      High-current terminal block, nom. voltage: 1000 V, nominal current: 150 A, number of connections: 2, number of positions: 1, connection method: Screw connection, Rated cross section: 50 mm2, cross section: 16 mm2 - 70 mm2, mounting type: direct screw connection, color: blue
Product details
| General | |
| Note | For a reliable contact of multi stranded conductors it is recommended to untwist multi stranded conductors. | 
| Product type | High current terminal block | 
| Number of positions | 1 | 
| Number of connections | 2 | 
| Number of rows | 1 | 
| Potentials | 1 | 
| Insulation characteristics | |
| Overvoltage category | III | 
| Degree of pollution | 3 | 
| Rated surge voltage | 8 kV | 
| Maximum power dissipation for nominal condition | 4.73 W | 
| Number of connections per level | 2 | 
| Nominal cross section | 50 mm² | 
| Connection method | Screw connection | 
| Screw thread | M6 | 
| Tightening torque | 6 ... 8 Nm | 
| Stripping length | 24 mm | 
| Internal cylindrical gage | B10 | 
| Connection in acc. with standard | IEC 60947-7-1 | 
| Conductor cross-section rigid | 16 mm² ... 70 mm² | 
| Cross section AWG | 4 ... 2/0 (converted acc. to IEC) | 
| Conductor cross-section flexible | 25 mm² ... 70 mm² | 
| Conductor cross-section, flexible [AWG] | 2 ... 2/0 (converted acc. to IEC) | 
| Conductor cross-section flexible (ferrule without plastic sleeve) | 16 mm² ... 50 mm² | 
| Flexible conductor cross-section (ferrule with plastic sleeve) | 16 mm² ... 50 mm² | 
| 2 conductors with same cross section, solid | 10 mm² ... 16 mm² | 
| 2 conductors with same cross section, flexible | 10 mm² ... 16 mm² | 
| 2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 10 mm² ... 16 mm² | 
| Nominal current | 150 A | 
| Maximum load current | 150 A (with 50 mm² conductor cross-section) | 
| Nominal voltage | 1000 V | 
| Note | Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area. | 
| Nominal cross section | 50 mm² | 
| Rated data (ATEX/IECEx) | |
| Identification |  II 2 GD Ex eb IIC Gb | 
| Operating temperature range | -60 °C ... 110 °C | 
| Ex-certified accessories | 1205082 SZS 1,2X8,0 VDE | 
| List of bridges | Fixed bridge / FBI 2-20-EX / 0201113 | 
| Fixed bridge / FBI 3-20-EX / 0201812 | |
| Bridge data | 130.5 A (50 mm²) | 
| Ex temperature increase | 40 K (146.5 A / 50 mm²) | 
| for bridging with bridge | 690 V | 
| Rated insulation voltage | 630 V | 
| output | (Permanent) | 
| Ex level General | |
| Rated voltage | 690 V | 
| Rated current | 133 A | 
| Maximum load current | 133 A | 
| Contact resistance | 0.1 mΩ | 
| Ex connection data General | |
| Torque range | 6 Nm ... 8 Nm | 
| Nominal cross section | 50 mm² | 
| Rated cross section AWG | 1/0 | 
| Connection capacity rigid | 16 mm² ... 50 mm² | 
| Connection capacity AWG | 6 ... 1/0 | 
| Connection capacity flexible | 25 mm² ... 50 mm² | 
| Connection capacity AWG | 4 ... 1/0 | 
| 2 conductors with same cross section, solid | 10 mm² ... 16 mm² | 
| 2 conductors with the same cross-section AWG rigid | 8 ... 6 | 
| 2 conductors with same cross section, stranded | 10 mm² ... 16 mm² | 
| 2 conductors with the same cross-section AWG flexible | 8 ... 6 | 
| Dimensional drawing |  | 
| Width | 20 mm | 
| Height | 75.5 mm | 
| Depth | 76 mm | 
| Hole diameter | 5.5 mm | 
| Color | blue (RAL 5015) | 
| Flammability rating according to UL 94 | V0 | 
| Insulating material group | I | 
| Insulating material | PA | 
| Static insulating material application in cold | -60 °C | 
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C | 
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 | 
| Surface flammability NFPA 130 (ASTM E 162) | passed | 
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed | 
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed | 
| Surge voltage test | |
| Test voltage setpoint | 9.8 kV | 
| Result | Test passed | 
| Temperature-rise test | |
| Requirement temperature-rise test | Increase in temperature ≤ 45 K | 
| Result | Test passed | 
| Short-time withstand current 50 mm² | 6 kA | 
| Result | Test passed | 
| Power-frequency withstand voltage | |
| Test voltage setpoint | 2.2 kV | 
| Result | Test passed | 
| Mechanical data | |
| Open side panel | No | 
| Mechanical strength | |
| Result | Test passed | 
| Attachment on the carrier | |
| DIN rail/fixing support | NS 32/NS 35 | 
| Test force setpoint | 10 N | 
| Result | Test passed | 
| Test for conductor damage and slackening | |
| Rotation speed | 10 (+/- 2) rpm | 
| Revolutions | 135 | 
| Conductor cross-section/weight | 16 mm² / 2.9 kg | 
| 50 mm² / 9.5 kg | |
| 70 mm²/10.4 kg | |
| Result | Test passed | 
| Needle-flame test | |
| Time of exposure | 30 s | 
| Result | Test passed | 
| Oscillation/broadband noise | |
| Specification | DIN EN 50155 (VDE 0115-200):2018-05 | 
| Spectrum | Long life test category 2, bogie-mounted | 
| Frequency | f1 = 5 Hz to f2 = 250 Hz | 
| ASD level | 6.12 (m/s²)²/Hz | 
| Acceleration | 3.12g | 
| Test duration per axis | 5 h | 
| Test directions | X-, Y- and Z-axis | 
| Result | Test passed | 
| Shocks | |
| Specification | DIN EN 50155 (VDE 0115-200):2022-06 | 
| Pulse shape | Half-sine | 
| Acceleration | 5g | 
| Shock duration | 30 ms | 
| Number of shocks per direction | 3 | 
| Test directions | X-, Y- and Z-axis (pos. and neg.) | 
| Result | Test passed | 
| Ambient conditions | |
| Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) | 
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) | 
| Ambient temperature (assembly) | -5 °C ... 70 °C | 
| Ambient temperature (actuation) | -5 °C ... 70 °C | 
| Permissible humidity (operation) | 20 % ... 90 % | 
| Permissible humidity (storage/transport) | 30 % ... 70 % | 
| Connection in acc. with standard | IEC 60947-7-1 | 
| Mounting type | direct screw connection | 
| Item number | 3247062 | 
| Packing unit | 10 pc | 
| Minimum order quantity | 10 pc | 
| Sales key | 02 | 
| Product key | BE1311 | 
| GTIN | 4046356733304 | 
| Weight per piece (including packing) | 131.05 g | 
| Weight per piece (excluding packing) | 131.05 g | 
| Customs tariff number | 85369010 | 
| Country of origin | IN | 
ECLASS
| ECLASS-13.0 | 27250101 | 
| ECLASS-15.0 | 27250101 | 
ETIM
| ETIM 9.0 | EC000897 | 
UNSPSC
| UNSPSC 21.0 | 39121400 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes (No exemptions) | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-E No hazardous substances above the limits | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 
Compatible products
            Note: Applying some accessories below might limit this product.
          
          
        - 
    
      FBI 2-20 - Fixed bridge 0201346
- 
    
      FBI 3-20 - Fixed bridge 0201317
- 
    
      FBI 2-20-EX - Fixed bridge 0201113
- 
    
      FBI 3-20-EX - Fixed bridge 0201812
- 
    
      AGK 10-UKH 50 - Pick-off terminal block 3001763
- 
    
      ZB 10:UNBEDRUCKT - Zack marker strip 1053001
- 
    
      ZB 10 CUS - Zack marker strip 0824941
- 
    
      ZB10,LGS:FORTL.ZAHLEN - Zack marker strip 1053014
- 
    
      ZB10,QR:FORTL.ZAHLEN - Zack marker strip 1053027
- 
    
      ZB10,LGS:L1-N,PE - Marker for terminal blocks 1053412
- 
    
      ZB10,LGS:U-N - Marker for terminal blocks 1053438
- 
    
      UC-TM 10 - Marker for terminal blocks 0818069
- 
    
      UC-TM 10 CUS - Marker for terminal blocks 0824605
- 
    
      UCT-TM 10 - Marker for terminal blocks 0829142
- 
    
      UCT-TM 10 CUS - Marker for terminal blocks 0829623
- 
    
      TMT 10 R - Marker for terminal blocks 0816210
- 
    
      TMT 10 R CUS - Marker for terminal blocks 0824500
- 
    
      SZS 1,2X8,0 VDE - Screwdriver 1205082
- 
    
      X-PEN 0,35 - Marker pen 0811228
- 
    
      WS-2K - Warning label 1004513
- 
    
      WS-4K - Warning label 1004584
- 
    
      UKH 50 EP - Insertion profile 3009228
Your advantages
Reliable cable connection is ensured by three-point centering of the conductor in the prismatic sleeve base
 
        Screw locking by means of spring-loaded elements in the clamping part
        Low contact resistance of the contact surface due to ribbing
        PHOENIX CONTACT S.A de C.V.
        
        Lago Alberto No. 319 - Piso 9, Colonia Granada, Alcaldía Miguel Hidalgo, México, Ciudad de México, C.P. 11520