PB IP 400 ME-ELR R-3A
   - 
  Motor starter
    
      2734840
      
      
    
  
      Module electronics, one-channel electronic reverse starter, PROFIBUS-DP connection, electronic motor monitoring can be used to switch on/off a three-phase asynchronous motor
      Free download available.
      Downloads
    
  Product details
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area | 
| Type | Stand-alone | 
| Diagnostics messages | Mains failure, phase failure Error message in the diagnostic code (bus) and display via the LED ERR on the module | 
| Motor connector not plugged in, motor temperature exceeded, thermistor line short-circuited Error message in the diagnostic code (bus) and display via the LED ERR on the module | |
| Sensor supply failure Error message in the diagnostic code (bus) and display via the LED ERR on the module | |
| Overcurrent Error message in the diagnostic code (bus) and display via the LED ERR on the module | |
| Output stage cannot be controlled Error message in the diagnostic code (bus) and display via the LED ERR on the module | |
| Short-circuit or overload of the digital outputs Message in the diagnostic code | |
| Module error during self test Message to the master | 
| Supply: Module electronics | |
| Connection method | POWER-COMBICON | 
| Designation | Terminal strip X13 and X15 | 
| Number of positions | 2 | 
| Pg screw connection | Pg16R | 
| Supply voltage | 24 V DC (US1) | 
| Supply voltage range | 20 V DC ... 30 V DC (including ripple) | 
| Supply current | typ. 0.17 A (at US1 = 24 V; plus current of digital inputs/outputs) | 
| Ripple | Permissible ripple 3.6 Vpp within the permissible voltage range | 
| Max. current carrying capacity | 16 A | 
| Derating | from 30 °C 0.1A/K | 
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: Remote bus / supply voltage US1 | 350 kV AC, 50 Hz, 1 min | 
| Test voltage: Supply voltage US1 /400 V level | 1.2 kV AC, 50 Hz, 1 min | 
| Test voltage: Supply voltage US1 / brake relay | 1.2 kV AC, 50 Hz, 1 min | 
| Test voltage: Supply voltage US1 / thermistor inputs | 1.2 kV AC, 50 Hz, 1 min | 
| Test voltage: Local bus/400 V level | 1.2 kV AC, 50 Hz, 1 min | 
| Test voltage: Remote bus/brake relay | 1.2 kV AC, 50 Hz, 1 min | 
| Test voltage: Remote bus/thermistor inputs | 1.2 kV AC, 50 Hz, 1 min | 
| Digital: Digital inputs | |
| Number of inputs | 4 | 
| Connection method | M12 connector, A-coded | 
| Connection technology | 3-, 4-conductor | 
| Number of positions | 5 | 
| Input voltage | 24 V DC (US1) | 
| Input voltage range "0" signal | -30 V ... 5 V (binary "0") | 
| Input voltage range "1" signal | 13 V ... 30 V (binary "1") | 
| Filter time | 3 ms | 
| Typical input current per channel | approx. 5 mA (for US1 = 24 V) | 
| PROFIBUS interface | |
| Connection method | M12 connector, B-coded | 
| Designation connection point | M12 connector; X30 (IN) and X31 (OUT) | 
| Number of positions | 5 | 
| Permissible conductor cross section | 0.25 mm² ... 0.75 mm² (flexible) | 
| Diagnostic messages | |
| Diagnostics | Mains failure, phase failure | 
| Message | Error message in the diagnostic code (bus) and display via the LED ERR on the module | 
| Diagnostic messages | |
| Diagnostics | Motor connector not plugged in, motor temperature exceeded, thermistor line short-circuited | 
| Message | Error message in the diagnostic code (bus) and display via the LED ERR on the module | 
| Diagnostic messages | |
| Diagnostics | Sensor supply failure | 
| Message | Error message in the diagnostic code (bus) and display via the LED ERR on the module | 
| Diagnostic messages | |
| Diagnostics | Overcurrent | 
| Message | Error message in the diagnostic code (bus) and display via the LED ERR on the module | 
| Diagnostic messages | |
| Diagnostics | Output stage cannot be controlled | 
| Message | Error message in the diagnostic code (bus) and display via the LED ERR on the module | 
| Diagnostic messages | |
| Diagnostics | Short-circuit or overload of the digital outputs | 
| Message | Message in the diagnostic code | 
| Diagnostic messages | |
| Diagnostics | Module error during self test | 
| Message | Message to the master | 
| Dimensional drawing | 
                 | 
            
| Width | 355 mm | 
| Height | 180 mm | 
| Depth | 100 mm | 
| Drill hole spacing | 386 mm | 
| Note on dimensions | Module electronics without lower part | 
| Technical data | |
| Drill hole spacing | 386 mm | 
| Ambient conditions | |
| Degree of protection | IP54 | 
| Ambient temperature (operation) | -20 °C ... 55 °C (non-condensing) | 
| Note | Notes on operation Line protection for the network supply line, max. 20 A. Observe derating of the POWER-COMBICON connector | 
| Notes on operation Permitted network type TN network, TT network, IT network available on request | |
| Air pressure (operation) | 86 kPa ... 106 kPa (up to 2000 m above sea level) | 
| Air pressure (storage/transport) | 86 kPa ... 106 kPa (up to 2000 m above sea level) | 
| Ambient temperature (storage/transport) | -25 °C ... 75 °C | 
| Permissible humidity (operation) | 4 % ... 100 % (non-condensing) | 
| Permissible humidity (storage/transport) | 75 % (slight temporary condensation may sometimes appear on the housing) | 
| Protection class | I (IEC 61140, EN 61140, VDE 0140-1) | 
| Noise emission | Test of emitted interference, housing, in acc. with EN 50081-2:1993 EN 55011:1991 class A | 
| Air clearances and creepage distances | |
| Air clearances and creepage distances | in accordance with EN 50178: 1998 | 
| Mounting type | Panel mounting | 
| Item number | 2734840 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Note | Made to order (non-returnable) | 
| Sales key | D06 | 
| Product key | DRFAAA | 
| GTIN | 4017918911898 | 
| Weight per piece (including packing) | 3,348.7 g | 
| Weight per piece (excluding packing) | 3,268.7 g | 
| Customs tariff number | 85371098 | 
| Country of origin | DE | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 6(c), 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | 
              EFUP-50
               An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. 
             | 
          
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
Compatible products
- 
    
      
 - 
    
      
IBS IP 400 MBH/MS - Housing 2734125
 - 
    
      
IBS IP 400 MBH/INST - Mounting base housing 2734947
 - 
    
      
IBS IP 400 MBH/FUSE - Mounting base housing 2734264
 - 
    
      
SACC-M12FSB-5CON-PG9 SH AU - Data connector 1507777
 - 
    
      
SACC-M12MSB-5CON-PG9 SH AU - Data connector 1507764
 - 
    
      
SAC-5P-M12MS PB TR - Termination resistor 1507803
 - 
    
      
IBS HVO/M12 - Operating panel 2837006
 
PHOENIX CONTACT Ltd
        