reversing load features electronic motor protection. It enables a three-phase asynchronous motor to be switched, protected, and monitored via a bus system. The terminal enables a three-phase asynchronous motor to be switched, protected, and monitored via a bus system.
    
  
  IB IL 400 ELR R-3A-2MBD
   - 
  Inline terminal
    
      2855130
      
      
    
  
      Inline power-level terminals, electronic reversing load starter
Product details
| Dimensional drawing |  | 
| Width | 63 mm | 
| Height | 224 mm | 
| Depth | 109 mm | 
| Inline local bus | |
| Connection method | Inline data jumper | 
| Transmission speed | 500 Mbps | 
| Transmission physics | Copper | 
| Module | |
| ID code (dec.) | 191 | 
| ID code (hex) | BF | 
| Length code (hex) | 81 | 
| Length code (dec) | 129 | 
| Process data channel | 8 bit | 
| Input address area | 1 Byte | 
| Output address area | 1 Byte | 
| Register length | 8 bit | 
| Required parameter data | 5 Byte | 
| Required configuration data | 5 Byte | 
| Product type | I/O component | 
| Product family | Inline | 
| Type | modular | 
| Diagnostics messages | Overcurrent Error message in the diagnostic code (bus) and display via the LED ERR on the module | 
| Output stage cannot be controlled Error message in the diagnostic code (bus) and display via the LED ERR on the module | 
| Potentials: Communications power (UL) | |
| Supply voltage | 7.5 V DC (via voltage jumper) | 
| Current draw | max. 60 mA | 
| Potentials: Segment circuit supply (US) | |
| Supply voltage | 24 V DC (via voltage jumper) | 
| Supply voltage range | 19.2 V DC ... 28.8 V DC (including all tolerances, including ripple) | 
| Current draw | max. 50 mA | 
| Supply: Module electronics | |
| Connection method | Through the potential jumper | 
| Designation | Terminal strips X11 and X12 | 
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: Supply voltage UL / 400 V level | 1.2 kV AC, 50 Hz, 1 min | 
| Test voltage: Supply voltage US / 400 V level | 1.2 kV AC, 50 Hz, 1 min | 
| Test voltage: Supply voltage US / brake control switch | 1.2 kV AC, 50 Hz, 1 min | 
| Test voltage: Supply voltage UL / brake control switch | 1.2 kV AC, 50 Hz, 1 min | 
| Test voltage: Local bus/400 V level | 1.2 kV AC, 50 Hz, 1 min | 
| Test voltage: Local bus/Brake control switch | 1.2 kV AC, 50 Hz, 1 min | 
| Connection technology | |
| Connection name | Motor circuit connector | 
| Conductor connection | |
| Connection method | Screw connection | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 12 | 
| Motor circuit connector | |
| Connection method | Screw connection | 
| Conductor cross-section, rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section, flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 12 | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -25 °C ... 55 °C | 
| Note | Notes on operation Line protection for the network supply line, max. 20 A. Observe derating of the POWER-COMBICON connector | 
| Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) | 
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Ambient temperature (storage/transport) | -25 °C ... 85 °C | 
| Permissible humidity (operation) | 75 % ... 85 % (in the range of -25°C ... +55°C, appropriate measures against increased humidity (> 85%) must be taken.) | 
| Permissible humidity (storage/transport) | 75 % ... 85 % (Slight temporary condensation may sometimes appear on the housing, e.g. when the terminal block is brought out of a vehicle into an enclosed room.) | 
| Protection class | I (IEC 61140, EN 61140, VDE 0140-1) | 
| Noise emission | Noise emission test of the housing EN 55011:1991 class A in accordance with EN 61000-6-4 | 
| Mounting type | DIN rail mounting | 
| Item number | 2855130 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Product key | DRI171 | 
| GTIN | 4046356044844 | 
| Weight per piece (including packing) | 604.8 g | 
| Weight per piece (excluding packing) | 584.8 g | 
| Country of origin | DE | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 
Compatible products
- 
    
      
- 
    
      IB IL 400 CN-PWR-IN - Power plug 2836078
- 
    
      IB IL 400 CN-BRG - Power bridge 2836081
- 
    
      GMVSTBW 2,5 HV/ 4-ST-7,62 NZIL - PCB connector 1893957
- 
    
      IB IL FIELD 8 - Marking field 2727515
- 
    
      ESL 62X46 - Insert strip 0809502
- 
    
      IB IL 400 CN-COV - Cover 2860947
- 
    
      IB IL 24 BR/DC - Inline terminal 2742036
- 
    
      IB IL 400 BR - Inline terminal 2727394
PHOENIX CONTACT Ltd
        
        Halesfield 13, Telford, Shropshire, TF7 4PG