You can integrate Axioline Smart Elements into systems with the Smart Element interface. This Smart Element detects the signals of resistive temperature sensors.
    
  
  AXL SE RTD2 PT100 EA
   - 
  Temperature module
    
      1398500
      
      
    
  
      Axioline Smart Elements, Temperature recording module, Detection of Pt 100 temperature sensors, Analog RTD inputs: 2 (Pt 100), connection technology: 4-conductor, degree of protection: IP20
      This product needs further products for operation.
      Mandatory accessories
    
  Product details
| Dimensional drawing |  | 
| Width | 14.9 mm | 
| Height | 62.2 mm | 
| Depth | 62 mm | 
| Smart Element interface | |
| Number of interfaces | 1 | 
| Connection method | Card edge connector | 
| Transmission speed | See system in which you use the Smart Element. | 
| Start time until ready to operate | < 1 s | 
| Module | |
| ID code (hex) | none | 
| Process data channel | 64 bit | 
| Input address area | 4 Byte | 
| Output address area | 4 Byte | 
| Analog | |
| Input name | Analog RTD inputs | 
| Description of the input | Inputs for resistive temperature sensors | 
| Number of inputs | 2 (Pt 100) | 
| Connection method | Push-in connection | 
| Connection technology | 4-conductor | 
| Note regarding the connection technology | shielded, 2-, 3-, and 4-conductor sensors can be connected | 
| A/D converter resolution | 16 bit | 
| Sensor types (RTD) that can be used | Pt 100 (IEC 60751/EN 60751) | 
| Data formats | Standardized representation | 
| Measured value representation | 16 bits (15 bits + sign bit) | 
| Nominal value of the current sources | 1 mA (120 ms during the sampling phase of the respective channel) | 
| Process data update | typ. 1 ms | 
| Protective circuit | Overload protection; max. ±30 V DC, 1 min. | 
| Transient protection | |
| Product type | I/O component | 
| Product family | Axioline Smart Elements | 
| Application | Detection of Pt 100 temperature sensors | 
| Type | modular | 
| Mounting position | See the system in which the Smart Element is used. | 
| Insulation characteristics | |
| Overvoltage category | II (IEC 61010-2-201/EN IEC 61010-2-201) | 
| Pollution degree | 2 (IEC 61010-2-201/EN 61010-2-201) | 
| Potentials: Communications power supply of the Smart Elements (USE) | |
| Supply voltage | using card edge connectors | 
| Potentials: I/O supply (UP) | |
| Supply voltage | 24 V DC (using card edge connectors) | 
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | 
| Current draw | max. 12 mA | 
| typ. 8 mA | |
| Current consumption | min. 5 mA (without connected peripherals) | 
| Power consumption | max. 290 mW | 
| min. 120 mW | |
| Protective circuit | Surge protection; See the system in which the Smart Element is used. | 
| Reverse polarity protection; Polarity protection diode | |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: Communications supply / 24 V supply (I/O) | 500 V AC, 50 Hz, 1 min | 
| Test voltage: Logic supply/analog inputs and outputs | 500 V AC, 50 Hz, 1 min | 
| Test voltage: Communications supply / functional ground | 500 V AC, 50 Hz, 1 min | 
| Test voltage: 24 V supply (I/O) / analog inputs and outputs | 2.5 kV | 
| Test voltage: 24 V supply (I/O) / functional ground | 2.5 kV | 
| Test voltage: Analog inputs and outputs/functional ground | 2.5 kV | 
| Connection technology | |
| Connection name | I/O | 
| Note on the connection method | Please observe the information provided on conductor cross-sections in the “Axioline Smart Elements” user manual. | 
| Conductor connection | |
| Connection method | Push-in connection | 
| Conductor cross-section rigid | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section flexible | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 24 ... 16 | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| Stripping length | 8 mm | 
| I/O | |
| Connection method | Push-in connection | 
| Note on the connection method | Please observe the information provided on conductor cross-sections in the “Axioline Smart Elements” user manual. | 
| Conductor cross-section, rigid | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section, flexible | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 24 ... 16 | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| Stripping length | 8 mm | 
| Ambient conditions | |
| Ambient temperature (operation) | -40 °C ... 70 °C | 
| Degree of protection | IP20 | 
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | 
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) | 
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | 
| Mounting type | Plug-in mounting (Smart Element slot) | 
| Mounting position | See the system in which the Smart Element is used. | 
| Item number | 1398500 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | ##### | 
| Product key | DRMBAC | 
| GTIN | 4063151930417 | 
| Weight per piece (including packing) | 33.9 g | 
| Weight per piece (excluding packing) | 31.4 g | 
| Customs tariff number | 85389099 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27242601 | 
| ECLASS-15.0 | 27242601 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
Compatible products
- 
    
      SZS 0,4X2,5 VDE - Screwdriver 1205037
- 
    
      CRIMPFOX 6 - Crimping pliers 1212034
- 
    
      CRIMPFOX DUO 10 - Crimping pliers 1031721
- 
    
      CRIMPFOX 10T-F - Crimping pliers 1134913
- 
    
      MM-TML (EX4,2)R C1 TR/BK - Label 0803979
- 
    
      SK 5,0 WH:REEL - Marker strip 0805221
- 
    
      UM6M-TM (5X12) - Marker for terminal blocks 0830928
- 
    
      UCT6M-TM 5 - Marker for terminal blocks 0830756
Your advantages
2 analog input channels for the connection of resistance temperature detectors (Pt 100)
        Connection of sensors in 4-conductor technology
        2- and 3-conductor sensors can also be connected
        Data format: standardized representation
        Resolution: 16 bits
        Wire-break detection
        Substitute value behavior can be parameterized for each input
        Ambient temperature -40 °C ... 70 °C
        Satisfies environmental and EMC conditions in accordance with IEC 61850-3
        Device rating plate stored
        PHOENIX CONTACT Middle East FZ LLC
        
        1201N-1206N, Dubai Science Park Towers - North, P.O. Box 345002, Dubai, United Arab Emirates