Uninterruptible power supply - QUINT-UPS/ 24DC/ 24DC/20
2320238

Uninterruptible power supply with IQ technology for DIN rail mounting, input: 24 V DC, output: 24 V DC/20 A, including mounted universal DIN rail adapter UTA 107/30

Downloads

Product Details


The UPS module for 24 V DC with output currents ranging from 5 to 40 A allows you to create a custom solution combining a power supply, UPS module, and energy storage.



DC operation
Input voltage 24 V DC
Nominal input voltage range 24 V DC
Input voltage range 18 V DC ... 30 V DC
Input voltage range DC 18 V DC ... 30 V DC
Voltage type of supply voltage DC
Buffer period 1 h (With battery module 38 AH)
Current consumption 32.9 A (maximum, mains operation)
10.5 mA (No load, mains operation)
6.9 A (Charging, mains operation)
Fixed backup threshold ≤ 22 V DC
Variable connect threshold 1 V/0.1 s

Efficiency > 98 % (Mains operation, with charged energy storage)
98 % (Battery operation)
Nominal output voltage 24 V DC
Output voltage range 18 V DC ... 30 V DC
Nominal output current (IN) 20 A (-25 °C ... 50 °C)
Output current limit In mains mode according to connected upstream current limiting device
> 27 A (Battery operation)
Bridging time 7200 s
Derating 60 °C ... 70 °C (2.5%/K)
60 °C ... 70 °C (2.5%/K)
Output power 480 W
Power dissipation 2.7 W (Mains operation)
7.65 W (Mains operation)
3.19 W (Battery operation)
9.35 W (Battery operation)
Connection in parallel yes, up to 2 modules with redundancy module
Connection in parallel 2 (Devices)
Connection in series No
Connection in series no
Mains operation
Nominal output voltage 24 V DC
Output voltage range 18 V DC ... 30 V DC
Nominal output current (IN) 20 A (-25 °C ... 60 °C)
POWER BOOST (IBoost) 26 A (-25°C ... 40°C)
Selective Fuse Breaking (ISFB) 120 A (-25 °C ... 60 °C)
Duration 12 ms (SFB technology)
Battery operation
Nominal output voltage 24 V DC
Output voltage range 19.2 V DC ... 27.6 V DC (UOUT = UBAT - 0,5 V DC)
Nominal output current (IN) 20 A (-25 °C ... 60 °C)
POWER BOOST (IBoost) 27 A (-25°C ... 40°C)
Selective Fuse Breaking (ISFB) 120 A (-25 °C ... 60 °C)
Duration 15 ms (SFB technology)
Signal: Alarm
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Continuous load current ≤ 100 mA
Signal: Battery charge
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Output voltage 24 V
Continuous load current ≤ 100 mA
Signal: Battery mode
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Output voltage 24 V
Continuous load current ≤ 100 mA
Signal: Alarm
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Continuous load current ≤ 100 mA
Signal: Battery charge
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Output voltage 24 V
Continuous load current ≤ 100 mA
Signal: Battery mode
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Output voltage 24 V
Continuous load current ≤ 100 mA
Signal: Alarm
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Continuous load current ≤ 100 mA
Signal: Battery charge
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Output voltage 24 V
Continuous load current ≤ 100 mA
Signal: Battery mode
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Output voltage 24 V
Continuous load current ≤ 100 mA
Signal: Alarm
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Continuous load current ≤ 100 mA
Signal: Battery charge
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Output voltage 24 V
Continuous load current ≤ 100 mA
Signal: Battery mode
Output description Relay (floating)
Maximum switching voltage ≤ 30 V AC/DC
Output voltage 24 V
Continuous load current ≤ 100 mA

Nominal voltage UN 24 V DC
End-of-charge voltage 24 V DC ... 29 V DC (temperature compensated)
Charge current 0.2 A ... 5 A
Nominal capacity range 3 Ah ... 200 Ah
Battery presence check/time interval 1 min.
Battery presence check (cyclic) 60 s
IQ technology Yes
Temperature compensation 42 mV/K (preset)
Temperature compensation (preset) 42 mV/K
Network management Yes

Input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 12
Conductor cross section AWG max. 10
Stripping length 8 mm
Screw thread M4
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 12
Conductor cross section AWG max. 10
Stripping length 8 mm
Screw thread M4
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Signal
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Screw thread M4
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

Interface IFS (Interface system data port)

Types of signaling LED
Relay contact
Interface/software
Signal output
Signalization designation Power In OK
Status display LED
Note on status display Static to
Static to
Signal output: Switching output
Signalization designation Alarm
Status display LED
Note on status display Static to
Color red
Note on status display Static to
Signal output: Switching output
Signalization designation Battery charge
Status display LED bar graph
Note on status display dynamic
Color green/red
Note on status display dynamic
Signal output: Switching output
Signalization designation Battery mode
Status display LED
Note on status display Static to
Color yellow
Note on status display Static to

Insulation voltage input/output 500 V DC
Insulation voltage input, output / housing 750 V DC

Product type Uninterruptible power supply
IQ technology Yes
MTBF (IEC 61709, SN 29500) > 500000 h (40 °C)
Insulation characteristics
Protection class III
Life expectancy (electrolytic capacitors)
Time 195013 h

Width 40 mm
Height 130 mm
Depth 125 mm
Installation dimensions
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm
Alternative assembly
Width 123 mm
Height 130 mm
Depth 43 mm

Mounting type DIN rail mounting
Assembly instructions alignable: horizontal 5 mm, vertical 50 mm
Mounting position horizontal DIN rail NS 35, EN 60715

Color aluminium
Housing material Metal
Type of housing Aluminum (AlMg3)
Hood version Galvanized sheet steel, free from chrome (VI)
Housing material Steel sheet, zinc-plated

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g tv = 90 min.

Rail applications EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)

UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Noise immunity EN 61000-6-2:2005
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 20 V/m
Frequency range 1 GHz ... 3 GHz
Test field strength 10 V/m
Frequency range 2 GHz ... 3 GHz
Test field strength 3 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 3 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 4 - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Item number 2320238
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key *****
Product Key CMUQ43
Catalog Page Page 275 (C-4-2017)
GTIN 4046356554190
Weight per Piece (including packing) 807.5 g
Weight per Piece (excluding packing) 600 g
Customs tariff number 85371091
Country of origin CN


ECLASS

ECLASS-9.0 27040705
ECLASS-10.0.1 27040705
ECLASS-11.0 27040705

ETIM

ETIM 8.0 EC000382

UNSPSC

UNSPSC 21.0 39121000

cUL Recognized

Approval ID: FILE E 211944

UL Recognized

Approval ID: FILE E 211944

EAC

Approval ID: EAC-Zulassung

DNV GL

Approval ID: TAA0000265

LR

Approval ID: 17/20032

UL Recognized

Approval ID: FILE E 211944

BV

Approval ID: 41516/B0 BV

EAC

Approval ID: EAC-Zulassung

UL Listed

Approval ID: FILE E 123528

cUL Recognized

Approval ID: FILE E 211944

cUL Listed

Approval ID: FILE E 123528

ABS

Approval ID: 22-2244289-PDA

cUL Listed

Approval ID: FILE E 123528

UL Listed

Approval ID: FILE E 123528

ABS

Approval ID: 22-2244289-PDA

BV

Approval ID: 41516/B0 BV

DNV GL

Approval ID: TAA0000265

LR

Approval ID: 17/20032

EAC

Approval ID: RU S-DE.BL08.W.00764

EAC

Approval ID: RU S-DE.BL08.W.00764

EAC

Approval ID: RU-DE.B.00184/20

EAC

Approval ID: RU-DE.B.00184/20

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

cUL Listed

Approval ID: FILE E 199827

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Easy handling thanks to automatic battery detection, tool-free battery replacement during operation, and communication via the IFS interface
Optimum use of the buffer time and preventive monitoring of the energy storage
Rapid battery charging
Comprehensive signaling and parameterization
Fast tripping of standard circuit breakers with SFB (selective fuse breaking) technology
Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently