PV-SET 4ST/1000DC/13A
-
Surge protection device set
2800600
Surge protection in IP65 housing for the DC side of an inverter for four-string photovoltaic systems up to 1000 V DC.
Product details
IEC test classification | PV T2 |
Type | Installation housing |
Distance between live and grounded parts | 8 mm |
Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics | |
Protection class | II |
Overvoltage category | III |
Pollution degree | 2 |
Nominal current IN | 4x 8 A DC |
Indicator/remote signaling | |
Switching function | Changeover contact, 1-pos. |
Operating voltage | 5 V AC ... 250 V AC |
30 V DC | |
Operating current | 5 mA AC ... 1.5 A |
1.5 A DC |
Connection method | MC 1,5/3 |
Screw thread | M2 |
Tightening torque, min | 0.25 Nm |
Tightening torque | 4 lbf-in. |
Stripping length | 7 mm |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 1.5 mm² |
Conductor cross section, rigid min. | 0.14 mm² |
Conductor cross section, rigid max. | 1.5 mm² |
Width | 200 mm |
Height | 200 mm |
Depth | 122 mm |
Horizontal pitch | 9 Div. |
Flammability rating according to UL 94 | V2 (Gehäuse / Deckel) |
Cover material | Polycarbonate, transparent |
Housing material | Polycarbonate, glass-fiber-reinforced |
Connector material | PA |
Direction of action | (L+)-PE & (L-)-PE & (L+)-(L-) |
Residual current IPE | ≤ 20 µA DC |
≤ 250 µA AC | |
Standby power consumption PC | ≤ 25 mVA |
Nominal discharge current In (8/20) µs (L+) - (L-) | 15 kA |
Nominal discharge current In (8/20) µs (L-) - PE | 15 kA |
Maximum discharge current Imax (8/20) µs (L+) - (L-) | 40 kA |
Total discharge current ITotal (8/20) µs | 40 kA |
Voltage protection level Up (L+) - (L-) | ≤ 3.7 kV |
Voltage protection level Up (L+) - PE | ≤ 3.7 kV |
Voltage protection level Up (L-) - PE | ≤ 3.7 kV |
Residual voltage Ures (L+) - (L-) | ≤ 3.7 kV (at In) |
≤ 3.1 kV (at 5 kA) | |
≤ 3.5 kV (at 10 kA) | |
≤ 4 kV (at 20 kA) | |
≤ 4.6 kV (at 30 kA) | |
≤ 5 kV (at 40 kA) | |
Residual voltage Ures (L+) - PE | ≤ 3.7 kV (at In) |
≤ 3.1 kV (at 5 kA) | |
≤ 3.5 kV (at 10 kA) | |
≤ 4 kV (at 20 kA) | |
≤ 4.6 kV (at 30 kA) | |
≤ 5 kV (at 40 kA) | |
Residual voltage Ures (L-) - PE | ≤ 3.7 kV (at In) |
≤ 3.1 kV (at 5 kA) | |
≤ 3.5 kV (at 10 kA) | |
≤ 4 kV (at 20 kA) | |
≤ 4.6 kV (at 30 kA) | |
≤ 5 kV (at 40 kA) | |
Response time tA (L+) - (L-) | ≤ 25 ns |
Response time tA (L+) - PE | ≤ 25 ns |
Response time tA (L-) - PE | ≤ 25 ns |
Protective circuit DC voltage side (DC) | |
Rated surge voltage resistance Uimp | 6 kV |
Short-circuit current ISCSTC | 4x 8 A DC |
Open circuit voltage UOCSTC | 830 V DC (Solar generator) |
Maximum discharge current Imax (8/20) µs (L+) - (L-) | 40 kA |
Maximum discharge current Imax (8/20) µs (L-) - PE | 40 kA |
Maximum discharge current Imax (8/20) µs (L+) - PE | 40 kA |
Response time tA (L+) - (L-) | ≤ 25 ns |
Response time tA (L+) - PE | ≤ 25 ns |
Response time tA (L-) - PE | ≤ 25 ns |
Recommended backup fuse maximum | not required |
Total discharge current ITotal (8/20) µs | 40 kA |
Insulation resistance Riso | > 5 GΩ (at 500 V DC) |
Nominal discharge current In (8/20) µs (L+) - (L-) | 15 kA |
Nominal discharge current In (8/20) µs (L+) - PE | 15 kA |
Nominal discharge current In (8/20) µs (L-) - PE | 15 kA |
Residual voltage Ures (L+) - (L-) | ≤ 3.7 kV (at In) |
≤ 3.1 kV (at 5 kA) | |
≤ 3.5 kV (at 10 kA) | |
≤ 4 kV (at 20 kA) | |
≤ 4.6 kV (at 30 kA) | |
≤ 5 kV (at 40 kA) | |
Residual voltage Ures (L+) - PE | ≤ 3.7 kV (at In) |
≤ 3.1 kV (at 5 kA) | |
≤ 3.5 kV (at 10 kA) | |
≤ 4 kV (at 20 kA) | |
≤ 4.6 kV (at 30 kA) | |
≤ 5 kV (at 40 kA) | |
Residual voltage Ures (L-) - PE | ≤ 3.7 kV (at In) |
≤ 3.1 kV (at 5 kA) | |
≤ 3.5 kV (at 10 kA) | |
≤ 4 kV (at 20 kA) | |
≤ 4.6 kV (at 30 kA) | |
≤ 5 kV (at 40 kA) | |
Residual current IPE | ≤ 20 µA DC |
≤ 250 µA AC | |
Voltage protection level Up (L+) - (L-) | ≤ 3.7 kV |
Voltage protection level Up (L+) - PE | ≤ 3.7 kV |
Voltage protection level Up (L-) - PE | ≤ 3.7 kV |
Standby power consumption PC | ≤ 25 mVA |
Ambient conditions | |
Degree of protection | IP65 |
IP65 | |
Ambient conditions | A, B |
Ambient temperature (operation) | -30 °C ... 50 °C |
Altitude | max. 2000 m |
Air clearances and creepage distances | |
Standards/regulations | EN 50539-11 |
Standards/specifications | IEC 61439-2 |
Note | 2011 |
Standards/specifications | EN 61439-2 |
Note | 2011 |
Standards/specifications | EN 50539-11 |
Note | Surge protection |
Mounting type | Surface/Panel mounting |
Mounting position | Connections downward |
Item number | 2800600 |
Packing unit | 1 pc |
Minimum order quantity | 5 pc |
Note | Made to order (non-returnable) |
Product key | CL1341 |
GTIN | 4046356607148 |
Weight per piece (including packing) | 1.657,2 g |
Weight per piece (excluding packing) | 1.657,2 g |
Country of origin | DE |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 6(c) |
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |