Feed-through terminal block - UK 5 N
3004362

Feed-through terminal block, nom. voltage: 800 V, nominal current: 32 A, connection method: Screw connection, Rated cross section: 4 mm2, cross section: 0.2 mm2 - 6 mm2, mounting type: NS 35/7,5, NS 35/15, NS 32, color: gray


Product Details




Product type Feed-through terminal block
Number of connections 2
Number of rows 1
Potentials 1
Insulation characteristics
Overvoltage category III
Degree of pollution 3

Rated surge voltage 8 kV
Maximum power dissipation for nominal condition 1.02 W

Number of connections per level 2
Nominal cross section 4 mm²
Level 1 above 1 below 1
Screw thread M3
Tightening torque 0.6 ... 0.8 Nm
Stripping length 8 mm
Internal cylindrical gage A4
Conductor cross section solid 0.2 mm² ... 6 mm²
Cross section AWG 24 ... 10
Conductor cross section flexible 0.2 mm² ... 4 mm²
Conductor cross section, flexible [AWG] 24 ... 12
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) 0.25 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve) 0.25 mm² ... 2.5 mm²
Cross-section with insertion bridge, rigid 4 mm²
Cross-section with insertion bridge, flexible 4 mm²
2 conductors with same cross section, solid 0.2 mm² ... 1.5 mm²
2 conductors with same cross section, flexible 0.2 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve 0.25 mm² ... 1.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve 0.5 mm² ... 2.5 mm²
Nominal current 32 A
Maximum load current 41 A (with 6 mm² conductor cross section)
Nominal voltage 800 V
Nominal cross section 4 mm²

Rated data (ATEX/IECEx)
ATEX certificate KEMA 98 ATEX 1651 U
IEC Ex certificate IECEx  KEM 06.0034 U
Identification  II 2 GD  Ex eb IIC Gb
Operating temperature range -60 °C ... 110 °C
Ex-certified accessories 3003020 D-UK 4/10
3006027 D-UK 16
3003224 ATP-UK
1212587 SF-SL 0,6X3,5-100 S-VDE
1201442 E/UK
Bridge data 27.5 A / 4 mm²
28.5 A / 4 mm²
28 A / 4 mm²
28 A / 4 mm²
26 A / 4 mm²
Ex temperature increase 40 K (30 A / 4 mm²)
Rated voltage 690 V (NS 35)
for bridging with bridge 550 V (NS 32)
- At bridging between non-adjacent terminal blocks 176 V
Rated insulation voltage 630 V (NS 35)
500 V (NS 32)
Ex level General
Rated current 27 A
Maximum load current 35 A
Contact resistance 0.37 mΩ
Ex connection data General
Torque range 0.6 Nm ... 0.8 Nm
Nominal cross section 4 mm²
Rated cross section AWG 12
Connection capacity rigid 0.2 mm² ... 6 mm²
Connection capacity AWG 24 ... 10
Connection capacity flexible 0.2 mm² ... 4 mm²
Connection capacity AWG 24 ... 12
2 conductors with same cross section, solid 0.2 mm² ... 1.5 mm²
2 conductors with the same cross-section AWG rigid 24 ... 16
2 conductors with same cross section, stranded 0.2 mm² ... 1.5 mm²
2 conductors with the same cross-section AWG flexible 24 ... 16

Width 6.2 mm
End cover width 1.8 mm
Height NS 35/15 54.5 mm
Height NS 35/7,5 47 mm
Height 1.85 "
Height NS 32 52 mm
Length 42.5 mm

Color gray
Flammability rating according to UL 94 V0
Insulating material group I
Insulating material PA
Static insulating material application in cold -60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 130 °C
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Smoke gas toxicity NFPA 130 (SMP 800C) passed

Surge voltage test
Test voltage setpoint 8 kV
Result Test passed
Temperature-rise test
Requirement temperature-rise test Increase in temperature ≤ 45 K
Result Test passed
Short-time withstand current 4 mm² 0.48 kA
Short-time withstand current 6 mm² 0.72 kA
Result Test passed
Power-frequency withstand voltage
Test voltage setpoint 2 kV
Result Test passed

Mechanical data
Open side panel Yes

Mechanical strength
Result Test passed
Attachment on the carrier
DIN rail/fixing support NS 32/NS 35
Test force setpoint 1 N
Result Test passed
Test for conductor damage and slackening
Rotation speed 10 rpm
Revolutions 135
Conductor cross section/weight 0.2 mm² / 0.2 kg
4 mm² / 0.9 kg
6 mm² / 1.4 kg
Result Test passed

Needle-flame test
Time of exposure 30 s
Result Test passed
Oscillation/broadband noise
Specification DIN EN 50155 (VDE 0115-200):2018-05
Spectrum Service life test category 1, class B, body mounted
ASD level 1.857 (m/s²)²/Hz
Acceleration 0.8g
Test duration per axis 5 h
Test directions X-, Y- and Z-axis
Result Test passed
Shocks
Specification DIN EN 50155 (VDE 0115-200):2018-05
Pulse shape Half-sine
Acceleration 5g (10-150-10 Hz)
Shock duration 30 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Result Test passed
Ambient conditions
Ambient temperature (operation) -60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly) -5 °C ... 70 °C
Ambient temperature (actuation) -5 °C ... 70 °C
Permissible humidity (storage/transport) 30 % ... 70 %

Connection in acc. with standard IEC 60947-7-1

Mounting type NS 35/7,5
NS 35/15
NS 32

Item number 3004362
Packing unit 50 pc
Minimum order quantity 1 pc
Sales Key BE
Product Key BE1211
Catalog Page Page 459 (C-1-2019)
GTIN 4017918090760
Weight per Piece (including packing) 8.64 g
Weight per Piece (excluding packing) 8.522 g
Customs tariff number 85369010
Country of origin DE


ECLASS

ECLASS-9.0 27141120
ECLASS-10.0.1 27141120
ECLASS-11.0 27141120

ETIM

ETIM 8.0 EC000897

UNSPSC

UNSPSC 21.0 39121400

DNV

Approval ID: TAE00001CT
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

CSA

Approval ID: 13631
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
600 V 30 A 28 - 10

IECEE CB Scheme

Approval ID: NL-65062
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
800 V 32 A - 4

EAC

Approval ID: RU C-DE.A*30.B.01742

cULus Recognized

Approval ID: E60425
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
Use group F
800 V 30 A 30 - 10

KEMA-KEUR

Approval ID: 71-113414
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
800 V - 4

KR

Approval ID: HMB17372-EL001

NK

Approval ID: 09 ME 141
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

RS

Approval ID: 17.00013.272

ATEX

Approval ID: KEMA98ATEX1651U

cUL Recognized

Approval ID: E192998
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
600 V 30 A 30 - 10

EAC Ex

Approval ID: RU C-DE.HA91.B.00066

GL

Approval ID: 98876-96 HH
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
EEx e II part certificate 690 V 32.5 A - 4

IECEx

Approval ID: IECEx KEM 06.0034U

UL Recognized

Approval ID: E192998
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
600 V 30 A 30 - 10

CCC

Approval ID: 2020322313000623

NEPSI

Approval ID: GYJ20.1195U

DNV GL-EX

Approval ID: TAE00003K6
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
EEx e II part certificate 440 V 32 A - 2.5

cULus Recognized


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products



Your advantages

Universal foot which can be used on NS 35... and NS 32... DIN rails
The UK universal screw terminal block series has the typical features which are decisive for practical applications
Potential distribution via fixed bridges in the terminal center or insertion bridges in the clamping space