Redundancy module - STEP-DIODE/5-24DC/2X5/1X10
2868606

Redundancy module, 5 ... 24 V DC, 2x 5 A, 1x 10 A


Product Details


A safe redundant system is the result of the parallel connection of two power supply units which are decoupled from one another. To further increase system availability, STEP DIODE provides the solution: decoupling with diode.



DC operation
Nominal input voltage range 5 V DC ... 24 V DC
Input voltage range 4.5 V DC ... 30 V DC
Voltage type of supply voltage DC
Reverse polarity protection < yes60 V
Transient surge protection Transil diode
Voltage drop, input/output 0.5 V

Efficiency > 97 %
> 97 %
Nominal output voltage 24 V DC
Output voltage UIn -
Setting range of the output voltage (USet) 5 V DC ... 24 V DC
Nominal output current (IN) 10 A (Increasing power)
5 A (Redundancy)
Derating 55 °C ... 70 °C (2.5%/K)
Power loss nominal load max. 2.5 W (IOUT = 5 A)
Connection in series No
Derating 60 °C ... 70 °C (2.5%/K)

Input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 6.5 mm
Screw thread M3
Tightening torque, min 0.6 Nm
Tightening torque max 0.8 Nm
Output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 6.5 mm
Screw thread M3
Tightening torque, min 0.6 Nm
Tightening torque max 0.8 Nm

Insulation voltage input, output / housing 500 V DC

Product type Redundancy module
MTBF (IEC 61709, SN 29500) > 25822000 h (40 °C)
Insulation characteristics
Protection class III
Degree of pollution 2

Width 18 mm
Height 90 mm
Depth 61 mm
Horizontal pitch 1 Div.
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 30 mm / 30 mm

Mounting type DIN rail: 35 mm
Assembly instructions alignable: 0 mm horizontally, 30 mm vertically
Mounting position horizontal DIN rail NS 35, EN 60715

Housing material Metal
Housing material Plastic

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard - Electrical safety IEC 62368-1 (SELV)

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Noise immunity EN 61000-6-2:2005
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 4 kV (Test Level 2)
Discharge in air 8 kV (Test Level 3)
Comments Criterion B
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 3 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Comments Criterion B
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 2 kV (Test Level 3 - asymmetrical)
1 kV (Test Level 2 - symmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
1 kV (Test Level 2 - symmetrical)
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 150 kHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Voltage dips
Standards/regulations EN 61000-4-11
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Item number 2868606
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C14
Product Key CMRS43
Catalog Page Page 309 (C-4-2019)
GTIN 4046356583923
Weight per Piece (including packing) 75.167 g
Weight per Piece (excluding packing) 73.2 g
Customs tariff number 85049090
Country of origin VN


ECLASS

ECLASS-9.0 27371010
ECLASS-10.0.1 27371010
ECLASS-11.0 27371010

ETIM

ETIM 8.0 EC000683

UNSPSC

UNSPSC 21.0 32151500

cUL Recognized

Approval ID: FILE E 214596

UL Recognized

Approval ID: FILE E 214596

EAC

Approval ID: EAC-Zulassung

EAC

Approval ID: RU S-DE.BL08.W.00764

UL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 123528

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Flexible mounting by simply snapping onto the DIN rail
Save energy
Rugged design
Permanent monitoring of redundancy
Consistent redundancy up to the load