SYS-SET/ 1
   - 
  Type 1+2 special combined lightning current and surge arrester
    
      2880448
      
      
    
  
      Plug-in lightning and surge arrester combination, in accordance with Type 1+2/Class I+II, for 3-phase power supply networks, with separate N and PE (L1, L2, L3, PE, N).
Product details
| Product type | Arrester combination | 
| Product family | SEC Family | 
| IEC test classification | I + II | 
| T1 + T2 | |
| I | |
| EN type | T1 + T2 | 
| IEC power supply system | TN-S | 
| TT | |
| Type | DIN rail module, two-section, divisible | 
| Number of positions | 4 | 
| Surge protection fault message | Optical, remote indicator contact | 
| Insulation characteristics | |
| Overvoltage category | III | 
| Pollution degree | 2 | 
| Nominal frequency fN | 50 Hz (60 Hz) | 
| Indicator/remote signaling | |
| Connection name | Remote fault indicator contact | 
| Switching function | Changeover contact | 
| Operating voltage | 12 V AC ... 250 V AC | 
| 125 V DC (200 mA DC) | |
| Operating current | 10 mA AC ... 1 A AC | 
| 1 A DC (30 V DC) | |
| Connection method | Screw connection | 
| Screw thread | M5 | 
| Tightening torque | 4.5 Nm | 
| Stripping length | 18 mm | 
| Conductor cross-section flexible | 2.5 mm² ... 35 mm² | 
| Conductor cross-section rigid | 2.5 mm² ... 35 mm² | 
| Conductor cross-section AWG | 13 ... 2 | 
| Connection method | Fork-type cable lug | 
| Conductor cross-section flexible | 1.5 mm² ... 16 mm² | 
| Remote fault indicator contact | |
| Connection method | Plug-in/screw connection via COMBICON | 
| Screw thread | M2 | 
| Tightening torque | 0.25 Nm | 
| Stripping length | 7 mm | 
| Conductor cross-section flexible | 0.14 mm² ... 1.5 mm² | 
| Conductor cross-section rigid | 0.14 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 28 ... 16 | 
| Dimensional drawing |  | 
| Width | 142.4 mm | 
| Height | 95.2 mm | 
| Depth | 74.5 mm (incl. DIN rail 7.5 mm) | 
| Horizontal pitch | 8 Div. | 
| Color (Male connector) | light gray (RAL 7035) | 
| Color (Base element) | gray (RAL 7042) | 
| Flammability rating according to UL 94 | V-0 | 
| CTI value of material | 600 | 
| Insulating material | PA6.6-FR 20% GF | 
| PBT-FR | |
| Material group | I | 
| Housing material | PA 6.6-FR 20 % GF | 
| PBT-FR | 
| Mechanical data | |
| Open side panel | No | 
| Mode of protection | L-N | 
| L-PE | |
| N-PE | |
| Direction of action | 3L-N & N-PE | 
| Nominal voltage UN | 240/415 V AC (TN-S) | 
| 240/415 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) | 
| Maximum continuous operating voltage UC | 350 V AC | 
| Rated load current IL | 125 A (< 55 °C) | 
| Protective conductor current IPE | ≤ 0.01 mA | 
| Nominal discharge current In (8/20) µs (L-N) | 25 kA | 
| Nominal discharge current In (8/20) µs (L-PE) | 25 kA | 
| Nominal discharge current In (8/20) µs (N-PE) | 100 kA | 
| Impulse discharge current (10/350) µs (L-N), charge | 12.5 As | 
| Impulse discharge current (10/350) µs (L-N), specific energy | 160 kJ/Ω | 
| Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 25 kA | 
| Impulse discharge current (10/350) µs (L-PE), charge | 12.5 As | 
| Impulse discharge current (10/350) µs (L-PE), specific energy | 160 kJ/Ω | 
| Impulse discharge current (10/350) µs (L-PE), peak current value Iimp | 25 kA | 
| Impulse discharge current (10/350) µs (N-PE), charge | 50 As | 
| Impulse discharge current (10/350) µs (N-PE), specific energy | 2500 kJ/Ω | 
| Impulse discharge current (10/350) µs (N-PE), peak current value Iimp | 100 kA | 
| Follow current quenching capacity Ifi (L-N) | 25 kA (264 V AC) | 
| 3 kA (350 V AC) | |
| Follow current interrupt rating Ifi (N-PE) | 100 A (350 V AC) | 
| Short-circuit current rating ISCCR | 25 kA (264 V AC) | 
| 3 kA (350 V AC) | |
| Voltage protection level Up (L-N) | ≤ 1.5 kV | 
| Voltage protection level Up (L-PE) | ≤ 2.2 kV | 
| Voltage protection level Up (N-PE) | ≤ 1.5 kV | 
| Residual voltage Ures (L-N) | ≤ 1.5 kV (at In) | 
| ≤ 1.2 kV (at 10 kA) | |
| ≤ 1 kV (at 5 kA) | |
| ≤ 0.9 kV (at 3 kA) | |
| Residual voltage Ures (L-PE) | ≤ 2.2 kV (at In) | 
| ≤ 2 kV (at 10 kA) | |
| ≤ 1.8 kV (at 5 kA) | |
| ≤ 1.6 kV (at 3 kA) | |
| Residual voltage Ures (N-PE) | ≤ 1.5 kV (at In) | 
| ≤ 1 kV (at 10 kA) | |
| ≤ 0.9 kV (at 5 kA) | |
| ≤ 0.8 kV (at 3 kA) | |
| TOV behavior at UT (L-N) | 415 V AC (5 s / withstand mode) | 
| 457 V AC (120 min / safe failure mode) | |
| TOV behavior at UT (N-PE) | 1200 V AC (200 ms / withstand mode) | 
| Response time tA (L-N) | ≤ 25 ns | 
| Response time tA (N-PE) | ≤ 100 ns | 
| Max. backup fuse with V-type through wiring | 125 A (gG) | 
| Max. backup fuse with branch wiring | 315 A (gG) | 
| Additional technical data | |
| Maximum discharge current Imax (8/20) µs | 100 kA | 
| Ambient conditions | |
| Degree of protection | IP20 (only when all terminal points are used) | 
| Ambient temperature (operation) | -40 °C ... 80 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 80 °C | 
| Altitude | ≤ 2000 m (amsl) | 
| Permissible humidity (operation) | 5 % ... 95 % | 
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) | 
| Vibration (operation) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) | 
| UL specifications | |
| Maximum continuous operating voltage MCOV (L-L) | 528 V AC | 
| Maximum continuous operating voltage MCOV (L-N) | 264 V AC | 
| Maximum continuous operating voltage MCOV (L-G) | 264 V AC | 
| Maximum continuous operating voltage MCOV (N-G) | 350 V AC | 
| Short-circuit current rating (SCCR) | 50 kA | 
| Voltage protection rating VPR (L-L) | 2000 V | 
| Voltage protection rating VPR (L-N) | 1200 V | 
| Voltage protection rating VPR (L-G) | 1500 V | 
| Voltage protection rating VPR (N-G) | 1200 V | 
| Nominal discharge current In | 20 kA | 
| Mode of protection | L-L | 
| L-N | |
| L-G | |
| N-G | |
| Nominal voltage | 240/415 V AC | 
| Rated load current IL | 50 A | 
| Power distribution system | Wye | 
| Nominal frequency | 50/60 Hz | 
| SPD Type | 2CA | 
| UL indicator/remote signaling | |
| Operating voltage | 125 V AC | 
| AC operating current | 1 A AC | 
| UL connection data | |
| Tightening torque | 40 lbf-in. | 
| Conductor cross-section AWG | 3 ... 2 | 
| Standards/specifications | IEC 61643-11 | 
| Note | 2011 | 
| EN 61643-11 | |
| Standards/specifications | EN 61643-11 | 
| Note | 2012 | 
| Mounting type | DIN rail: 35 mm | 
| Item number | 2880448 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | CL1 | 
| Product key | CL1243 | 
| GTIN | 4017918981303 | 
| Weight per piece (including packing) | 1,290.5 g | 
| Weight per piece (excluding packing) | 1,184 g | 
| Customs tariff number | 85363030 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27171204 | 
| ECLASS-15.0 | 27171204 | 
ETIM
| ETIM 9.0 | EC001457 | 
UNSPSC
| UNSPSC 21.0 | 39121600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 6(c) | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
Compatible products
- 
    
      CLIPFIX 35 - End bracket 3022218
- 
    
      EML (20XE)R - Label 0803452
- 
    
      EML (20XE)R YE - Label 0803453
- 
    
      ZBN 18:UNBEDRUCKT - Zack marker strip 2809128
- 
    
      ZBN 18,LGS:L1-N,ERDE - Marker for terminal blocks 2749576
- 
    
      ZBN 18,LGS:ERDE - Marker for terminal blocks 2749589
- 
    
      ZBFM 5/WH:UNBEDRUCKT - Flat zack marker sheet 0803595
- 
    
      ZBN 18 CUS - Zack marker strip 0825059
- 
    
      X-PEN 0,35 - Marker pen 0811228
- 
    
      SZK PZ2 VDE - Screwdriver 1206463
- 
    
      FLT-SEC-T1-350/25-P - Type 1/2 surge protection plug 2905471
- 
    
      VAL-SEC-T2-350-P - Type 2 surge protection plug 2905346
- 
    
      FLT-SEC-P-T1-N/PE-350/100-P - Type 1 surge protection plug 2905473
PHOENIX CONTACT Trading LLC
        
        Riyadh Moon Tower, 7586 King Fahed Branch Road, Ar Rahmaniyah, ZIP Code: 12341-4119, Riyadh, Kingdom of Saudi Arabia