PV-SET 2ST/1000DC/2MPP-SPD-SC
   - 
  Surge protection device set
    
      2801317
      
      
    
  
      Lightning and surge arrester in IP65 housing for protecting the DC side of an inverter with two MPP trackers up to 1000 V DC, connection via SUNCLIX plug/socket, plug-in varistors with thermal disconnect device between L+, L-, and ground/PE.
Product details
| IEC test classification | PV T1 | 
| PV T2 | |
| Type | Installation housing | 
| Surge protection fault message | optical | 
| Set comprises | 1774674 PV-CF-S 2,5-6 (+) | 
| 1774687 PV-CM-S 2,5-6 (-) | |
| Insulation characteristics | |
| Protection class | II | 
| Overvoltage category | III | 
| Pollution degree | 2 | 
| Nominal current IN | 25 A DC (per MPP) | 
| Indicator/remote signaling | |
| Switching function | Changeover contact, 1-pos. | 
| Maximum operating voltage Umax. AC | 250 V AC | 
| Maximum operating voltage Umax DC | 30 V DC | 
| Max. operating current Imax | 1.5 A AC (250 V AC) | 
| 1.5 A DC (30 V DC) | |
| Connection method | MC 1,5/3 | 
| Screw thread | M2 | 
| Tightening torque, min | 0.25 Nm | 
| Tightening torque | 2 lbf-in. ... 4 lbf-in. | 
| Stripping length | 7 mm | 
| Conductor cross-section flexible min. | 0.14 mm² | 
| Conductor cross-section flexible max. | 1.5 mm² | 
| Conductor cross-section, rigid min. | 0.14 mm² | 
| Conductor cross-section, rigid max. | 1.5 mm² | 
| Conductor cross-section AWG | 30 ... 14 (UL) | 
| Width | 200 mm | 
| Height | 200 mm | 
| Depth | 122 mm | 
| Horizontal pitch | 9 Div. | 
| Flammability rating according to UL 94 | V2 (Gehäuse / Deckel) | 
| V0 (Steckverbinder) | |
| Cover material | Polycarbonate, transparent | 
| Housing material | Polycarbonate, glass-fiber-reinforced | 
| Connector material | PA | 
| Direction of action | (L+)-PE & (L-)-PE & (L+)-(L-) | 
| Rated load current IL | 80 A DC | 
| Protective conductor current IPE | ≤ 25 µA | 
| ≤ 350 µA | |
| Standby power consumption PC | ≤ 25 mVA | 
| Nominal discharge current In (8/20) µs | 15 kA | 
| Maximum discharge current Imax (8/20) µs | 40 kA | 
| Total discharge current ITotal (8/20) µs | 40 kA | 
| Total discharge current ITotal (10/350) µs | 5 kA | 
| Voltage protection level Up (L+) - (L-) | ≤ 3.5 kV | 
| Voltage protection level Up (L+/L-) - PE | ≤ 3.5 kV | 
| Response time tA | ≤ 25 ns | 
| Response time tA (L+) - (L-) | ≤ 25 ns | 
| Response time tA (L+/L-) - PE | ≤ 25 ns | 
| Max. backup fuse with branch wiring | not required | 
| Protective circuit DC voltage side (DC) | |
| Rated surge voltage resistance Uimp | 6 kV | 
| Short-circuit current ISCSTC | 25 A DC (per MPP) | 
| Open-circuit voltage UOCSTC | 830 V DC (Solar generator) | 
| Maximum discharge current Imax (8/20) µs | 40 kA | 
| Response time tA | ≤ 25 ns | 
| Response time tA (L+) - (L-) | ≤ 25 ns | 
| Response time tA (L+/L-) - PE | ≤ 25 ns | 
| Impulse discharge current (10/350) µs, peak value limp | 5 kA | 
| Recommended backup fuse maximum | not required | 
| Total discharge current ITotal (8/20) µs | 40 kA | 
| Total discharge current ITotal (10/350) µs | 5 kA | 
| Max. backup fuse with branch wiring | not required | 
| Nominal discharge current In (8/20) µs | 15 kA | 
| Rated load current IL | 80 A DC | 
| Protective conductor current IPE | ≤ 25 µA | 
| ≤ 350 µA | |
| Voltage protection level Up (L+) - (L-) | ≤ 3.5 kV | 
| Voltage protection level Up (L+/L-) - PE | ≤ 3.5 kV | 
| Standby power consumption PC | ≤ 25 mVA | 
| Ambient conditions | |
| Degree of protection | IP65 | 
| IP65 | |
| Impact strength | IK08 | 
| Ambient conditions | A, B | 
| Ambient temperature (operation) | -30 °C ... 55 °C | 
| Air clearances and creepage distances | |
| Standards/regulations | EN 50539-11 | 
| Standards/specifications | IEC 61439-2 | 
| Note | 2011 | 
| Standards/specifications | EN 61439-2 | 
| Note | 2011 | 
| Standards/specifications | EN 50539-11 | 
| Note | Surge protection | 
| Mounting type | Surface/Panel mounting | 
| Item number | 2801317 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Product key | DTHAAA | 
| GTIN | 4046356761697 | 
| Weight per piece (including packing) | 2,095 g | 
| Weight per piece (excluding packing) | 2,095 g | 
| Country of origin | DE | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 