The module is designed for use within an Axioline F station. The IO-Link master enables the operation of up to eight IO-Link devices. Alternatively, you can connect a standard digital sensor or actuator to each port. When used in combination with the Axioline F bus coupler, the IO-Link master is the connecting element that integrates IO-Link devices into a higher-level bus system.
AXL F IOL8 2H
-
Communication module
1027843
Axioline F, IO-Link master, IO-Link ports Class A: 8, connection method: Push-in connection, connection technology: 3-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
Free download available.
Downloads
Product details
Dimensional drawing |
|
Width | 35 mm |
Height | 129.9 mm |
Depth | 54 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Note on application | |
Note on application | Only for industrial use |
Axioline F local bus | |
Number of interfaces | 2 |
Connection method | Bus base module |
Transmission speed | 100 Mbps |
Module | |
Process data channel | 512 bit |
Input address area | 64 Byte |
Output address area | 64 Byte |
Digital | |
Description of the input | IO-Link ports in digital input (DI) mode |
Number of inputs | max. 8 (EN 61131-2 type 1) |
Connection method | Push-in connection |
Connection technology | 3-conductor |
Nominal input voltage UIN | 24 V DC |
Input voltage range "0" signal | -0.3 V DC ... 5 V DC |
Input voltage range "1" signal | 11 V DC ... 30 V DC |
Nominal input current | typ. 2.5 mA |
Sensor current per channel | max. 1 A (from L+/L-) |
Input filter time | 1 µs |
IO-Link | |
Number of ports | 8 |
Connection method | Push-in connection |
Connection technology | 3-conductor |
Port type | Class A |
Digital | |
Output description | IO-Link ports in digital output (DO) mode |
Connection method | Push-in connection |
Connection technology | 2-, 3-conductor |
Number of outputs | max. 8 |
Nominal output voltage | 24 V DC |
Nominal current per channel | 200 mA |
Product type | I/O component |
Product family | Axioline F |
Type | block modular |
Mounting position | any (no temperature derating) |
Scope of supply | including bus base module and Axioline F connectors |
Insulation characteristics | |
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Maximum power dissipation for nominal condition | 1.7 W |
Supply: IO-Link | |
Nominal voltage for I/O supply | 24 V DC |
Supply voltage range | 18 V DC ... 30 V DC (including all tolerances, including ripple) |
Nominal current for every IO-Link port | 1 A (at L+/L-) |
200 mA (at C/Q) | |
Protective circuit | Overload protection for L+; electronically limited to 1.2 A |
Short-circuit protection for L+; by switching off after 5 ms | |
Potentials: Axioline F local bus supply (UBus) | |
Supply voltage | 5 V DC (via bus base module) |
Current draw | max. 50 mA |
Potentials: Feed-in of the supply voltage for the I/O devices (UO), including IO-Link port supply | |
Supply voltage | 24 V DC |
Supply voltage range | 18 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 8 A (in total, current consumption of I/O circuit and at C/Q as DO and at L+/L-) |
max. 60 mA (without connected peripherals) | |
Protective circuit | Surge protection; electronic (35 V, 0.5 s) |
Reverse polarity protection; parallel diode; with external 5 A fuse (only for commissioning) | |
Electrical isolation/isolation of the voltage ranges | |
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) | 500 V AC, 50 Hz, 1 min |
Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min |
Connection technology | |
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection | |
Connection method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector | |
Connection method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 60 °C |
Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Mounting position | any (no temperature derating) |
Item number | 1027843 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DRI |
Product key | DRI253 |
Catalog page | Page 89 (C-6-2019) |
GTIN | 4055626523552 |
Weight per piece (including packing) | 215 g |
Weight per piece (excluding packing) | 215 g |
Customs tariff number | 85176200 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27242608 |
ETIM
ETIM 9.0 | EC001604 |
UNSPSC
UNSPSC 21.0 | 32151600 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | cfa3d82c-783c-487e-ac47-4dfc884df865 |
Compatible products
Your advantages
Connection of eight IO-Link devices
Alternatively: connection of one digital sensor or actuator per port
Connection of IO-Link devices in 3-conductor technology
Connection of sensors in 3-conductor technology
Connection of actuators in 2- and 3-conductor technology
Parameter data storage on the master
IO-Link specification V1.1.2
Substitute value behavior of inputs and outputs can be parameterized for each port
Supports IOL-CONF (firmware version 1.02 or later)
Device rating plate stored
PHOENIX CONTACT s.r.o.
Námestie Mateja Korvína 1, 811 07 Bratislava. Zapísaná v Obchodnom registri Okresného súdu Bratislava III, vložka číslo 48994/B.