You can connect this Axioline E device to an IO-Link master via an IO-Link A port. You can use this device to acquire digital signals via IO-Link. Use within different networks is possible via the IO-Link master.
    
  
  AXL E IOL DI8 M12 3M
   - 
  Digital module
    
      1480996
      
      
    
  
      Axioline E, Digital input device, IO-Link ports Class A: 1, connection method: M12 connector, A-coded, connection technology: 3-conductor, Digital inputs: 8, 24 V DC, connection technology: 4-conductor, IO-Link, degree of protection: IP65/IP67/IP69
      Free download available.
      Downloads
    
  Product details
| Dimensional drawing |  | 
| Width | 30 mm | 
| Height | 184 mm | 
| Depth | 30.3 mm | 
| Note on application | |
| Note on application | Only for industrial use | 
| Housing material | Die-cast zinc | 
| Digital: | |
| Input name | Digital inputs | 
| Description of the input | EN 61131-2 types 1 and 3 | 
| Number of inputs | 8 | 
| Cable length | max. 30 m (to the sensor) | 
| Connection method | M12 connector, A-coded | 
| Note on the connection method | Push-pull fast connection according to IEC 61076-2-010 or screw connection according to IEC 61076-2-101 | 
| Connection technology | 4-conductor | 
| Input voltage range "0" signal | -3 V ... 5 V DC | 
| Input voltage range "1" signal | 11 V DC ... 30 V DC | 
| Nominal input voltage UIN | 24 V DC | 
| Nominal input current at UIN | typ. 2.5 mA | 
| Input filter time | 1 ms | 
| Protective circuit | Reverse polarity protection; yes | 
| Short-circuit protection; yes | |
| Overload protection; yes | |
| IO-Link | |
| Number of ports | 1 | 
| Connection method | M12 connector, A-coded | 
| Note on the connection method | Push-pull fast connection according to IEC 61076-2-010 or screw connection according to IEC 61076-2-101 | 
| Connection technology | 3-conductor | 
| Port type | Class A | 
| Specification | V1.1.3 | 
| Reverse polarity protection | yes | 
| Transmission speed | 230.4 kbps (COM3) | 
| Cycle Time | 1 ms | 
| Amount of process data | 2 Byte (Input data) | 
| 0 Byte (Output data) | |
| Product type | I/O component | 
| Product family | Axioline E | 
| Type | Stand-alone | 
| Special properties | IO-Link | 
| Insulation characteristics | |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) | 
| Supply: IO-Link | |
| Designation | IO-Link port supply (L+) | 
| Nominal voltage for I/O supply | 24 V DC (Provided via the IO-Link interface of the IO-Link master.) | 
| Supply voltage range | 18 V DC ... 30 V DC (including all tolerances, including ripple) | 
| Nominal current per device | typ. 30 mA | 
| Current consumption | max. 800 mA (device dependent; observe the current of the IO-Link master that is made available via L+) | 
| Protective circuit | Reverse polarity protection; yes | 
| Supply: Sensors | |
| Designation | Supply of the sensors (from L+) | 
| Current consumption | max. 800 mA (per port) | 
| max. 800 mA (device dependent; observe the current of the IO-Link master that is made available via L+) | |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: 24 V supply L+ (IO-Link)/functional ground | 500 V AC, 50 Hz, 1 min | 
| Connection method | M12 connector | 
| Tightening torque | 0.4 Nm | 
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 70 °C | 
| Degree of protection | IP65/IP67/IP69 | 
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Ambient temperature (storage/transport) | -25 °C ... 85 °C | 
| Permissible humidity (operation) | 5 % ... 95 % | 
| Permissible humidity (storage/transport) | 5 % ... 95 % | 
| Test (noxious gas) | |
| Test standard | IEC 60068-2-60:2015 Method 4 | 
| Temperature | 25 °C ±1 K | 
| Humidity (relative) | 75 % ±3 % | 
| Test duration | 14 Days | 
| Volume concentration H2S (Hydrogen sulfide) | 10 ppb ±5 ppb | 
| Volume concentration NO2 (Nitrogen dioxide) | 200 ppb ±20 ppb | 
| Volume concentration Cl2 (Chlorine) | 10 ppb ±5 ppb | 
| Volume concentration SO2 (Sulfur dioxide) | 200 ppb ±20 ppb | 
| Test (Salt spray) | |
| Test standard | DIN EN 60068-2-52 | 
| Number of cycles | 4 | 
| Test steps per cycle | 2 | 
| Test duration (Total) | 168 h | 
| Test step (Salt mist) | 2 h with 5 % ±0.5 % NaCl, pH value 6.5...7.2 for 35 °C ±2 K | 
| Test step (Humidity) | 166 h with 93 % ±3 % Humidity for 40 °C ±2 K | 
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | 
| Mounting type | Screw mounting | 
| Item number | 1480996 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | ***** | 
| Product key | DRI7MF | 
| GTIN | 4063151900403 | 
| Weight per piece (including packing) | 293.7 g | 
| Weight per piece (excluding packing) | 279 g | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27242604 | 
| ECLASS-15.0 | 27242604 | 
ETIM
| ETIM 9.0 | EC001599 | 
UNSPSC
| UNSPSC 21.0 | 32151600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
Compatible products
- 
    
      
- 
    
      US-EMLP-HA (20X9) - Plastic label 0830989
- 
    
      US-EML (20X8) - Label 0800458
- 
    
      PROT-M12 - Screw plug 1680539
- 
    
      PROT-M12 SH - Screw plug 1503302
- 
    
      SAC-3P-Y/2XM 8FS SCO - Y distributor 1523984
- 
    
      SAC-3P-Y/2XFS PE SCO - Y distributor 1523971
- 
    
      SAC-3P-Y/2XFS B PE SCO - Y distributor 1523968
- 
    
      SAC-5P-P12MS/ 1,5-PUR/P12FR - Sensor/actuator cable 1224223
- 
    
      SAC-5P-P12MS/ 1,5-PUR/P12FS - Sensor/actuator cable 1224208
- 
    
      SAC-5P-P12MR/ 1,5-PUR/P12FS - Sensor/actuator cable 1224229
- 
    
      SAC-5P-P12MS/ 1,5-PUR - Sensor/actuator cable 1393925
- 
    
      SAC-5P-P12MR/ 1,5-PUR - Sensor/actuator cable 1395742
- 
    
      SAC-5P-M12MS/1,5-PUR/M12FS - Sensor/actuator cable 1681606
- 
    
      SAC-5P-M12MS/1,5-PUR - Sensor/actuator cable 1669767
- 
    
      SAC-5P-M12MS/1,5-PUR/M12FR - Sensor/actuator cable 1681648
- 
    
      SAC-5P-M12MR/1,5-PUR - Sensor/actuator cable 1669796
- 
    
      SACC-P12MS-4PL-CM M - Connector 1438146
- 
    
      SACC-P12MS-5PL-CM M - Connector 1438156
- 
    
      SACC-P12MR-4PL-CM M - Connector 1438148
- 
    
      SACC-P12MR-5PL-CM M - Connector 1438158
- 
    
      SACC-M12MS-5PL M - Connector 1424649
- 
    
      SACC-M12MS-4PL M - Connector 1424657
- 
    
      SACC-P12FS-4PL-CM M - Connector 1438151
- 
    
      SACC-P12FR-4PL-CM M - Connector 1438155
- 
    
      SACC-P12FR-5PL-CM M - Connector 1438162
- 
    
      SACC-P12FS-5PL-CM M - Connector 1438159
- 
    
      SACC-M12FS-5PL M - Connector 1424652
- 
    
      SACC-M12FS-4PL M - Connector 1424655
- 
    
      SAC BIT M12-D15 - Tool 1208432
- 
    
      SACC BIT M12-D20 - Tool 1208445
- 
    
      TSD 04 SAC - Torque screwdriver 1208429
- 
    
      NF PD IOL R - Inductive coupler 1736165
- 
    
      NF PD IOL B - Inductive coupler 1736167
Your advantages
Connection to an IO-Link master with M12 connector (A-coded, 4-pos.)
        Type A port
        IO-Link specification V1.1.3
        Connection of up to 8 inputs with M12 connectors (A-coded, 5-pos.)
        Diagnostic and status indicators
        Single-channel diagnostics
        Short-circuit and overload protection of the sensor supply
        Device rating plate stored
        IP65/IP67/IP69 degree of protection
        Frequently searched