PTCB BE PT 6
-
Base element
1567576
Base element, mounting type: DIN rail: TH 35 - 7.5 mm, rated current: 31 A
This product needs further products for operation.
Mandatory accessories
Product details
General | |
Note | The base element does not contain any electronic circuits. |
Product type | Base element |
Product family | CB BE |
Mechanical service life | 25 insertion cycles |
Insulation characteristics | |
Overvoltage category | II (250 V AC / IEC 60934) |
III (UL 1077, UL 1059) | |
III (80 V DC / IEC 60934) | |
Pollution degree | 2 (250 V AC / IEC 60934) |
3 (UL 1077, UL 1059) |
General | |
Rated voltage | 240 V AC (IEC 60934) |
277 V AC (UL 1077) | |
277 V AC (UL 1059) | |
56 V DC (IEC 60934) | |
56 V DC (UL 1077) | |
56 V DC (UL 1059) | |
Rated insulation voltage Ui | 250 V AC (IEC 60934) |
80 V DC (IEC 60934) | |
277 V AC (UL 1077) | |
277 V AC (UL 1059) | |
Rated current IN | 31 A (UL 1059, without device circuit breaker) |
16 A (Main contacts 1-2, UL 1077 and IEC 60934) | |
1 A (Auxiliary contacts 3-4, without device circuit breaker) | |
Rated surge voltage | 2.5 kV (IEC 60934, reinforced insulation between load and auxiliary circuit) |
Insulation resistance Riso | > 100 MΩ (500 V DC) |
Dielectric strength | 3000 V AC (between load circuit 1-2 and auxiliary circuit 3-4) |
1554 V AC (between open load contacts 1-2, auxiliary contacts 3-4) | |
Indicator/remote signaling | |
Connection name | Connection 3 / 4 |
Connection 1 / 2 | |
Connection method | Push-in connection |
Stripping length | 12 mm |
Conductor cross-section flexible | 0.5 mm² ... 10 mm² |
Conductor cross-section rigid | 0.5 mm² ... 10 mm² |
1 mm² ... 10 mm² (direct plug-in) | |
Conductor cross-section AWG | 20 ... 8 |
Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.5 mm² ... 6 mm² |
1 mm² ... 6 mm² (direct plug-in) | |
Conductor cross-section flexible, with ferrule without plastic sleeve | 0.5 mm² ... 6 mm² |
1 mm² ... 6 mm² (direct plug-in) | |
Connection 3 / 4 | |
Connection method | Push-in connection |
Stripping length | 8 mm |
Conductor cross-section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross-section rigid | 0.14 mm² ... 1.5 mm² |
Conductor cross-section AWG | 26 ... 16 |
Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.14 mm² ... 1.5 mm² |
Conductor cross-section flexible, with ferrule without plastic sleeve | 0.14 mm² ... 1.5 mm² |
Dimensional drawing |
|
Width | 8.2 mm |
Height | 122.9 mm |
Depth | 54.1 mm |
Complete module width | 8.2 mm |
Complete module height | 122.9 mm |
Complete module depth | 85.2 mm |
Color | gray (RAL 7042) |
Material | PA |
Flammability rating according to UL 94 | V-0 |
Insulating material group | I |
Mechanical data | |
Open side panel | No |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -30 °C ... 60 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (250 V AC / IEC 60934) |
Humidity test | 96 h, 95 % RH, 40 °C |
Shock (operation) | 30g (IEC 60068-2-27, Test Ea) |
Vibration (operation) | 10 Hz ... 150 Hz, 20 cycles (IEC 60068-2-6, Test Fc) |
10 Hz ... 75 Hz (Amplitude ±0.35 mm; in accordance with IEC 60068-2-6, Test Fc) | |
75 Hz ... 150 Hz (8g) |
UL approval | |
Identification | UL Recognized UL 1059 |
UL Recognized UL 1077 | |
CSA, Canada | |
Identification | CSA C22.2 No. 235-04 |
Standards/specifications | IEC 60934 |
Note | 2019 |
Standards/specifications | UL 1077 |
Note | Additional protective devices for use in electrical equipment |
Standards/specifications | UL 1059 |
Note | Terminal blocks |
Standards/specifications | CSA C22.2 No. 235-04 |
Note | 2017 |
Standards/specifications | IEC 60068-2-6 |
Note | Environmental influences – Vibrations (sinusoidal) |
Standards/specifications | EN 60068-2-27 |
Note | Environmental influences – Shocks |
Standards/specifications | EN 60068-2-78 |
Note | Environmental influences – Moisture and heat, constant |
Standards/specifications | DIN EN 50274 |
Note | Touch protection and back-of-hand safety |
Standards/specifications | IEC 60529 |
Note | 2019 |
Mounting type | DIN rail: TH 35 - 7.5 mm |
Item number | 1567576 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Product key | CLA193 |
GTIN | 4067923054332 |
Weight per piece (excluding packing) | 28.01 g |
ECLASS
ECLASS-13.0 | 27140401 |
ECLASS-15.0 | 27140401 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Not applicable (No electrical and electronic equipment (EEE), cannot be used in EEE) |
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Compatible products
-
PTCB TM1 0.5A F2 NO P - Thermal-magnetic device circuit breaker 1509512
-
PTCB TM1 1A F2 NO P - Thermal-magnetic device circuit breaker 1509519
-
PTCB TM1 2A F2 NO P - Thermal-magnetic device circuit breaker 1509520
-
PTCB TM1 3A F2 NO P - Thermal-magnetic device circuit breaker 1509522
-
PTCB TM1 4A F2 NO P - Thermal-magnetic device circuit breaker 1509524
-
PTCB TM1 5A F2 NO P - Thermal-magnetic device circuit breaker 1509528
-
PTCB TM1 6A F2 NO P - Thermal-magnetic device circuit breaker 1509529
-
PTCB TM1 8A F2 NO P - Thermal-magnetic device circuit breaker 1509532
-
PTCB TM1 10A F2 NO P - Thermal-magnetic device circuit breaker 1509535
-
PTCB TM1 12A F2 NO P - Thermal-magnetic device circuit breaker 1509537
-
PTCB TM1 16A F2 NO P - Thermal-magnetic device circuit breaker 1567580
-
PTCB TM1 0.5A M1 NO P - Thermal-magnetic device circuit breaker 1575555
-
PTCB TM1 1A M1 NO P - Thermal-magnetic device circuit breaker 1575557
-
PTCB TM1 2A M1 NO P - Thermal-magnetic device circuit breaker 1575558
-
PTCB TM1 3A M1 NO P - Thermal-magnetic device circuit breaker 1575565
-
PTCB TM1 4A M1 NO P - Thermal-magnetic device circuit breaker 1575566
-
PTCB TM1 5A M1 NO P - Thermal-magnetic device circuit breaker 1575571
-
PTCB TM1 6A M1 NO P - Thermal-magnetic device circuit breaker 1575572
-
PTCB TM1 8A M1 NO P - Thermal-magnetic device circuit breaker 1575573
-
PTCB TM1 10A M1 NO P - Thermal-magnetic device circuit breaker 1575580
-
PTCB TM1 12A M1 NO P - Thermal-magnetic device circuit breaker 1575581
-
PTCB TM1 16A M1 NO P - Thermal-magnetic device circuit breaker 1575586
Note: Applying some accessories below might limit this product.
-
FBS 2-6 - Plug-in bridge 3030336
-
FBS 3-8 - Plug-in bridge 3030297
-
FBS 2-8 - Plug-in bridge 3030284
-
FBS 2-3,5 GY - Plug-in bridge 3213153
-
FBS 2-6 BU - Plug-in bridge 3036932
-
RB ST 6-(2,5/4) - Reducing bridge 3030860
-
PT 6 - Feed-through terminal block 3211813
-
PT 6-TWIN - Feed-through terminal block 3211929
-
PT 6-QUATTRO - Feed-through terminal block 3212934
-
PT 4 - Feed-through terminal block 3211757
-
PT 4-TWIN - Feed-through terminal block 3211771
-
PT 4-QUATTRO - Feed-through terminal block 3211797
-
PT 2,5 - Feed-through terminal block 3209510
-
PT 2,5-TWIN - Feed-through terminal block 3209549
-
PT 2,5-QUATTRO - Feed-through terminal block 3209578
-
CP-PT 1,5 - Coding profile 1985564
-
LPO 6 - Pick-off plug 3270526
-
LPO 6/E - Pick-off plug 3270525
-
ATP-PTCB BE - Partition plate 1683464
-
UCT-TM 8 - Marker for terminal blocks 0828740
-
ZB 8:UNBEDRUCKT - Zack marker strip 1052002
-
ZBF 8:UNBEDRUCKT - Zack Marker strip, flat 0808781
Your advantages
More space in the control cabinet: protection and signaling in an overall width of just 8 mm
Simple application setup due to bridging option to CLIPLINE complete terminal block system
Transparency regarding utilization and status with practical current monitoring and remote signaling
Easy handling from commissioning right through to maintenance due to clear functionality and switching state at all times
PHOENIX CONTACT s.r.o.
Námestie Mateja Korvína 1, 811 07 Bratislava. Zapísaná v Obchodnom registri Okresného súdu Bratislava III, vložka číslo 48994/B.