Signal conditioner - MINI MCR-2-I0-U-PT
2902001

3-way signal conditioner with plug-in connection technology for the electrical isolation of analog signals. Input signal: 0 ... 20 mA, output signal: 0 ... 10 V, push-in connection technology


Product Details


Standard signal 3-way signal conditioner with plug-in connection technology for the electrical isolation, conversion, amplification, and filtering of standard signals. The measuring transducer supports fault monitoring and NFC communication.



Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

No. of channels 1
Type Signal conditioner
Insulation characteristics
Overvoltage category II
Degree of pollution 2

No. of channels 1
Rated insulation voltage 300 V (effective)
Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Limit frequency (3 dB) approx. 30 Hz
Test voltage, input/output/supply 3 kV (50 Hz, 1 min.)
Protective circuit Transient protection
Step response (10-90%) approx. 10 ms
Maximum temperature coefficient 0.01 %/K
Temperature coefficient, typical 0.01 %/K
Maximum transmission error 0.1 % (of final value)
Supply
Nominal supply voltage 24 V DC
Supply voltage range 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Item No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption 25 mA (24 V DC)
54 mA (12 V DC)
Power consumption ≤ 200 mW (at 9.6 V DC)

Signal
Number of inputs 1
Configurable/programmable no
Current input signal 0 mA ... 20 mA
Input resistance current input approx. 63 Ω (+0.7 V for test diode)

Signal: Voltage
Output name Voltage output
Number of outputs 1
Configurable/programmable no
Voltage output signal 0 V ... 10 V
Max. voltage output signal 11 V
Short-circuit current < 15 mA
Load/output load voltage output ≥ 10 kΩ
Ripple < 20 mVPP (at 10 kΩ)

Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.2 mm² ... 2.5 mm² (with ferrule)
0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 12 (flexible)

Operating voltage display Green LED

Width 6.2 mm
Height 109.81 mm
Depth 119.2 mm

Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
Housing material PBT

Ambient conditions
Degree of protection IP20 (not assessed by UL)
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

CE
Certificate CE-compliant
ATEX
Identification  II 3 G Ex ec IIC T4 Gc
Certificate BVS 19 ATEX E 047 X
UKCA Ex (UKEX)
Identification  II 3 G Ex ec IIC T4 Gc
Certificate PxCIF21UKEX2902000X
IECEx
Identification Ex ec IIC T4 Gc
Certificate IECEx BVS 19.0041X
CCC / China-Ex
Identification Ex nA IIC T4 Gc
UL, USA / Canada
Identification UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Shipbuilding approval
Certificate DNV GL TAA00002UA
DNV GL data
Temperature B
Humidity B
Vibration A
EMC A
Enclosure Required protection according to the Rules shall be provided upon installation on board

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Comments Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Fast transients (burst)
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Surge current load (surge)
Standards/regulations EN 61000-4-5
Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6

Electrical isolation Reinforced insulation in accordance with IEC 61010-1
GB Standard
Standards/regulations GB 3836.1
GB 3836.8

Mounting type DIN rail mounting
Assembly instructions The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
Mounting position any

Order Key 2902001
Packing unit 1 pc
Minimum order quantity 1 pc
Note Made to Order (non-returnable)
Sales Key *****
Product Key CK1411
Catalog Page Page 76 (C-5-2019)
GTIN 4046356651837
Weight per Piece (including packing) 111.5 GRM
Weight per Piece (excluding packing) 97.0 GRM
Customs tariff number 85437090
Country of origin DE


ECLASS

ECLASS-9.0 27210120
ECLASS-10.0.1 27210120
ECLASS-11.0 27210120

ETIM

ETIM 6.0 EC002653

UNSPSC

UNSPSC 19.0 39121008
UNSPSC 20.0 39121008
UNSPSC 21.0 39121008

DNV GL

UL Listed

CCC

cUL Listed

EAC Ex

IECEx

cUL Listed

UL Listed

ATEX

ATEX


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”