IECEE CB Scheme
Approval ID: DK-114506-ULNominal Voltage UN | Nominal Current IN | Cross Section AWG | Cross Section mm2 | |
---|---|---|---|---|
Redundancy module, QUINT ORING, 12 V DC ... 24 V DC, 2x 20 A
Nominal input voltage range | 12 V DC ... 24 V DC |
Input voltage range | 8 V DC ... 29.5 V DC |
Voltage type of supply voltage | DC |
Nominal input current (IN) | 2x 20 A |
Static Boost (IStat.Boost) | 2x 25 A |
Dynamic Boost (IDyn.Boost) | 2x 30 A (5 s) |
Selective Fuse Breaking (ISFB) | 2x 120 A (15 ms) |
Reverse polarity protection | < yes60 V DC |
Intended listed circuit breaker for input protection | 60 V DC |
Intended listed circuit breaker for input protection | 16 A (Characteristic B, C) |
Voltage drop, input/output | typ. 0.1 V (IOUT = 20 A) |
Efficiency | typ. 99 % (12 V DC) |
typ. 99 % (24 V DC) | |
Output voltage | UIn - |
Nominal output current (IN) | 2x 20 A |
Static Boost (IStat.Boost) | 2x 25 A |
Dynamic Boost (IDyn.Boost) | 2x 30 A (5 s) |
Selective Fuse Breaking (ISFB) | 2x 120 A (15 ms) |
Connection in series | No |
Feedback voltage resistance | ≤ 32 V DC |
Protection against overvoltage at the output (OVP) | ≤ 32 V DC |
Power loss nominal load max. | 4.08 W (IOUT = 40 A) |
4.25 W (IOUT = 20 A) | |
Signal relay 13/14 | |
Connection labeling | 3.1, 3.2 |
Switch contact (floating) | floating |
Maximum contact load | 100 mA |
Signal relay 23/24 | |
Connection labeling | 3.3, 3.4 |
Switch contact (floating) | floating |
Maximum contact load | 100 mA |
Signal option | ACB OK |
Conductor connection | |
Connection method | Screw connection |
rigid | 0.2 mm² ... 6 mm² |
flexible | 0.2 mm² ... 4 mm² |
flexible with ferrule without plastic sleeve | 0.25 mm² ... 4 mm² |
flexible with ferrule with plastic sleeve | 0.25 mm² ... 4 mm² |
rigid (AWG) | 24 ... 10 |
Stripping length | 8 mm |
Torque | 0.5 Nm ... 0.6 Nm |
Drive form screw head | Slotted L |
Conductor connection | |
Connection method | Screw connection |
rigid | 0.2 mm² ... 6 mm² |
flexible | 0.2 mm² ... 4 mm² |
flexible with ferrule without plastic sleeve | 0.25 mm² ... 4 mm² |
flexible with ferrule with plastic sleeve | 0.25 mm² ... 4 mm² |
rigid (AWG) | 24 ... 10 |
Stripping length | 8 mm |
Torque | 0.5 Nm ... 0.6 Nm |
Drive form screw head | Slotted L |
Conductor connection | |
Connection method | Push-in connection |
rigid | 0.2 mm² ... 1 mm² |
flexible | 0.2 mm² ... 1.5 mm² |
flexible with ferrule without plastic sleeve | 0.2 mm² ... 1.5 mm² |
flexible with ferrule with plastic sleeve | 0.2 mm² ... 0.75 mm² |
rigid (AWG) | 24 ... 16 |
Stripping length | 8 mm |
Types of signaling | DC OK (green) |
Signal threshold | Redundancy OK (LED lights up green) |
I < In (LED lights up green) | |
ACB OK (LED lights up green) | |
ACB OK (sources are slightly asymmetrical) (LED lights up green and yellow) | |
Sources are asymmetrical (LED flashing red) |
Insulation voltage input, output / housing | 500 V AC |
710 V DC |
Product type | Redundancy module |
MTBF (IEC 61709, SN 29500) | > 1112000 h (25 °C) |
> 673000 h (40 °C) | |
> 309000 h (60 °C) | |
Environmental protection directive | RoHS Directive 2011/65/EU |
WEEE | |
Reach | |
Insulation characteristics | |
Protection class | III |
Degree of pollution | 2 |
Life expectancy (electrolytic capacitors) | |
Current | 20 A |
Temperature | 40 °C |
Time | 295000 h |
Additional text | 12 V DC |
Life expectancy (electrolytic capacitors) | |
Current | 20 A |
Temperature | 40 °C |
Time | 240000 h |
Additional text | 24 V DC |
Width | 46 mm |
Height | 130 mm |
Depth | 125 mm (Device depth (DIN rail mounting)) |
Depth | 132 mm |
Installation dimensions | |
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Alternative assembly | |
Width | 122 mm |
Height | 130 mm |
Depth | 49 mm |
Mounting type | DIN rail mounting |
Assembly instructions | alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
Housing material | Metal |
Type of housing | Aluminum (AlMg3) |
Hood version | Galvanized sheet steel, free from chrome (VI) |
Side element version | Aluminum |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | 5000 m |
Max. permissible relative humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) |
Shock (operation) | 18 ms, 30g, per spatial direction (IEC 60068-2-27) |
Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (IEC 60068-2-6) |
15 Hz ... 150 Hz, 2.3g, 90 min. |
Electrical safety | |
Standards/specifications | IEC 61010-1 |
Electrical safety | |
Standards/specifications | EN 61010-1 (SELV) |
Electrical safety | |
Standards/specifications | IEC 61010-2-201 (PELV) |
Shipbuilding | |
Identification | DNV |
Shipbuilding | |
Identification | UL Listed UL 61010-1 |
Shipbuilding | |
Identification | UL Listed UL 61010-2-201 |
Shipbuilding | |
Identification | UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
Shipbuilding | |
Identification | CAN/CSA-C22.2 No. 61010-1-12 |
Shipbuilding | |
Identification | CAN/CSA C22.2 No. 61010-2-201:18 |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
EMC requirements for noise emission | EN 61000-6-3 |
EN 61000-6-4 | |
EMC requirements for noise immunity | EN 61000-6-1 |
EN 61000-6-2 | |
Conducted noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Interference emission | Noise emission according to EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
Noise emission | Additional basic standard EN 61000-6-5 (immunity in power station) |
Noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Noise immunity | Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone ) |
DNV GL conducted interference | Class B |
Additional text | Bridge and deck area |
DNV GL noise radiation | Class B |
Additional text | Bridge and deck area |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Contact discharge | 6 kV (Test Level 4) |
Discharge in air | 8 kV (Test Level 4) |
Comments | Criterion B |
Electromagnetic HF field | |
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field | |
Frequency range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m (Test Level 3) |
Frequency range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | |
Standards/regulations | EN 61000-4-4 |
Fast transients (burst) | |
Input | 2 kV (Test Level 4 - asymmetrical) |
Output | 2 kV (Test Level 4 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge) | |
Standards/regulations | EN 61000-4-5 |
Input | 0.5 kV (Test Level 1 - symmetrical) |
1 kV (Test Level 2 - asymmetrical) | |
Output | 0.5 kV (Test Level 2 - symmetrical) |
1 kV (Test Level 2 - asymmetrical) | |
Comments | Criterion A |
Conducted interference | |
Standards/regulations | EN 61000-4-6 |
Conducted interference | |
I/O/S | asymmetrical |
Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Item number | 1088207 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Product Key | CMRI43 |
GTIN | 4055626887753 |
Weight per Piece (including packing) | 645 g |
Weight per Piece (excluding packing) | 645 g |
Country of origin | CN |
ECLASS-11.0 | 27371010 |
ETIM 8.0 | EC000683 |
UNSPSC 21.0 | 32151500 |
Nominal Voltage UN | Nominal Current IN | Cross Section AWG | Cross Section mm2 | |
---|---|---|---|---|
REACh SVHC | Lead 7439-92-1 |