FLM DIO 16/16 M12/8-DIAG
-
Distributed I/O device
2736738
The local bus device has digital inputs and outputs. Functions: 16 digital inputs, 3 ms filter time, 16 digital outputs of 500 mA each, 500 kbaud/2 Mbaud selection, diagnostics strategy, short-circuit/overload protection, 8-pos. M12 fast connection technology.
Product details
Dimensional drawing |
|
Width | 70 mm |
Height | 178 mm |
Depth | 50 mm |
Drill hole spacing | 168 mm |
Fieldline local bus | |
Connection method | M12 connector, B-coded |
Designation connection point | Copper cable |
Number of positions | 5 |
Transmission speed | 500 kbps / 2 Mbps |
Module | |
ID code (dec.) | 223 |
ID code (hex) | DF |
Length code (hex) | 01 |
Process data channel | 16 bit |
Input address area | 2 Byte |
Output address area | 2 Byte |
Register length | 32 bit |
Required parameter data | 18 Byte |
Required configuration data | 5 Byte |
Digital: | |
Input name | Digital inputs |
Description of the input | IEC 61131-2 type 1 |
Number of inputs | 16 |
Connection method | M12 connector, 8-pos. |
Connection technology | 2-, 3-conductor |
Input voltage | 24 V DC |
Input voltage range "0" signal | -30 V DC ... 5 V DC |
Input voltage range "1" signal | 13 V DC ... 30 V DC |
Nominal input voltage UIN | 24 V DC |
Total sensor current | max. 500 mA (Maximum current per socket) |
Filter time | 3 ms |
Delay at signal change from 0 to 1 | 3 ms |
Delay at signal change from 1 to 0 | 3 ms |
Protective circuit | Short-circuit protection, overload protection of the sensor supply; Reverse polarity protection |
Digital: | |
Output name | Digital outputs |
Connection method | M12 connector, 8-pos. |
Connection technology | 2-conductor |
Number of outputs | 16 |
Protective circuit | Short-circuit protection, overload protection of the sensor supply; Polarity protection diode |
Maximum output current per channel | 500 mA |
Product type | I/O component |
Product family | Fieldline |
Type | modular |
No. of channels | 16 |
Potentials | |
Voltage supply UL | 24 V DC |
Power supply at UL | max. 4 A |
Current consumption from UL | max. 100 mA (At 2 Mbaud) |
typ. 80 mA (At 2 Mbaud) | |
max. 75 mA (At 500 kBaud) | |
typ. 60 mA (At 500 kBaud) | |
Voltage supply US | 24 V DC |
Power supply at US | max. 4 A |
Current consumption from US | typ. 20 mA (plus power supply for sensors) |
max. 1.2 A | |
max. 1.2 A | |
Voltage supply UA11 | 24 V DC |
Power supply at UA11 | max. 4 A |
Current consumption at UA11 | typ. 15 mA |
max. 4 A | |
Voltage supply UA12 | 24 V DC |
Power supply at UA12 | max. 4 A |
Current consumption at UA12 | typ. 15 mA |
max. 4 A | |
Supply: Module electronics | |
Connection method | M12 connector |
Designation | UL |
Supply voltage | 24 V DC |
Supply voltage range | 18 V DC ... 30 V DC (including ripple) |
Electrical isolation/isolation of the voltage ranges | |
Test voltage: To I/O | 500 V DC, 1 min |
Connection method | M12 connector |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 60 °C |
Degree of protection | IP65/IP67 |
Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (storage/transport) | 95 % |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | Panel mounting |
Item number | 2736738 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DRI |
Product key | DRI434 |
GTIN | 4046356042642 |
Weight per piece (including packing) | 458.4 g |
Weight per piece (excluding packing) | 400 g |
Customs tariff number | 85389099 |
Country of origin | DE |
ETIM
ETIM 8.0 | EC001599 |
UNSPSC
UNSPSC 21.0 | 32151600 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 6(c), 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
Compatible products
-
-
FLM MP 5 - Mounting panel 2736660
-
FLM MP 7 - Mounting panel 2736673
-
SAC-5P-MS/ 0,13-186/FS SCO - Sensor/actuator cable 1518481
-
SAC-5P-MSB/0,13-PUR/FSB SCO SH - Sensor/actuator cable 1518478
-
SAC-8P-MR SCO/.../... - Sensor/actuator cable 1523654
-
SAC-8P-MR-FS SCO/.../... - Sensor/actuator cable 1552191
-
SAC-8P-MS-FR SCO/.../... - Sensor/actuator cable 1523696
-
SAC-8P-MR-FR SCO/.../... - Sensor/actuator cable 1552201
-
SACC-M12MS-8CON-PG9-M - Connector 1513334
-
SACC-M12MS-8CON-PG 9-SH - Connector 1511857
Your advantages
Flexible power supply concept
SPEEDCON fast locking system
Short-circuit and overload protection
Diagnostic and status indicators
Consistent connection via M12 connectors
PHOENIX CONTACT Middle East FZ LLC
1201N-1206N, Dubai Science Park Towers - North, P.O. Box 345002, Dubai, United Arab Emirates