PLC-V8R/PT-24DC/EM
-
Extension module
1487020
Extension module with 16 I/Os, for plug-in connection to 8 PLC-INTERFACE terminal blocks for extending the PLC-V8R.../BM base module (max. 3 extension modules per base module). Approved in accordance with ATEX/IECEx (Zone 2) and Ex Zone Class I, Zone 2 (Div. 2).
This product needs further products for operation.
Mandatory accessories
Free download available.
Downloads
Product details
| Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
| Notes on operation | Please note any deviating technical data, installation directives, and approvals for the PLC-INTERFACE modules, which can be found with the respective item. |
| Note regarding laboratory testing | Environmental tests (vibration and shock): Upright non-perforated DIN rail, DIN rail screw-fastened every 10 cm, in-line mounting including upright and screw-fastenable end brackets |
| Note on application | As things stand now, we are preparing the product so that, as of December 11, 2027, it will comply with the requirements of the EU Cyber Resilience Act (CRA) based on the information currently available regarding the CRA. |
| Product type | Extension module |
| Product family | PLC-INTERFACE |
| Operating mode | 100% operating factor |
| Insulation characteristics: Air clearances and creepage distances | |
| Insulation | Functional insulation |
| Overvoltage category | II |
| Pollution degree | 2 |
| Power consumption | 450 mW (no other inputs and outputs active) |
| ≤ 850 mW (no other inputs and outputs active) | |
| 2.5 W (IN0 ... IN7 and relay active) | |
| ≤ 4.3 W (IN0 ... IN7 and relay active) | |
| Air clearances and creepage distances | |
| Rated insulation voltage | 50 V |
| Rated surge voltage | 0.5 kV |
| Supply | |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC |
| Input current | 16 mA (no other inputs and outputs active) |
| ≤ 22 mA (no other inputs and outputs active) | |
| 80 mA (IN0 ... IN7 and relay active) | |
| ≤ 130 mA (IN0 ... IN7 and relay active) | |
| Protective circuit | Reverse polarity protection |
| Surge protection | |
| Digital inputs | |
| Number of inputs | 8 (4 configurable as analog) |
| Description of the input | EN 61131-2, type 3 |
| Input voltage | 24 V DC |
| Typical current consumption | 2.4 mA (per channel, IN0 ... IN3) |
| 2.8 mA (per channel, IN4 ... IN7) | |
| Input voltage range "0" signal | 0 V DC ... 5 V DC |
| Input voltage range "1" signal | 11 V DC ... 30 V DC |
| Process data update | < 1 ms (Local bus asynchronous) |
| Status display | LED (yellow) |
| Digital inputs via PLC-INTERFACE plug-in contacts | |
| Number of inputs | ≤ 8 |
| Process data update | < 1.5 ms (Local bus asynchronous) |
| Analog inputs | |
| Number of inputs | ≤ 4 (IN4, IN5, IN6, and IN7 are configurable as analog) |
| Input voltage range | 0 V DC ... 10 V DC |
| Temperature coefficients | ± 0.01 %/K |
| <± 0.06 %/K | |
| Measuring error | 1 % (From the range end value) |
| <± 3 % (From the range end value) | |
| Input impedance | see diagram |
| Resolution | 10 bit |
| LSB | 10 mV |
| Permissible voltage | 0 V ... 30 V |
| Cable length | < 10 m |
| Input filter | 1st order |
| Limit frequency (3 dB) | 150 Hz (The system is designed to record static voltage signals. With dynamic voltage signals, aliasing can occur.) |
| Process data update | ≤ 10 ms (Local bus asynchronous) |
| Analog inputs via PLC-INTERFACE plug-in contacts | |
| Number of inputs | ≤ 8 |
| Process data update | < 1 s (Local bus asynchronous) |
| Digital outputs via PLC-INTERFACE plug-in contacts | |
| Number of outputs | ≤ 8 |
| Process data update | < 1 ms (Local bus asynchronous) |
| Analog outputs via PLC-INTERFACE plug-in contacts | |
| Process data update | < 500 ms (Local bus asynchronous) |
| COMBICON connection | |
| Connection method | Push-in connection |
| Stripping length | 9 mm |
| Number of positions | 10 |
| Note | Device supply and 8 x inputs |
| Conductor cross-section rigid | 0.14 mm² ... 1.5 mm² |
| Conductor cross-section flexible | 0.14 mm² ... 1.5 mm² |
| 0.25 mm² ... 1.5 mm² (Ferrule without plastic sleeve) | |
| 0.25 mm² ... 0.5 mm² (Ferrule with plastic sleeve) | |
| Conductor cross-section AWG | 26 ... 16 |
| Interface to other extension modules | |
| Connection method | Insulation displacement connection |
| Number of connections | 1 |
| Number of positions | 4 |
| Local bus | |
| Designation | Local bus |
| Cycle time (1 Erweiterungsmodul) | 5 ms |
| ≤ 12 ms | |
| Cycle time (2 Erweiterungsmodule) | 15 ms |
| ≤ 35 ms | |
| Cycle time (3 Erweiterungsmodule) | 28 ms |
| ≤ 65 ms | |
| PLC-INTERFACE plug-in contacts | |
| Designation | PLC-INTERFACE plug-in contacts |
| Operating voltage display | Green LED |
| Item dimensions | |
| Width | 50 mm |
| Height | 49 mm |
| Depth | 83 mm |
| Width | 50 mm |
| Height | 111 mm |
| Depth | 87 mm |
| Ambient conditions | |
| Degree of protection (Housing) | IP20 |
| Degree of protection (Connection terminal blocks) | IP20 |
| Degree of protection (Installation location) | ≥ IP54 |
| Ambient temperature (operation) | -40 °C ... 60 °C (observe derating) |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Altitude | ≤ 2000 m |
| ≤ 3000 m (≤ 52 °C) | |
| ≤ 4000 m (≤ 46 °C) | |
| Max. permissible relative humidity (operation) | 95 % (non-condensing) |
| Shock (operation) | 15g (11 ms, 3 axes) (EN 60068-2-27) |
| Vibration (operation) | 5g (5 Hz ... 150 Hz, 3 axes) (EN 60068-2-6) |
| Interference emission | EN 55016-2-3 (residential area) |
| Noise immunity (against electrostatic discharge) | EN 61000-4-2: ±6 kV (contact discharge) |
| EN 61000-4-2: ±8 kV (air discharge) | |
| Noise immunity (against electromagnetic fields) | EN 61000-4-3: 10 V/m |
| Noise immunity (against conducted high frequency) | EN 61000-4-6: 10 V |
| Noise immunity (against fast transients (bursts)) | EN 61000-4-4: ±2 kV supply and signal lines |
| Noise immunity (against surge current loads (surges)) | EN 61000-4-5: 0.5 kV symmetrical on supply line |
| EN 61000-4-5: 1 kV asymmetrical on supply line | |
| EN 61000-4-5: 1 kV asymmetrical on signal line |
| Air clearances and creepage distances | |
| Standards/regulations | IEC/EN/UL 61010-2-201 |
| EN IEC 60664-1 | |
| Standards/regulations | DIN EN 61131-2 |
| Mounting type | Plug-in mounting |
| Assembly note | can be plugged onto 8 x PLC-INTERFACE terminal blocks |
| Mounting position | horizontal |
| Item number | 1487020 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Sales key | ***** |
| Product key | DK62R1 |
| GTIN | 4063151929183 |
| Weight per piece (including packing) | 90.3 g |
| Weight per piece (excluding packing) | 90.3 g |
| Customs tariff number | 85371098 |
| Country of origin | DE |
ECLASS
| ECLASS-13.0 | 27242602 |
| ECLASS-15.0 | 27242602 |
ETIM
| ETIM 10.0 | EC001597 |
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes |
| Exemption | 7(a), 7(c)-I |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
| EF3.1 Climate Change | |
| CO2e kg | 8.897 kg CO2e |
Compatible products
-
PLC-RPT- 24DC/1/CB1-6 - Relay module 1328360
-
PLC-RSC- 24DC/1/CB1-6 - Relay module 1328357
-
PLC-BPT- 24DC/21 - Relay base 2900445
-
PLC-BSC- 24DC/21 - Relay base 2966016
-
PLC-BPT- 24DC/ 1/SEN - Relay base 2900262
-
PLC-BSC- 24DC/ 1/SEN - Relay base 2966061
-
PLC-RSC- 24DC/21 - Relay module 2966171
-
PLC-RPT- 24DC/21 - Relay module 2900299
-
PLC-RSC- 24DC/21AU - Relay module 2966265
-
PLC-RPT- 24DC/21AU - Relay module 2900306
-
PLC-RSC- 24DC/ 1/ACT - Relay module 2966210
-
PLC-RPT- 24DC/ 1/ACT - Relay module 2900312
-
PLC-RSC- 24DC/21/MS - Relay module 2909649
-
PLC-RPT- 24DC/21/MS - Relay module 2909667
-
PLC-RSC- 24DC/21AU/MS - Relay module 2909655
-
PLC-RPT- 24DC/21AU/MS - Relay module 2909672
-
PLC-RSC- 24DC/ 1/MS/ACT - Relay module 2909661
-
PLC-RPT- 24DC/ 1/MS/ACT - Relay module 2909677
-
PLC-RSC- 24UC/ 1/S/H - Switch 2982236
-
PLC-RPT- 24UC/ 1/S/H - Switch 2900328
-
PLC-RSC-24DC/21/EX - Relay module 2909524
-
PLC-RPT-24DC/21/EX - Relay module 2909528
-
PLC-OSC- 24DC/ 48DC/100 - Solid-state relay module 2966728
-
PLC-OPT- 24DC/ 48DC/100 - Solid-state relay module 2900352
-
PLC-OPT- 24DC/ 24DC/2 - Solid-state relay module 2900364
-
PLC-OSC- 24DC/ 24DC/ 2 - Solid-state relay module 2966634
-
PLC-OPT- 24DC/230AC/1 - Solid-state relay module 2900369
-
PLC-OSC- 24DC/230AC/ 1 - Solid-state relay module 2967840
-
PLC-OSC- 24DC/ 24DC/ 2/ACT - Solid-state relay module 2966676
-
PLC-OPT- 24DC/ 24DC/2/ACT - Solid-state relay module 2900376
-
PLC-OSC- 24DC/230AC/ 1/ACT - Solid-state relay module 2967947
-
PLC-OPT- 24DC/300DC/1 - Solid-state relay module 2900383
-
PLC-OSC- 24DC/300DC/ 1 - Solid-state relay module 2980678
-
PLC-OSC- 24DC/ 24DC/ 10/R - Solid-state relay module 2982702
-
PLC-OPT- 24DC/ 24DC/10/R - Solid-state relay module 2900398
-
PLC-OSC- 24DC/ 48DC/500/W - Solid-state relay module 2980636
-
PLC-OPT- 24DC/ 48DC/500/W - Solid-state relay module 2900378
-
PLC-OSC- 24DC/TTL - Solid-state relay module 2982728
-
PLC-OPT- 24DC/TTL - Solid-state relay module 2900363
-
PLC-OSC- 24DC/ 48DC/100/C1D2 - Optocoupler 5603261
-
PLC-OSC- 24DC/ 24DC/ 2/C1D2 - Optocoupler 5603260
-
PLC-RSC- 24DC/ 1AU/SEN - Relay module 2966317
-
PLC-RPT- 24DC/ 1AU/SEN - Relay module 2900313
-
PLC-RSC-120UC/ 1AU/SEN - Relay module 2966320
-
PLC-RPT-120UC/ 1AU/SEN - Relay module 2900314
-
PLC-RSC-230UC/ 1AU/SEN - Relay module 2966333
-
PLC-RPT-230UC/ 1AU/SEN - Relay module 2900315
-
PLC-RSC- 24DC/ 1AU/MS/SEN - Relay module 2909663
-
PLC-RPT- 24DC/ 1AU/MS/SEN - Relay module 2909678
-
PLC-RPT-230UC/ 1AU/MS/SEN - Relay module 2909680
-
PLC-OPT-24DC/V8C/SEN - Solid-state relay module 2908172
-
PLC-OPT-120UC/V8C/SEN - Solid-state relay module 2908174
-
PLC-OPT-230UC/V8C/SEN - Solid-state relay module 2908176
-
PLC-APT-UI-IN - Analog module 2906917
-
PLC-APT-PT100-IN - Analog module 2906919
-
PLC-APT-UI-OUT - Analog module 2906921
PHOENIX CONTACT (SEA) Pte Ltd
80 Bendemeer Road, #09-01A | #10-02 (Reception), Singapore 339949