MACX MCR-EX-SL-TC-I
   - 
  Temperature measuring transducer
    
      2865942
      
      
    
  
      Ex i temperature transducer: converts signals from thermocouples installed in the Ex area and mV sources and transmits a 0/4 - 20 mA signal to a load in the safe area. Freely programmable, custom-configured. Replacement item: 1052458 MACX MCR-EX-TC-I-C.
      Free download available.
      Downloads
    
  Product details
| Product type | Temperature transmitter | 
| Application | Temperature | 
| No. of channels | 1 | 
| Insulation characteristics | |
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Alignment span | ± 5 % | 
| Alignment zero | ± 5 % | 
| Typical cold point errors | ± 1 K | 
| Step response (0–99%) | 700 ms | 
| ≤ 1100 ms | |
| Temperature coefficient, typical | 0.01 %/K | 
| Electrical isolation Input/output/power supply | |
| Rated insulation voltage | 300 Vrms | 
| Test voltage | 2.5 kV AC (50 Hz, 60 s) | 
| Insulation | Safe isolation in accordance with IEC/EN 61010-1 | 
| Electrical isolation Input/output | |
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) | 
| Electrical isolation Input/power supply | |
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) | 
| Supply | |
| Nominal supply voltage | 24 V DC | 
| Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) | 
| Max. current consumption | < 40 mA (24 V DC) | 
| Power dissipation | < 1 W | 
| Signal | |
| Number of inputs | 1 | 
| Input signal | Temperature | 
| Voltage | |
| Voltage input signal | -20 mV ... 70 mV | 
| Measurement | |
| Description of the input | intrinsically safe | 
| Sensor types that can be used (TC) | E, J, K, N as per IEC / EN 60584, L as per DIN 43760 | 
| Temperature measuring range | -250 °C ... 1372 °C (Range depending on the sensor type) | 
| Temperature measuring range: Thermoelement Typ J | -210 °C ... 1200 °C | 
| Temperature measuring range: Thermoelement Typ K | -200 °C ... 1372 °C | 
| Temperature measuring range: Thermoelement Typ N | -200 °C ... 1300 °C | 
| Temperature measuring range: Thermoelement Typ E | -226 °C ... 1000 °C | 
| Temperature measuring range: Thermoelement Typ L | -200 °C ... 900 °C | 
| Linear mV signal range | -20 mV ... 70 mV | 
| Temperature measuring range | Min. 50 K for thermocouples, 3 mV for mV sources | 
| Switching: | |
| Configurable/programmable | no | 
| Signal | |
| Output description | Current output | 
| Number of outputs | 1 | 
| Configurable/programmable | Yes | 
| Current output signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA | |
| Load/output load current output | ≤ 500 Ω | 
| Output ripple (current) | < 50 µAPP | 
| < 10 µArms | |
| Behavior in the event of a sensor error | As per NE 43 or can be freely defined | 
| Connection method | Screw connection | 
| Stripping length | 7 mm | 
| Screw thread | M3 | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 14 | 
| Tightening torque | 0.5 Nm ... 0.6 Nm | 
| Safety data | |
| Max. output voltage Uo | 6 V | 
| Max. output current Io | 4.7 mA | 
| Max. output power Po | 7 mW | 
| Safety-related maximum voltage Um | 253 V AC | 
| 125 V DC | |
| IIC: Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 1.5 µF, 10 mH / 1.9 µF, 1 mH / 2.7 µF | 
| IIB: Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 7 µF, 10 mH / 9.4 µF, 1 mH / 15 µF | 
| Status display | LED supply voltage, PWR (green) | 
| Red LED, flashing 2.8 Hz (cable error, sensor error on input or output, ERR) | |
| Red LED, flashing 1.2 Hz (simulation mode, ERR) | |
| Red LED, permanently on (module error, ERR) | 
| Dimensional drawing |  | 
| Width | 12.5 mm | 
| Height | 106.4 mm | 
| Depth | 114.5 mm | 
| Color | gray (RAL 7042) | 
| Flammability rating according to UL 94 (Housing) | V0 (Housing) | 
| Housing material | PA 6.6-FR | 
| Safety data | |
| Safety Integrity Level (SIL) | 2 | 
| Ambient conditions | |
| Degree of protection | IP20 (not assessed by UL) | 
| Ambient temperature (operation) | -20 °C ... 60 °C (Any mounting position) | 
| Ambient temperature (storage/transport) | -40 °C ... 80 °C | 
| Altitude | ≤ 2000 m | 
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | 
| CE | |
| Certificate | CE-compliant | 
| Note | and EN 61326 | 
| ATEX | |
| Identification |  II (1) G [Ex ia Ga] IIC/IIB | 
|  II (1) D [Ex ia Da] IIIC | |
|  II 3(1) G Ex nA ic [ia Ga] IIC T4 Gc X | |
| Certificate | IBExU 09 ATEX 1030 | 
| IECEx | |
| Identification | [Ex ia Ga] IIC/IIB | 
| [Ex ia Da] IIIC | |
| Ex nA ic [ia Ga] IIC T4 Gc | |
| Certificate | IECEx IBE 09.0002X | 
| UL, USA/Canada | |
| Identification | Class I Div 2; IS for Class I, II, III Div 1 | 
| Certificate | , C.D.-No 83104549 | 
| KC-s | |
| Identification | [Ex ia] IIC/IIB | 
| Certificate | 17-KA4BO-0415X | 
| Shipbuilding approval | |
| Identification | C, EMC1 | 
| Certificate | GL 86 644-10HH | 
| EAC Ex | |
| Identification |  [Ex ia Ga] IIC | 
|  [Ex ia Da] IIIC | |
| Certificate | RU C-DE.AB72.B.00093/19 | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Mounting type | DIN rail mounting | 
| Item number | 2865942 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Note | Made to order (non-returnable) | 
| Sales key | 0971* | 
| Product key | CK3121 | 
| Weight per piece (including packing) | 177 g | 
| Weight per piece (excluding packing) | 128.3 g | 
| Customs tariff number | 85437090 | 
| Country of origin | DE | 
UNSPSC
| UNSPSC 21.0 | 41112105 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 
Compatible products
- 
    
      
- 
    
      MACX MCR-PTB - Power and error message module 2865625
- 
    
      MACX MCR-PTB-SP - Power and error message module 2924184
- 
    
      IFS-USB-PROG-ADAPTER - Programming adapter 2811271
- 
    
      TC-D37SUB-ADIO16-EX-P-UNI - Module carrier 2924854
- 
    
      TC-D37SUB-AIO16-EX-PS-UNI - Module carrier 2902932
- 
    
      UC-EMLP (11X9) - Plastic label 0819291
- 
    
      UC-EMLP (11X9) CUS - Plastic label 0824547
- 
    
      UC-EMLP (11X9) YE - Plastic label 0822602
- 
    
      UC-EMLP (11X9) YE CUS - Plastic label 0824548
- 
    
      UC-EMLP (11X9) SR - Plastic label 0828094
- 
    
      UC-EMLP (11X9) SR CUS - Plastic label 0828098
- 
    
      US-EMLP (11X9) - Plastic label 0828789
- 
    
      US-EMLP (11X9) YE - Plastic label 0828871
- 
    
      US-EMLP (11X9) SR - Plastic label 0828872
- 
    
      LS-EMLP (11X9) WH - Device marker 0831678
- 
    
      LS-EMLP (11X9) YE - Device marker 0831732
- 
    
      LS-EMLP (11X9) SR - Device marker 0831705
- 
    
      MPS-MT - Test plug 0201744
- 
    
      MPS-IH BK - Insulating sleeve 0201731
- 
    
      MPS-IH GY - Insulating sleeve 0201728
- 
    
      MPS-IH GN - Insulating sleeve 0201702
- 
    
      MPS-IH YE - Insulating sleeve 0201692
- 
    
      MPS-IH BU - Insulating sleeve 0201689
- 
    
      MPS-IH RD - Insulating sleeve 0201676
- 
    
      MPS-IH WH - Insulating sleeve 0201663
Your advantages
Input for thermocouples and mV sources
        Power supply possible via DIN rail connector
        Programming during operation with Ex measuring circuit connected and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
        Installation in zone 2, protection type "n" (EN 60079-15) permitted
        3-way electrical isolation
        Status indicator for supply voltage, cable, sensor, and module errors
        Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output range
        Output: 0 mA ... 20 mA or 4 mA ... 20 mA