      Axioline E, EtherCAT®, M12 connector, IO-Link ports Class A: 4, connection method: M12 connector, connection technology: 3-conductor, IO-Link ports Class B: 4, connection method: M12 connector, connection technology: 3-conductor, Digital inputs at pin 2 for class A ports: 4, 24 V DC, connection technology: 3-conductor, Plastic housing, degree of protection: IP65/IP67
      Free download available.
      Downloads
    
  Product details
| Dimensional drawing |  | 
| Width | 60 mm | 
| Height | 185 mm | 
| Depth | 30.5 mm | 
| Drill hole spacing | 198.5 mm | 
| Note on dimensions | The height is 212 mm including fixing clips. | 
| Note on application | |
| Note on application | Only for industrial use | 
| Housing material | Pocan® | 
| Color | anthracite | 
| EtherCAT® | |
| No. of channels | 2 | 
| Connection method | M12 connector | 
| Note on the connection method | D-coded | 
| Number of positions | 4 | 
| Transmission speed | 100 Mbps (with auto negotiation) | 
| EtherCAT® | |
| Equipment type | EtherCAT® subdevice | 
| System-specific protocols | Mailbox protocols CANopen® over EtherCAT® | 
| Mailbox protocols File access over EtherCAT® | |
| Specification | ETG.1000 V1.02 | 
| Digital: | |
| Input name | Digital inputs at pin 2 for class A ports | 
| Description of the input | IEC 61131-2 type 1 | 
| Number of inputs | 4 | 
| Connection method | M12 connector, X01 ... X04 have double occupancy | 
| Connection technology | 3-conductor | 
| Input voltage range "0" signal | -0.3 V DC ... 5 V DC | 
| Input voltage range "1" signal | 15 V DC ... 30 V DC | 
| Nominal input voltage UIN | 24 V DC | 
| Nominal input current at UIN | typ. 3 mA | 
| Sensor current per channel | max. 200 mA (from L+/L-) | 
| Total sensor current | max. 1.6 A (from L+/L-) | 
| Input frequency | 0.5 kHz | 
| Input filter time | < 1000 µs | 
| Protective circuit | Overload protection, short-circuit protection of sensor supply | 
| Digital | |
| Description of the input | IO-Link ports in digital input (DI) mode | 
| Number of inputs | max. 8 (EN 61131-2 type 1) | 
| Connection method | M12 connector, X01 ... X04 have double occupancy | 
| Connection technology | 3-conductor | 
| Nominal input voltage UIN | 24 V DC | 
| Input voltage range "0" signal | -0.3 V DC ... 5 V DC | 
| Input voltage range "1" signal | 15 V DC ... 30 V DC | 
| Nominal input current | typ. 3 mA | 
| Sensor current per channel | max. 200 mA (from L+/L-) | 
| Total sensor current | max. 1.6 A (from L+/L-) | 
| Input filter time | < 1000 µs | 
| Input frequency | 0.5 kHz | 
| Protective circuit | Overload protection; yes | 
| Short-circuit protection for the sensor supply; yes | |
| IO-Link | |
| Number of ports | 4 | 
| Connection method | M12 connector | 
| Connection technology | 3-conductor | 
| Port type | Class A | 
| Cycle Time | min. 2 ms (MasterCycleTime: PDInput* + PDOutput* + OnReqData* < = 17 Bytes, COM3; * see "IO-Link Interface and System Specification V1.1.2") | 
| IO-Link | |
| Number of ports | 4 | 
| Connection method | M12 connector | 
| Connection technology | 3-conductor | 
| Port type | Class B | 
| Cycle Time | min. 2 ms (MasterCycleTime: PDInput* + PDOutput* + OnReqData* < = 17 Bytes, COM3; * see "IO-Link Interface and System Specification V1.1.2") | 
| Digital | |
| Output description | IO-Link ports in digital output (DO) mode | 
| Connection method | M12 connector, X01 ... X04 have double occupancy | 
| Connection technology | 3-conductor | 
| Number of outputs | max. 8 | 
| Nominal output voltage | 24 V DC | 
| Maximum output current per channel | 150 mA | 
| Maximum output current per module | 1.2 A | 
| Nominal load, ohmic | 3.6 W (160 Ω, at nominal load) | 
| Nominal load, inductive | 3.6 VA (0.8 H, 160 Ω, at nominal load) | 
| Signal delay | max. 150 µs (when switched on) | 
| max. 200 µs (when switched off) | |
| Switching rate | 1 per second, maximum (at nominal inductive load) | 
| 5500 per second, maximum (at nominal ohmic load) | |
| Limitation of the voltage induced on circuit interruption | -15 V DC | 
| Output voltage when switched off | max. 1 V | 
| Output current when switched off | max. 300 µA | 
| Protective circuit | Overload protection; yes | 
| Short-circuit protection; yes | |
| Behavior with overload | Shutdown with automatic restart | 
| Product type | I/O component | 
| Product family | Axioline E | 
| Type | Stand-alone | 
| Special properties | Plastic housing | 
| Potentials | |
| Voltage supply US | 24 V DC | 
| Power supply at US | max. 4 A | 
| Current consumption from US | typ. 8 mA | 
| max. 1.2 A | |
| Supply: IO-Link | |
| Nominal voltage for I/O supply | 24 V DC | 
| Nominal current for every IO-Link port | max. 150 mA (at C/Q (pin 4), maximum of 1.6 A over all 8 IO-Link C/Q and L+ cables) | 
| max. 200 mA (at L+/L- (pin 1 and pin 3), during startup, up to 1.6 A for short periods) | |
| max. 2 A (at UA (IO-Link B ports, pin 2 and pin 5)) | |
| Permissible cable length | < 20 m (to the sensor) | 
| Protective circuit | Overload protection; yes | 
| Supply: Module electronics and sensors | |
| Designation | Supply of module electronics and sensors (US) | 
| Connection method | M12 connector, T-coded | 
| Number of positions | 4 | 
| Supply voltage | 24 V DC | 
| Supply voltage range | 19.5 V DC ... 31.2 V DC (including all tolerances, including ripple) | 
| Current consumption | typ. 180 mA ±15 % (at 24 V DC) | 
| max. 12 A | |
| Supply: Actuators | |
| Designation | Supply of actuators (UA) | 
| Connection method | M12 connector, T-coded | 
| Number of positions | 4 | 
| Supply voltage | 24 V DC | 
| Supply voltage range | 18 V DC ... 31.2 V DC (including all tolerances, including ripple) | 
| Current consumption | typ. 28 mA ±15 % (at 24 V DC) | 
| max. 12 A | |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 1) | 500 V AC, 50 Hz, 1 min | 
| Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 2) | 500 V AC, 50 Hz, 1 min | 
| Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/FE | 500 V AC, 50 Hz, 1 min | 
| Test voltage: Bus connection (Ethernet 1)/FE | 500 V AC, 50 Hz, 1 min | 
| Test voltage: Bus connection (Ethernet 2)/FE | 500 V AC, 50 Hz, 1 min | 
| Test voltage: Bus connection (Ethernet 1)/bus connection (Ethernet 2) | 500 V AC, 50 Hz, 1 min | 
| Test voltage: 24 V supply (actuator supply)/24 V supply (communications power and sensor supply, IO-Link ports) | 500 V AC, 50 Hz, 1 min | 
| Test voltage: 24 V supply (actuator supply)/bus connection (Ethernet 1) | 500 V AC, 50 Hz, 1 min | 
| Test voltage: 24 V supply (actuator supply)/bus connection (Ethernet 2) | 500 V AC, 50 Hz, 1 min | 
| Test voltage: 24 V supply (actuator supply)/FE | 500 V AC, 50 Hz, 1 min | 
| Connection method | M12 connector | 
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 60 °C | 
| Degree of protection | IP65/IP67 | 
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Ambient temperature (storage/transport) | -25 °C ... 85 °C | 
| Permissible humidity (operation) | 5 % ... 95 % | 
| Permissible humidity (storage/transport) | 5 % ... 95 % | 
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | 
| Mounting type | Screw mounting | 
| Item number | 2701524 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | 02 | 
| Product key | DRI7DE | 
| GTIN | 4046356763745 | 
| Weight per piece (including packing) | 555.5 g | 
| Weight per piece (excluding packing) | 551.4 g | 
| Customs tariff number | 85176200 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27242604 | 
| ECLASS-15.0 | 27242604 | 
ETIM
| ETIM 9.0 | EC001599 | 
UNSPSC
| UNSPSC 21.0 | 32151600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 6(c) | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-25 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
Compatible products
- 
    
      PROT-M12 - Screw plug 1680539
- 
    
      SACC-M12MSD-4CON-PG 9-SH - Data connector 1521261
- 
    
      UCT-EM (7X10) - Snap-in markers 0830765
- 
    
      SAC-4P- 1,5-PUR/M12FRT SH - Power cable 1424116
- 
    
      SAC-4P-M12MST/ 1,5-PUR SH - Power cable 1424120
- 
    
      NBC-M12MSD-PN/.../... - Network cable 1408640
- 
    
      NBC-M12MSD-M12FSD-PN/.../... - Network cable 1408617
- 
    
      NBC-M12MSD-M12MSD-PN/.../... - Network cable 1408634
- 
    
      NBC-M12MSD-R4AC-PN/.../... - Network cable 1408639
- 
    
      SAC-4P-M12MST/ 1,0-PUR - Power cable 1408812
- 
    
      SAC-4P-M12MST/ 2,0-PUR - Power cable 1408813
- 
    
      SAC-4P-M12MST/ 5,0-PUR - Power cable 1408814
- 
    
      SAC-4P-M12MST/10,0-PUR - Power cable 1408815
- 
    
      SAC-4P-M12MRT/ 1,0-PUR - Power cable 1408816
- 
    
      SAC-4P-M12MRT/ 2,0-PUR - Power cable 1408819
- 
    
      SAC-4P-M12MRT/ 5,0-PUR - Power cable 1408820
- 
    
      SAC-4P-M12MRT/10,0-PUR - Power cable 1408822
- 
    
      SAC-4P- 1,0-PUR/M12FST - Power cable 1408823
- 
    
      SAC-4P- 2,0-PUR/M12FST - Power cable 1408824
- 
    
      SAC-4P- 5,0-PUR/M12FST - Power cable 1408825
- 
    
      SAC-4P-10,0-PUR/M12FST - Power cable 1408826
- 
    
      SAC-4P- 1,0-PUR/M12FRT - Power cable 1408827
- 
    
      SAC-4P- 2,0-PUR/M12FRT - Power cable 1408828
- 
    
      SAC-4P- 5,0-PUR/M12FRT - Power cable 1408829
- 
    
      SAC-4P-10,0-PUR/M12FRT - Power cable 1408830
- 
    
      SAC-4P-M12MST/ 0,3-PUR/M12FST - Power cable 1408806
- 
    
      SAC-4P-M12MST/ 0,6-PUR/M12FST - Power cable 1408807
- 
    
      SAC-4P-M12MST/ 1,0-PUR/M12FST - Power cable 1408808
- 
    
      SAC-4P-M12MST/ 2,0-PUR/M12FST - Power cable 1408809
- 
    
      SAC-4P-M12MST/ 5,0-PUR/M12FST - Power cable 1408810
- 
    
      SAC-4P-M12MST/10,0-PUR/M12FST - Power cable 1408811
- 
    
      SAC-3P-M12MS/.../... - Sensor/actuator cable 1696662
- 
    
      SAC-3P-M12MR/.../... - Sensor/actuator cable 1696675
- 
    
      SAC-3P-M12MS-M12FS/.../... - Sensor/actuator cable 1696756
- 
    
      SAC-3P-M12MR-M12FS/.../... - Sensor/actuator cable 1513428
- 
    
      SAC-3P-M12MR-M12FR/.../... - Sensor/actuator cable 1513318
- 
    
      SAC-4P-M12MR-M12FS/.../... - Sensor/actuator cable 1697030
- 
    
      SAC-4P-M12MR-M12FR/.../... - Sensor/actuator cable 1697043
- 
    
      SAC-5P-M12MS/.../... - Sensor/actuator cable 1697098
- 
    
      SAC-5P-M12MR/.../... - Sensor/actuator cable 1697108
- 
    
      SAC-5P-M12MR-M12FS/.../... - Sensor/actuator cable 1508734
- 
    
      SAC-5P-M12MR-M12FR/.../... - Sensor/actuator cable 1529506
- 
    
      SAC-3P-Y/2XM 8FS SCO - Y distributor 1523984
- 
    
      SAC-3P-Y/2XFS PE SCO - Y distributor 1523971
- 
    
      SAC-3P-Y/2XFS B PE SCO - Y distributor 1523968
- 
    
      PROT-M12 SH - Screw plug 1503302
- 
    
      NF PD IOL R - Inductive coupler 1736165
- 
    
      NF PD IOL B - Inductive coupler 1736167
Your advantages
Connection to EtherCAT® network using M12 connectors (D-coded)
        Transmission speed of 100 Mbps
        Connection of four IO-Link devices with additional digital input
        Connection of four IO-Link actuators with additional power supply
        Connection of IO-Link ports using M12connectors (A-coded, 5-pos.)
        IO-Link specification V1.1.2
        Diagnostic and status indicators
        Short-circuit and overload protection of the sensor supply
        IP65/IP67 degree of protection
        Frequently searched
PHOENIX CONTACT S.A de C.V.
        
        Lago Alberto No. 319 - Piso 9, Colonia Granada, Alcaldía Miguel Hidalgo, México, Ciudad de México, C.P. 11520