Monitoring relay - EMD-SL-LL-230
2885906

Monitoring relay for level monitoring of conductive fluids, minimum monitoring, maximum monitoring, 230 V AC supply voltage, 2 changeover contacts


Product Details


Increasingly higher demands are being placed on safety and system availability - across all sectors. Processes are becoming more and more complex, not only in mechanical engineering and the chemical industry, but also in plant and automation technology. Demands on power engineering are also increasing constantly.
Error-free and therefore cost-effective operation can only be achieved through continuous monitoring of important network and system parameters. Electronic monitoring relays in the EMD series are available for a wide range of monitoring tasks to avoid the consequences of errors or to keep them within limits.
The operating states are indicated using colored LEDs, errors that may occur can be sent to a control system via a floating contact or can shut down a part of the system. Some device versions are equipped with startup and response delays in order to briefly tolerate measured values outside the set monitoring range.



Product type Level monitoring relay
Operating mode 100% operating factor
Mechanical service life approx. 2x 107 cycles
Insulation characteristics
Overvoltage category III
Pollution degree 2
Insulation Basic insulation

Service life electrical 2x 105 cycles at ohmic load, 1000 VA
Mains type 1-phase
Rated insulation voltage 300 V
Supply
Supply voltage 230 V AC -15 % ... +15 % AC
Supply voltage range 195.5 V AC ... 264.5 V AC
Nominal power consumption 2 VA (1.5 W)

Input name Measuring input
Description of the input Conductive probe, type: SK1, SK2, SK3
Frequency range 48 Hz ... 63 kHz
Function Pump up (minimum monitoring)
Pump down (maximum monitoring)
Recovery time 500 ms
Max. probe voltage 16 V AC
Max. probe current 7 mA
Length of probe cable < 1000 m (Line capacity 100 nF/km; set value < 50%)
< 100 m (Line capacity 100 nF/km; set value 100%)
Switching Threshold 0.25 kΩ ... 100 kΩ (4 mS ... 1 μS)

Switching
Contact type 2 floating changeover contacts
Maximum switching voltage 250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max. 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse 5 A (fast-blow)

Connection method Screw connection
Stripping length 8 mm
Conductor cross section solid 0.5 mm² ... 2.5 mm²
Conductor cross section flexible 0.25 mm² ... 2.5 mm²
Conductor cross section AWG 20 ... 14

Width 22.5 mm
Height 90 mm
Depth 113 mm

Housing insulation material Polyamide PA, self-extinguishing

Ambient conditions
Degree of protection IP40 (Housing)
IP20 (Connection terminal blocks)
Ambient temperature (operation) -25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport) -25 °C ... 70 °C
Climatic class 3K3 (in acc. with EN 60721)
Permissible humidity (operation) 15 % ... 85 %

CE
Designation CE
Certificate CE-compliant
CE
Designation UL, USA / Canada
Identification UL/C-UL Listed UL 508

Low Voltage Directive Conformance with Low Voltage Directive
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-3
Noise immunity EN 61000-6-2

Standards/regulations EN 50178

Mounting type DIN rail mounting
Assembly instructions on standard DIN rail NS 35 in accordance with EN 60715
Mounting position any

Item number 2885906
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CK
Product Key CK4141
Catalog Page Page 255 (C-5-2019)
GTIN 4046356144148
Weight per Piece (including packing) 193 g
Weight per Piece (excluding packing) 193 g
Country of origin AT


ECLASS

ECLASS-9.0 27371813
ECLASS-10.0.1 27371813
ECLASS-11.0 27371813

ETIM

ETIM 8.0 EC001447

UNSPSC

UNSPSC 21.0 39121100

EAC

Approval ID: TR_TS_D_00573_c

EAC

Approval ID: RU*C-DE.*08.B.00010

UL Listed

Approval ID: FILE E 172140

cUL Listed

Approval ID: FILE E 172140

cULus Listed


China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Your advantages

Short-circuit and open-circuit monitoring
Test function with integrated test/reset button
Variable supply voltage range